GSW Galvanised Steel Strand (GJ)
26 rows · 1×3, 1×7 and 1×19 · 1175 to 1570 N/mm² · YB/T 5004-2001
This is not a conductor. Galvanised steel strand carries no load current. It is the material for overhead earth wire, guy wires, messenger and stay strand, and for the tie and lashing work around a pole. The international name is GSW, galvanised steel wire strand, to ASTM A475 and BS 183; GJ is the GB designation under YB/T 5004-2001. It is on this page rather than filed under the conductors because the columns, the units and the basis of the breaking load column are all different from every other table here.
Anyone who needs a conductor and lands here has the wrong page: go to ACSR or AAC.
| structure | Steel Wire Dia.(mm) | Steel Stranded Conductor Dia.(mm) | Steel Stranded Conductor Cross-Section (mm2) | Nominal Tensile Strength (N/mm2) | Reference Weight(kg/100m) | ||||
|---|---|---|---|---|---|---|---|---|---|
| 1175 | 1270 | 1370 | 1470 | 1570 | |||||
| Steel Wire Breaking Load Sum, Not Less Than (kN) | |||||||||
| 1×3 | 2.9 | 6.2 | 19.82 | 23.29 | 25.17 | 27.15 | 29.14 | 31.12 | 15.99 |
| 1×3 | 3.20 | 6.4 | 24.13 | 28.35 | 30.65 | 33.06 | 35.47 | 37.88 | 19.47 |
| 1×3 | 3.50 | 7.5 | 28.86 | 33.91 | 36.65 | 39.54 | 42.43 | 45.31 | 23.29 |
| 1×3 | 4.00 | 8.6 | 37.70 | 44.30 | 47.88 | 51.65 | 55.42 | 59.19 | 30.42 |
| 1×7 | 1.00 | 3.0 | 5.50 | 6.46 | 6.98 | 7.54 | 8.08 | 8.64 | 4.37 |
| 1×7 | 1.20 | 3.6 | 7.92 | 9.31 | 10.06 | 10.85 | 11.64 | 12.43 | 6.29 |
| 1×7 | 1.40 | 4.2 | 10.78 | 12.67 | 13.69 | 14.77 | 15.85 | 16.92 | 8.56 |
| 1×7 | 1.60 | 4.8 | 14.07 | 16.53 | 17.87 | 19.28 | 20.68 | 22.09 | 11.17 |
| 1×7 | 1.80 | 5.4 | 17.81 | 20.93 | 22.62 | 24.40 | 26.18 | 27.96 | 14.14 |
| 1×7 | 2.00 | 6.0 | 21.99 | 25.84 | 29.73 | 30.13 | 32.32 | 34.52 | 17.46 |
| 1×7 | 2.30 | 6.9 | 29.08 | 34.17 | 36.93 | 39.84 | 42.75 | 45.66 | 23.09 |
| 1×7 | 2.60 | 7.8 | 37.17 | 43.60 | 47.20 | 50.92 | 54.63 | 58.35 | 29.51 |
| 1×7 | 2.90 | 8.7 | 46.24 | 54.33 | 58.72 | 63.35 | 67.97 | 72.60 | 36.71 |
| 1×7 | 3.20 | 9.6 | 56.30 | 66.15 | 71.50 | 77.13 | 82.76 | 88.39 | 44.70 |
| 1×7 | 3.50 | 10.5 | 67.35 | 79.14 | 85.85 | 92.27 | 99.00 | 105.74 | 53.48 |
| 1×7 | 3.80 | 11.4 | 79.39 | 93.28 | 100.82 | 108.76 | 116.70 | 124.64 | 63.04 |
| 1×7 | 4.00 | 12.0 | 87.96 | 103.35 | 111.71 | 120.50 | 129.30 | 138.10 | 69.84 |
| 1×19 | 1.60 | 8.0 | 38.20 | 44.88 | 48.51 | 52.33 | 56.15 | 59.97 | 30.40 |
| 1×19 | 1.80 | 9.0 | 48.35 | 56.81 | 61.40 | 66.24 | 71.07 | 75.91 | 38.49 |
| 1×19 | 2.00 | 10.0 | 59.69 | 70.14 | 75.81 | 81.78 | 87.74 | 93.71 | 47.51 |
| 1×19 | 2.30 | 11.5 | 78.94 | 92.75 | 100.25 | 108.15 | 116.04 | 123.94 | 62.84 |
| 1×19 | 2.60 | 13.0 | 100.88 | 118.53 | 128.12 | 138.20 | 148.29 | 158.38 | 80.30 |
| 1×19 | 2.90 | 14.5 | 125.50 | 147.46 | 159.38 | 171.93 | 184.48 | 197.03 | 99.90 |
| 1×19 | 3.20 | 16.0 | 152.81 | 179.55 | 194.06 | 209.35 | 224.63 | 239.91 | 121.64 |
| 1×19 | 3.50 | 17.5 | 182.80 | 214.79 | 232.16 | 250.44 | 268.72 | 287.00 | 145.51 |
| 1×19 | 4.00 | 20.0 | 238.76 | 280.54 | 303.23 | 327.10 | 350.98 | 374.86 | 190.05 |
Three Structures, Five Grades
The table is a matrix rather than a list. Down the side there are three structures — 1×3, 1×7 and 1×19 — and across the top five nominal tensile strengths: 1175, 1270, 1370, 1470 and 1570 N/mm².
- 1×3 — four rows, wire 2.90 to 4.00 mm, section 19.82 to 37.70 mm².
- 1×7 — thirteen rows, wire 1.00 to 4.00 mm, section 5.50 to 87.96 mm². This is the widest set on the page.
- 1×19 — nine rows, wire 1.60 to 4.00 mm, section 38.20 to 238.76 mm².
The same structure appears five times across, once per strength grade, with a different breaking load each time and the same weight. So the grade has to be chosen before the size. A 1×19 of 4.00 mm wire is 238.76 mm² and weighs 190.05 kg per 100 m whether it is 1175 or 1570 grade, but its breaking load runs from 280.54 to 374.86 kN — a third more for the same steel.
The Breaking Load Column Is A Sum, Not A Strand Rating
The sub-header says it in full: Steel Wire Breaking Load Sum, Not Less Than. That is the sum of the individual wire breaks, not the breaking load of the finished strand.
- 1×19 of 4.00 mm at 1175 grade: 238.76 mm² × 1175 N/mm² = 280.5 kN, and the table prints 280.54.
- The same row at 1570 grade: 238.76 × 1570 = 374.9 kN, printed 374.86.
The column is section times grade, exactly, on all 26 rows. A finished 19-wire strand does not reach the sum of its wires — it loses a few per cent to the helical lay and to the slight inequality of tension between layers — so this column is a material figure, not a guaranteed strand break. For a guy or an earth wire design, the derated value is what has to be used, and the page does not give it.
One Cell Does Not Fit The Rule
Every row follows section times grade except one: 1×7 of 2.00 mm wire at 1270 grade prints 29.73 kN.
- section 21.99 mm² × 1270 = 27.93 kN;
- the row above, 1.80 mm, gives 17.81 × 1270 = 22.62, printed 22.62;
- the row below, 2.30 mm, gives 29.08 × 1270 = 36.93, printed 36.93;
- and the same 2.00 mm row at 1370 prints 30.13, which is 21.99 × 1370 exactly.
So the 1270 cell has its last two digits transposed — 27.93 printed as 29.73. Use 27.93 kN for 1×7 × 2.00 at 1270 grade. It is the only cell on the page that fails the check.
Weight Is Per 100 Metres
The weight column reads kg/100m, not kg/km, and every other table in this appendix reads kg/km. The difference is a factor of ten and it is the easiest mistake to make on this page.
- 1×7 of 2.00 mm: 21.99 mm² × 7.85 = 172.6 kg/km = 17.26 kg per 100 m, printed 17.46.
- 1×19 of 4.00 mm: 238.76 × 7.85 = 1874 kg/km = 187.4 kg per 100 m, printed 190.05.
The printed weight runs 1.1 to 1.4 per cent above bare steel on every row, which is the zinc coating. That is consistent, so the column can be used — as long as the unit is read as 100 m.
What Is Missing
- No product code. There is no GJ-35, GJ-50 or GJ-70 column. The page identifies a strand by structure, wire diameter and grade, so a purchase order has to specify all three.
- No zinc coating mass in g/m², and no coating class A, B or C. The standard is named and the class is not.
- No lay length, no direction of lay.
- No drum length.
Related Pages
Hardware for earth wire and guys: GD attachment point fitting, QY and PQ towing plate, YL and YLP extension rod. The conductor tables: ACSR, AAC. Back to the designation reference.
Note: Twenty-six rows in three structures and five strength grades. This is not a conductor — it is earth wire, guy and messenger strand — and the breaking load column is the sum of the single wire breaks, not a finished-strand rating, so it cannot be used as a guaranteed break. Weight is per 100 metres here and per kilometre everywhere else in the appendix. Every cell equals section times grade except 1×7 × 2.00 at 1270 grade, which prints 29.73 for 27.93 kN.