PF Power Fittings Technical Reference

JGHD High Voltage Cable Fixing Clamp

Models: JGHD-1 – JGHD-7 · Cable OD: 55–166 mm · Bolting: M12 on every size

JGHD High Voltage Cable Fixing Clamp

The Heavy Version of the JGH

Same job, more steel. The JGHD carries five dimensions where the JGH carries four — L, W, H and L1 — and the extra one is the height H, 100 to 215 mm.

That H is the difference between the two families. The JGH is a flat two-bolt clamp that sits against a bracket; the JGHD stands the cable off the bracket by 100 to 215 mm, which is what you need when the cable has to clear a structure edge, another cable, or the termination body itself.

  • L — overall length, 155 to 280 mm.
  • W — body width, 75 to 100 mm.
  • H — standoff height, 100 to 215 mm.
  • L1 — the jaw opening, 125 to 230 mm.
  • M 12 — one bolt size across all seven rows.

That last point is unusual: every JGHD closes on an M12. Where the JGH steps M10 → M12 → M14 with cable size, the heavy clamp uses M12 on a 55 mm cable and on a 166 mm cable alike. Two M12 bolts are enough for the whole range because the load path is through the body, not the bolts.

Note the notation: the JGH column reads 2-M10, the JGHD column reads plain 12. It is the same thing — two M12 bolts — but a system that parses M12 will not match 12.

Where The Ranges Meet

Read the cable ranges in order:

5565, 6580, 80100, 100125, **126136**, 136150, 140~166

Two places where they do not simply tile:

  • JGHD-4 ends at 125 and JGHD-5 starts at 126. The rows are printed in whole millimetres; a cable measuring over 125.0 mm takes JGHD-5, and 125.0 or under takes JGHD-4.
  • Between JGHD-6 and JGHD-7 the ranges overlap by 10 mm. A 145 mm cable is covered by both.

For the overlap the choice is the H: JGHD-6 stands 200 mm off the bracket, JGHD-7 stands 215 mm. Take the one that matches your clearance and ignore the overlap.

H Is Roughly L1 Minus 20

Across the seven rows, H runs 15 to 30 mm below L1 — 100 against 125, 140 against 162, 215 against 230.

That is the geometry of the casting: the jaw’s centre sits about 20 mm inside the top of the standoff. It is a useful check when you are laying out a bracket from a photograph, because it means H is not an independent choice — if you need more standoff you take the next size up, which also brings a bigger jaw.

Technical Parameters

JGHD High Voltage Cable Fixing Clamp JGHD High Voltage Cable Fixing Clamp

ModelApplicable Cable Outer Diameter (mm)Main Dimensions (mm)
LWHL1M
JGHD-155~651557510012512
JGHD-265~801707512014012
JGHD-380~1001928014016212
JGHD-4100~1252158016518512
JGHD-5126~13624410018021012
JGHD-6136~15025010020021512
JGHD-7140~16628010021523012

The flat clamp for the same cables: JGH cable fixing clamp. The wide-body version: JGP HV cable fixing clamp. Spacing and support for bundled cable: JGW cable fixing clamp.

Note: H is the standoff height, the dimension the JGH does not have, and it runs 100 to 215 mm. Every size uses M12 (printed 12 here, 2-M12 elsewhere). JGHD-4 takes cable to 125 mm and JGHD-5 from 126; JGHD-6 and JGHD-7 overlap between 140 and 150, and there you pick on H — 200 against 215 mm.

Sizing data behind this page

A cable fixing clamp is chosen by the cable's overall diameter and sheath, not by its conductor area. The overall diameters for the cables in this catalogue are in: