ACSR/AW Conductor Table, IEC 61089 Type A1/S1A
37 rows · 21 code numbers · 16 to 1250 mm² · plain aluminium over aluminium-clad steel · Table D.4
ACSR/AW is plain aluminium wires over an aluminium-clad steel core. GB/T 1179 writes it JL/LB1A; IEC 61089 writes it A1/S1A — A1 for hard-drawn aluminium, S1A for the clad steel core, and the slash means the two metals are stranded together rather than alloyed.
Two neighbours are easy to confuse with it, and neither is this conductor:
- ACSR — the same plain aluminium, but the core is hot-dip galvanised steel, A1 in IEC and LGJ in GB. The zinc is the difference: it is a coating that is consumed, and once it is gone the core rusts.
- AACSR/AW — the same clad core, but the outer layer is aluminium alloy, not plain aluminium. That is A2/S1A in IEC and JLHA1/LB1A in GB.
So the aluminium-clad core buys corrosion resistance at the coast and in industrial air, where a galvanised core has a service life measured in the zinc mass. It costs conductivity: the clad steel is a poorer conductor than the aluminium it displaces, and the steel ratio below decides how much.
| Code No. | Steel Ratio % | Al Area mm² | Steel Area mm² | Total Area mm² | Wires Al/St | Wire Dia Al/St mm | Core Dia mm | Conductor Dia mm | Mass kg/km | Rated Strength kN | DC Resistance at 20 °C Ω/km |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 16 | 17 | 16 | 2.67 | 18.7 | 6/1 | 1.84/1.84 | 1.84 | 5.53 | 64.6 | 6.06 | 1.7934 |
| 25 | 17 | 25 | 4.17 | 29.2 | 6/1 | 2.30/2.30 | 2.30 | 6.91 | 100.9 | 9.13 | 1.1478 |
| 40 | 17 | 40 | 6.67 | 46.7 | 6/1 | 2.91/2.91 | 2.91 | 8.74 | 161.5 | 14.40 | 0.7174 |
| 63 | 17 | 63 | 10.5 | 73.5 | 6/1 | 3.66/3.66 | 3.66 | 11.0 | 254.4 | 21.63 | 0.4555 |
| 100 | 17 | 100 | 16.7 | 117 | 6/1 | 4.61/4.61 | 4.61 | 13.8 | 403.8 | 34.33 | 0.2869 |
| 125 | 6 | 125 | 6.94 | 132 | 18/1 | 2.97/2.97 | 2.97 | 14.9 | 397.9 | 29.17 | 0.2304 |
| 125 | 16 | 125 | 20.4 | 145 | 26/7 | 2.47/1.92 | 5.77 | 15.7 | 503.9 | 45.69 | 0.2310 |
| 160 | 6 | 160 | 8.89 | 169 | 18/1 | 3.36/3.36 | 3.36 | 16.8 | 509.3 | 36.18 | 0.1800 |
| 160 | 16 | 160 | 26.1 | 186 | 26/7 | 2.80/2.18 | 6.53 | 17.7 | 644.9 | 57.69 | 0.1805 |
| 200 | 6 | 200 | 11.1 | 211 | 18/1 | 3.76/3.76 | 3.76 | 18.8 | 636.7 | 44.22 | 0.1440 |
| 200 | 16 | 200 | 32.6 | 233 | 26/7 | 3.13/2.43 | 7.30 | 19.8 | 806.2 | 70.13 | 0.1444 |
| 250 | 10 | 250 | 24.6 | 275 | 22/7 | 3.80/2.11 | 6.34 | 21.6 | 880.6 | 68.72 | 0.1154 |
| 250 | 16 | 250 | 40.7 | 291 | 26/7 | 3.50/2.72 | 8.16 | 22.2 | 1007.7 | 87.67 | 0.1155 |
| 315 | 7 | 315 | 21.8 | 337 | 45/7 | 2.99/1.99 | 5.97 | 23.9 | 1039.6 | 79.03 | 0.0917 |
| 315 | 16 | 315 | 51.3 | 366 | 26/7 | 3.93/3.05 | 9.16 | 24.9 | 1269.7 | 106.83 | 0.0917 |
| 400 | 7 | 400 | 27.7 | 428 | 45/7 | 3.36/2.24 | 6.73 | 26.9 | 1320.1 | 98.36 | 0.0722 |
| 400 | 13 | 400 | 51.9 | 452 | 54/7 | 3.07/3.07 | 9.21 | 27.6 | 1510.3 | 123.04 | 0.0723 |
| 450 | 7 | 450 | 31.1 | 481 | 45/7 | 3.57/2.38 | 7.14 | 28.5 | 1485.2 | 107.47 | 0.0642 |
| 450 | 13 | 450 | 58.3 | 508 | 54/7 | 3.26/3.26 | 9.77 | 29.3 | 1699.1 | 138.42 | 0.0643 |
| 500 | 7 | 500 | 34.6 | 535 | 45/7 | 3.76/2.51 | 7.52 | 30.1 | 1650.2 | 119.41 | 0.0578 |
| 500 | 13 | 500 | 64.8 | 565 | 54/7 | 3.43/3.43 | 10.3 | 30.9 | 1887.9 | 153.80 | 0.0578 |
| 560 | 7 | 560 | 38.7 | 599 | 45/7 | 3.98/2.65 | 7.96 | 31.8 | 1848.2 | 133.74 | 0.0516 |
| 560 | 13 | 560 | 70.9 | 631 | 54/19 | 3.63/2.18 | 10.9 | 32.7 | 2103.4 | 172.59 | 0.0516 |
| 630 | 7 | 630 | 43.6 | 674 | 45/7 | 4.22/2.81 | 8.44 | 33.8 | 2079.2 | 150.45 | 0.0459 |
| 630 | 13 | 630 | 79.8 | 710 | 54/19 | 3.85/2.31 | 11.6 | 34.7 | 2366.3 | 191.77 | 0.0459 |
| 710 | 7 | 710 | 49.1 | 759 | 45/7 | 4.48/2.99 | 8.96 | 35.9 | 2343.2 | 169.56 | 0.0407 |
| 710 | 13 | 710 | 89.9 | 800 | 54/19 | 4.09/2.45 | 12.3 | 36.8 | 2666.8 | 216.12 | 0.0407 |
| 800 | 4 | 800 | 34.6 | 835 | 72/7 | 3.76/2.51 | 7.52 | 37.6 | 2480.2 | 167.41 | 0.0361 |
| 800 | 8 | 800 | 66.7 | 867 | 84/7 | 3.48/3.48 | 10.4 | 38.3 | 2732.7 | 205.33 | 0.0362 |
| 800 | 13 | 800 | 101 | 901 | 54/19 | 4.34/2.61 | 13.0 | 39.1 | 3004.9 | 243.52 | 0.0362 |
| 900 | 4 | 900 | 38.9 | 939 | 72/7 | 3.99/2.66 | 7.98 | 39.9 | 2790.2 | 188.33 | 0.0321 |
| 900 | 8 | 900 | 75.0 | 975 | 84/7 | 3.69/3.69 | 11.1 | 40.6 | 3074.2 | 226.50 | 0.0322 |
| 1000 | 4 | 1000 | 43.2 | 1043 | 72/7 | 4.21/2.80 | 8.41 | 42.1 | 3100.3 | 209.26 | 0.0289 |
| 1120 | 4 | 1120 | 47.3 | 1167 | 72/19 | 4.45/1.78 | 8.90 | 44.5 | 3464.9 | 234.53 | 0.0258 |
| 1120 | 8 | 1120 | 91.2 | 1211 | 84/19 | 4.12/2.47 | 12.4 | 45.3 | 3811.5 | 283.17 | 0.0258 |
| 1250 | 8 | 1250 | 102 | 1352 | 84/19 | 4.35/2.61 | 13.1 | 47.9 | 4253.9 | 316.04 | 0.0232 |
| 1250 | 4 | 1250 | 52.8 | 1303 | 72/19 | 4.70/1.88 | 9.40 | 47.0 | 3867.1 | 261.75 | 0.0231 |
The Code Number Is Not The Section
The first column is not a section in square millimetres, even though it looks like one. IEC 61089 D.1.3 defines it as the equivalent conductive area of A1 aluminium — the section of hard-drawn aluminium that would have the same resistance. That is why 125-A1/S1A carries 124.5 mm² of aluminium, not 125, and why the total section is 145.
D.1.4 draws the consequence: conductors with the same code number have the same d.c. resistance, whatever their type, designation or stranding. The table keeps that promise to the fourth decimal. Multiply the resistance by the aluminium area and it lands between 28.7 and 29.0 on every one of the 37 rows:
| Row | Resistance Ω/km | Al area mm² | Product |
|---|---|---|---|
| 16-17 | 1.7934 | 16.0 | 28.69 |
| 125-6 | 0.2304 | 124.7 | 28.73 |
| 500-7 | 0.0578 | 499.7 | 28.88 |
| 1250-4 | 0.0231 | 1249.2 | 28.86 |
One number under the whole table, spread over a section range of 78 to 1. Buy on the code number and the resistance is fixed before you choose the steel ratio.
Steel Ratio Runs From 4 To 17 Per Cent
Eight ratios appear, and they are not one tidy series:
| Ratio | Rows | Code numbers |
|---|---|---|
| 17 % | 5 | 16, 25, 40, 63, 100 |
| 16 % | 5 | 125, 160, 200, 250, 315 |
| 13 % | 7 | 400, 450, 500, 560, 630, 710, 800 |
| 10 % | 1 | 250 |
| 8 % | 4 | 800, 900, 1120, 1250 |
| 7 % | 7 | 315, 400, 450, 500, 560, 630, 710 |
| 6 % | 3 | 125, 160, 200 |
| 4 % | 5 | 800, 900, 1000, 1120, 1250 |
Every code from 16 to 100 mm² is 17 per cent, without an exception. That is not a strength choice on a small conductor, it is the only way a 16 mm² line carries a span: the aluminium alone would not hold. Above 100 the ratio drops to 6 to 16, and at 800 and up it falls again to 4 to 13.
Only one code, 800, appears at three ratios — 4, 8 and 13 per cent — which makes it the one place in the table where you can compare the whole trade at a fixed size:
| 800 mm² | 4 % | 8 % | 13 % |
|---|---|---|---|
| Steel area mm² | 34.6 | 66.7 | 101 |
| Total area mm² | 835 | 867 | 901 |
| Mass kg/km | 2480.2 | 2732.7 | 3004.9 |
| Rated strength kN | 167.41 | 205.33 | 243.52 |
| Resistance Ω/km | 0.0361 | 0.0362 | 0.0362 |
From 4 to 13 per cent the strength rises 45 per cent and the weight 21, and the resistance moves by a fortieth of a decimal place. Paying for steel at a fixed code buys strength and costs weight, nothing else.
Rated Strength Follows The Steel
Strength per square millimetre of total section runs from 200 to 324 N/mm² across the table — a 60 per cent spread, not the flat material figure you get on an all-aluminium conductor. It is a mixture of two materials, and the mixture moves with the ratio:
- 16-17: 6.06 kN on 18.7 mm² = 324 N/mm²
- 125-6: 29.17 on 132 = 221
- 125-16: 45.69 on 145 = 315
- 1250-4: 261.75 on 1303 = 201
- 1250-8: 316.04 on 1352 = 234
At the same code the step from 6 to 16 per cent is worth 57 per cent more strength (125: 29.17 to 45.69), and the weight rises 27 per cent with it. That is the whole trade in one comparison.
One, Seven Or Nineteen Steel Wires
The core is a stranded conductor in its own right, and its wire count climbs with the size:
| Steel wires | Core diameter | Codes |
|---|---|---|
| 1 | 1 × d | 16 to 200 |
| 7 | 3 × d | 125 to 1250 |
| 19 | 5 × d | 560 to 1250 |
The multiples are exact, not rounded — 7 wires give a core of 3d, 19 wires 5d, and every row in the table follows it to the printed decimal (3 × 2.99 = 8.97 against 8.96 printed on 710-7; 5 × 2.18 = 10.9 against 10.9 on 560-13).
The aluminium side is not a simple 6, 12, 18 ladder. IEC 61089 allows a last layer to be partly filled, so the counts run 6, 18, 22, 26, 45, 54, 72, 84 — none of which is a whole multiple of six except the first. The conductor diameter is still core plus two diameters per layer, and every row closes on an integer layer count.
What Is Missing
- No ampacity. Neither this table nor the standard gives one; it depends on wind, ambient and allowable temperature.
- No modulus, no expansion coefficient, no sag. A stringing calculation cannot be run from these columns.
- No A1/S1B, A1/S2A or A1/S2B rows. The standard carries them as Tables D.5 to D.7; they are different steel grades at the same construction, and mixing them into one list would repeat the grade-mixing problem the AAAC page warns about.
- No GB code column. JL/LB1A is numbered by area over area, not by this code number, so a GB tender cannot be matched row for row here.
Related Pages
The other conductor tables: ACSR / LGJ, AAC / LJ, AAAC / JLHA, AACSR/AW, TACSR, GSW, expanded diameter, ACAR. Back to the designation reference.
Note: Thirty-seven rows from IEC 61089 Table D.4, A1/S1A. The code number is an equivalent aluminium area, not a section: 125 carries 124.5 mm² of aluminium, and resistance times aluminium area stays at 28.7 to 29.0 across all 37 rows, which is D.1.4 holding. Every code from 16 to 100 mm² is 17 per cent steel; 800 is the only code offered at three ratios. Strength per square millimetre runs 200 to 324 N/mm², so this is a mixed-material figure and not a derated single-metal one.