Cable and Aerial Insulated Cable Tables
11 + 12 rows · 10 to 300 mm² · copper, aluminium and aluminium alloy cores
Two tables for insulated product rather than bare conductor. The first is a single-core cable structure table; the second is the 10 kV and 35 kV aerial insulated cable that covered-conductor clamps and insulation covers are selected against.
They describe the same conductors. The resistance and breaking load columns for a given section are identical between the two tables — at 240 mm² both print 0.0777, 0.125 and 0.145 Ω/km and 79,823, 34,679 and 60,329 N — because both are built on the same compacted strand. What differs is the insulation system around it.
Single-Core Cable Structure
| Conductor Nominal Section (mm2) | Min Single Wire Count in Compact Round Conductor | Conductor Outer Dia. (Ref.) (mm) | Nominal Insulation Thickness (mm) | Single Core Cable Avg Outer Dia. Upper Limit (mm) | 20°C Conductor Resistance (Ω/km) Not Greater Than | Min Insulation Resistance at Rated Temp. (MΩ·km) | Cable Breaking Load (N) Not Less Than | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Copper Core | Aluminum Core & Aluminum Alloy Core | Copper Core | Aluminum Core | Aluminum Alloy Core | 70℃ | 90℃ | Hard Copper Core | Aluminum Core | Aluminum Alloy Core | |||||
| Hard Copper | Soft Copper | |||||||||||||
| 10 | 6 | 6 | 3.8 | 1.0 | 6.5 | 1.906 | 1.83 | 3.08 | 3.574 | 0.0067 | 0.67 | 3471 | 1650 | 2514 |
| 16 | 6 | 6 | 4.8 | 1.2 | 8.0 | 1.198 | 1.15 | 1.91 | 2.217 | 0.0065 | 0.65 | 5486 | 2512 | 4022 |
| 25 | 6 | 6 | 6.0 | 1.2 | 9.4 | 0.749 | 0.727 | 1.20 | 1.303 | 0.0054 | 0.54 | 8465 | 3762 | 6284 |
| 35 | 6 | 6 | 7.0 | 1.4 | 11.0 | 0.540 | 0.524 | 0.868 | 1.007 | 0.0054 | 0.46 | 11731 | 5177 | 8800 |
| 50 | 6 | 6 | 8.4 | 1.4 | 12.3 | 0.399 | 0.387 | 0.641 | 0.744 | 0.0046 | 0.40 | 16502 | 7011 | 12566 |
| 70 | 12 | 12 | 10.0 | 1.4 | 14.1 | 0.276 | 0.268 | 0.443 | 0.514 | 0.0040 | 0.39 | 23461 | 10354 | 17596 |
| 95 | 15 | 15 | 11.6 | 1.6 | 16.5 | 0.199 | 0.193 | 0.320 | 0.371 | 0.0039 | 0.35 | 31759 | 13727 | 23880 |
| 120 | 15 | 18 | 13.0 | 1.6 | 18.1 | 0.158 | 0.153 | 0.253 | 0.294 | 0.0035 | 0.35 | 39911 | 17339 | 30164 |
| 150 | 15 | 18 | 14.6 | 1.8 | 20.2 | 0.128 | - | 0.206 | 0.239 | 0.0035 | 0.35 | 49505 | 21033 | 37706 |
| 185 | 30 | 30 | 16.2 | 2.0 | 22.5 | 0.1021 | - | 0.164 | 0.190 | 0.0035 | 0.35 | 61846 | 26732 | 46503 |
| 240 | 30 | 34 | 18.4 | 2.2 | 25.6 | 0.0777 | - | 0.125 | 0.145 | 0.0034 | 0.34 | 79823 | 34679 | 60329 |
10 kV and 35 kV Aerial Insulated Cable
| Conductor Nominal Section (mm2) | Min Single Wire Count in Conductor | Conductor Outer Dia. (Ref.) (mm) | Conductor Shield Min Thickness (Approx.) (mm) | Nominal Insulation Thickness (mm) | Insulation Shield Nominal Thickness (mm) | 20°C Conductor Resistance (Ω/km) Not Greater Than | Cable Breaking Load (N) Not Less Than | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 10kV | 35kV | 10kV | 35kV | 10kV | 35kV | Hard Copper Core | Soft Copper Core | Aluminum Core | Aluminum Alloy Core | Hard Copper Core | Aluminum Core | Aluminum Alloy Core | ||||
| 10 | 6 | 3.8 | 0.5 | - | - | 3.4 | - | - | - | - | 1.830 | 3.080 | - | - | - | - |
| 16 | 6 | 4.8 | 0.5 | - | - | 3.4 | - | - | - | - | 1.150 | 1.910 | - | - | - | - |
| 25 | 6 | 6.0 | 0.5 | - | 2.5 | 3.4 | - | 1.0 | - | 0.749 | 0.727 | 1.200 | 1.393 | 8465 | 3762 | 6284 |
| 35 | 6 | 7.0 | 0.5 | - | 2.5 | 3.4 | - | 1.0 | - | 0.540 | 0.524 | 0.868 | 1.007 | 11731 | 5177 | 8800 |
| 50 | 6 | 8.3 | 0.5 | 0.8 | 2.5 | 3.4 | 9.3 | 1.0 | 1.5 | 0.399 | 0.387 | 0.641 | 0.744 | 16502 | 7011 | 12569 |
| 70 | 12 | 10.0 | 0.5 | 0.8 | 2.5 | 3.4 | 9.3 | 1.0 | 1.5 | 0.276 | 0.268 | 0.443 | 0.514 | 23461 | 10354 | 17596 |
| 95 | 15 | 11.6 | 0.6 | 0.8 | 2.5 | 3.4 | 9.3 | 1.0 | 1.5 | 0.199 | 0.193 | 0.320 | 0.371 | 31759 | 13727 | 23880 |
| 120 | 18 | 13.0 | 0.6 | 0.8 | 2.5 | 3.4 | 9.3 | 1.0 | 1.5 | 0.158 | 0.153 | 0.253 | 0.294 | 39911 | 17339 | 30164 |
| 150 | 18 | 14.6 | 0.6 | 0.8 | 2.5 | 3.4 | 9.3 | 1.0 | 1.5 | 0.128 | - | 0.206 | 0.239 | 49505 | 21033 | 37706 |
| 185 | 30 | 16.2 | 0.6 | 0.8 | 2.5 | 3.4 | 9.3 | 1.0 | 1.5 | 0.1021 | - | 0.164 | 0.190 | 61846 | 26732 | 46503 |
| 240 | 34 | 18.4 | 0.6 | 0.8 | 2.5 | 3.4 | 9.3 | 1.0 | 1.5 | 0.0777 | - | 0.125 | 0.145 | 79823 | 34679 | 60329 |
| 300 | 34 | 20.6 | 0.6 | 0.8 | 2.5 | 3.4 | 9.3 | 1.0 | 1.5 | 0.0619 | - | 0.100 | 0.110 | 99788 | 43349 | 75411 |
What The First Table Says
- Three core metals in one row: hard copper, soft copper, aluminium and aluminium alloy, each with its own resistance. The copper pair sits in one group because hard and soft copper differ only in temper — 0.0777 against a dash at 240 mm², because soft copper is not offered above 120 mm².
- The single wire count is a minimum for a compacted conductor, not a stranding. 240 mm² shows 30 wires for copper and 34 for aluminium, which is the least number that may be used in a compacted round conductor, not a description of the lay.
- Insulation thickness runs 1.0 to 2.2 mm across the range, and the cable outer diameter 6.5 to 25.6 mm.
- The two insulation resistance columns are two compounds, not one compound at two temperatures. 0.0034 against 0.34 MΩ·km at 240 mm², 0.0067 against 0.67 at 10 mm² — a hundredfold step on every row. Insulation resistance roughly halves per 10 °C, so temperature cannot produce that; the material does. Read the left column as PVC at 70 °C and the right as cross-linked polyethylene at 90 °C, and quote the column that matches the cable you are buying.
What The Second Table Says, And Where It Is Ambiguous
The 10 kV and 35 kV constructions run side by side, with three layers for each voltage — conductor shield, insulation, insulation shield.
- The 10 kV head spans two insulation thicknesses, 2.5 mm and 3.4 mm. The 2.5 mm column is empty at 10 and 16 mm² and filled from 25 mm² up, so it is the reduced-wall 10 kV build, offered from 25 mm²; the 3.4 mm column is the standard wall and is filled on all twelve rows. Quote the wall with the size — 2.5 and 3.4 mm are different cables at the same voltage.
- The 35 kV construction is not offered below 50 mm². Conductor shield, insulation and insulation shield are all blank on the first four rows and filled from 50 mm², which is why the 9.3 mm column starts there.
- The two tables round the same strand differently by a tenth of a millimetre. 50 mm² is 8.4 mm in the cable table and 8.3 mm in the aerial table. For a clamp bore, work to the cable maker’s figure for the drum you are installing.
- The breaking loads agree to within 3 N — 12,566 against 12,569 N on the alloy column at 50 mm². That is rounding, not a different conductor.
Why These Two Tables Matter To The Hardware
A covered-conductor clamp, a piercing connector and an insulation cover are all selected on the outside of the cable, not on the conductor section. That number is in these two tables and nowhere else in the appendix:
- the cable outer diameter, 6.5 to 25.6 mm in the first table;
- the insulation thickness, which decides whether a cover will close over the joint;
- the conductor shield and insulation shield, which decide whether the joint needs a stress control layer at all.
Selecting a cover from the conductor section alone is how a 25.6 mm cable ends up with a cover sized for a bare 240 mm² conductor.
Related Pages
Covers and clamps for these cables: PZ insulating cover range, JCD meter box clamp, JBLY parallel groove clamp. The bare conductors underneath: ACSR, AAC. Back to the designation reference.
Note: Two tables on the same compacted strand — resistance and breaking load agree cell for cell, within 3 N — with different insulation around it. The aerial table runs the 10 kV insulation as two columns, 2.5 mm from 25 mm² up and 3.4 mm on all twelve rows; the 2.5 mm option is the thin-wall 10 kV build. The 35 kV build starts at 50 mm². In the cable table the two insulation resistance columns are PVC at 70 °C and cross-linked polyethylene at 90 °C — a hundredfold apart on every row, which is the compound, not the temperature.