PF Power Fittings Technical Reference

AACSR/AW Conductor (JLHA1/LB1A)

37 rows · 16 to 1250 mm² · GB/T 1179-1999

AACSR/AW is the international name: All Aluminium Alloy Conductor, Steel Reinforced, Aluminium-Clad. The GB/T 1179 designation JLHA1/LB1A names the two wires — LHA1 the aluminium alloy strand, LB1A the aluminium-clad steel. Not the same conductor as ACSR/AW, which has plain aluminium over an aluminium-clad core.

An aluminium alloy conductor over an aluminium-clad steel core. The core is steel with an aluminium cladding bonded to it, which keeps the tensile strength of steel without exposing a galvanised surface to the atmosphere — the reason the type is used on coastal lines and in industrial pollution.

The header is the most compressed in the appendix: three tiers, ending in a units row that separates sections in mm² from diameters in mm. Reading the first two header rows without the third is how a section gets mistaken for a diameter.

Specification No.Steel Ratio %AreaSingle Wire CountSingle Wire Dia.DiameterUnit Length Weight kg/kmRated Tensile Strength kN20°C DC Resistance Not Greater Than Ω/km
aluminum alloyAluminum Clad SteelTotalaluminum alloyAluminum Clad Steelaluminum alloyAluminum Clad SteelAluminum Clad SteelStranded
mm2mmmm
1616.717.72.9620.7611.941.941.945.8266.19.311.789
2516.727.74.6232.3612.422.422.427.28106.414.541.132
4016.744.37.3951.7613.073.073.079.21170.223.270.707
6316.769.811.681.4613.853.853.8511.6268.034.790.449
10016.711018.5129614.854.854.8514.6425.553.380.283
1255.61437.941511813.183.183.1815.9445.555.970.229
12516.313922.61512672.612.036.0816.5532.072.170.227
1605.618310.21931813.603.603.6018.0570.369.210.179
16016.317828.92062672.952.296.8818.7680.992.380.179
2005.522912.72411814.024.024.0220.1712.886.000.143
20016.322236.13582673.302.567.6920.9851.2115.40.142
2509.828227.73102274.042.256.7422.9961.7122.250.114
25016.327745.23232673.692.878.6023.41064.0141.50.114
3156.935924.63644573.192.126.3725.51154.6146.30.091
31516.334956.94062674.143.229.6526.21340.6178.380.090
4006.945631.54874573.592.397.1828.71466.1181.320.071
40013.044858.15065473.253.259.7529.31621.6215.220.071
4506.951335.45484573.812.547.6230.51649.4203.990.063
45013.050465.35695473.453.4510.331.01624.3240.80.063
5006.957039.46094574.012.688.0332.11832.6226.60.057
50013.056072.66325473.633.6310.932.72027.0259.00.057
5606.963844.16824574.252.838.5034.02052.6253.80.051
56012.762579.570754193.852.3111.534.82261.6293.00.051
5306.971549.67674574.513.009.0136.12309.1285.580.045
63012.770689.479554194.082.4512.236.72544.3329.60.045
7106.980955.98654574.783.199.5738.32602.3321.80.046
71012.779610189654194.332.6013.039.02867.4371.50.046
8004.391839.79587274.032.698.0640.32798.8336.70.036
8008.390675.69838473.713.7111.140.83010.0369.10.036
80012.7898114101054194.602.7813.641.43230.9416.60.035
9004.3103344.610777274.272.858.5542.73148.6378.890.032
9008.3102185.111068473.933.9311.843.23366.3415.20.031
10004.3114849.611977274.503.009.0145.03498.5420.90.028
11204.2128654.3134072194.771.919.5447.73912.3470.10.025
11208.11271104137584194.392.6313.248.34202.7524.70.025
12504.2143560.6149572195.042.0110.150.44366.4524.60.023
12508.11419116153584194.642.7813.951.04690.5585.60.023

Reading The Fourteen Columns

The header nests as follows:

  • Area spans three columns — aluminium alloy, aluminium-clad steel, total.
  • Single Wire Count spans two — the number of alloy wires and the number of clad steel wires.
  • Single Wire Dia. spans two — one diameter for each of those.
  • Diameter spans two — the core diameter and the stranded diameter. This is the pair most easily confused with the single-wire diameters next to it: for 1250 mm² the core is 13.9 mm and the finished conductor 51.0 mm, against single wires of 4.64 and 2.78 mm.

The last three columns are weight in kg/km, rated tensile strength in kN, and maximum DC resistance at 20 °C.

Steel Ratio Is Not Constant, And It Falls As The Conductor Grows

The steel ratio column takes twelve values between 4.2 and 16.7 per cent, and the pattern is inverse to size:

  • the smallest row, 16 mm², is 16.7 per cent steel — over a sixth of the metal is core;
  • the largest, 1250 mm², is 8.1 per cent;
  • the thinnest core in the table is 4.2 per cent, on a mid-range size.

So two conductors quoted at the same nominal section can have very different steel, and therefore very different breaking loads. The model number is the nominal section, and the ratio has to be read from its own column.

Strength Is Rated, Not Calculated

The column says Rated Tensile Strength, in kN, and the values run from 9.31 kN at 16 mm² to 585.6 kN at 1250 mm². That is a different quantity from the “calculated breaking load” printed on the ACSR and LJ pages, and the two should not be compared as if they were the same number.

  • The ACSR table gives a calculated break from the strand construction.
  • This table gives a rated value, which is what the standard guarantees rather than what the wires add up to.

For a line design the rated figure is the safe one, and it is the one to quote. For a comparison between the two conductor types, the calculation bases have to be reconciled first.

What The Table Does Not Carry

  • No current rating. The appendix’s only ampacity columns are on the heat-resistant table.
  • No modulus or expansion coefficient. LGKK is the only conductor here with those.
  • No cladding thickness. The aluminium layer on the core is the whole reason for the type, and its thickness is not a column.
  • No corrosion class. Coastal and industrial use is the application, and the table gives no exposure class to design against.

Sleeves for aluminium-clad steel: JY-BG splice sleeve. The ordinary steel-core conductor: ACSR LGJ table. The heat-resistant alloy version: NRLH58GJ and NRLH60GJ. Back to the designation reference.

Note: Thirty-seven rows, 16 to 1250 mm², under a three-tier header whose last row is units — sections in mm², diameters in mm. The Diameter group holds two columns, core and stranded, which sit next to two single-wire diameters and are easily confused with them. Steel ratio runs 4.2 to 16.7 per cent and falls as the conductor grows. Strength is a rated value in kN, not a calculated break, so it is not comparable with the ACSR column without reconciling the basis.