PF Power Fittings Technical Reference

TACSR Conductor (NRLH58GJ / NRLH60GJ)

6 + 6 + 43 rows · 50/8 to 1440/120 mm² · 58 and 60 per cent IACS

TACSR is the international name: Thermal-resistant Aluminium Alloy Conductor, Steel Reinforced, to IEC 62004 and JEC 197. The GB designation NRLH58GJ is the 58 per cent IACS alloy, NRLH60GJ the 60 per cent one; both are steel-cored. The family sits with the high-temperature low-sag conductors, not with ordinary ACSR.

Three tables that describe one product family. The first two are the same conductor at two conductivities, six sizes each. The third is a 43-row table that runs the 58 per cent resistance alongside current ratings at 90, 110 and 150 °C, which is the whole point of the alloy: the conductor keeps its strength and carries more current at a temperature that would soften ordinary ACSR.

58 Per Cent IACS

Nominal Section (mm2) Aluminum Alloy/SteelStructure Strands/Dia.(mm)Calculated Section (mm2)Calculated Outer Dia.(mm)20°CDC Resistance Not Greater Than(Ω/km)Calculated Breaking Load (N)Calculated Weight (kg/km)
aluminum alloysteelaluminum alloysteelTotal
300/5026/3.837/2.98299.5448.82348.3524.260.10141010901210
400/5054/3.077/3.07399.7351.82451.5527.630.07611178451513
500/6554/3.447/3.44501.8865.06566.9430.960.06061479631899
630/8054/3.8719/2.32635.1980.32715.5134.820.04791877922190
800/10054/4.3319/2.60795.17100.88896.0538.930.03832315602995
1440/12084/4.6719/2.801438.81116.991555.8951.360.02133445024928

60 Per Cent IACS

Nominal Section (mm2) Aluminum Alloy/SteelStructure Strands/Dia.(mm)Calculated Section (mm2)Calculated Outer Dia.(mm)20℃DC Resistance Not Greater Than(Ω/km)Calculated Breaking Load (N)Calculated Weight (kg/km)
aluminum alloysteelaluminum alloysteelTotal
400/5054/3.077/3.07399.7351.82451.5527.630.073701179111511
400/5024/4.607/3.00398.8649.48448.3427.400.073451149391489
500/6554/3.447/3.44501.8865.06566.9430.960.058701480471897
630/8054/3.8719/2.32635.1980.32715.5134.820.046381879512388
800/10054/4.3319/2.60795.17100.88896.0538.980.037052316852991
1440/12084/4.6719/2.801438.81116.991555.8051.360.020573446424930

58 Per Cent Resistance With The Three Temperature Ratings

Nominal Section (mm2) Aluminum/Steel Al/SteelStructure Strands/Dia.(mm)Calculated Outer Dia.(mm)20°C 58% IACS DC Resistance Not Greater Than(Ω/km)20°C D.C.Calculated Breaking Load (N)Calculated Weight (kg/km)Reference Current Carrying Capacity A
aluminumsteel90°C110°C150°C
50/86/3.21/3.209.600.625416200195216256326
70/106/3.801/3.8011.400.443522850275256217407
70/4012/2.727/2.7213.600.435657230511249303401
95/207/4.167/1.8513.870.317636040409295355490
95/5512/3.207/3.2016.000.314776760708298365498
120/718/2.901/2.9014.500.254726180379337469594
120/257/4.727/2.1015.740.246746420527335467591
120/7012/3.607/3.6018.000.248697150896383410570
150/818/3.201/3.2016.000.209230870461438533676
150/2024/2.787/1.8516.670.208344920549452550699
185/1018/3.601/3.6018.000.165339070584508620789
185/2524/3.157/2.1018.900.162256850706510623792
185/3026/2.987/2.3218.880.167462140733512625796
210/1018/3.801/3.8019.000.148443530651545664847
210/2524/3.337/2.2219.980.145263530789555676863
210/3526/3.227/2.5020.380.143471280854565690882
210/5030/2.987/2.9820.860.145288400961570695887
240/3024/3.607/2.4021.600.124273170922613756967
240/4026/3.427/2.6621.660.127180570964610746956
240/5530/3.207/3.2022.400.1260987701108612758969
300/1542/3.007/1.6723.010.10230645709406958481082
300/2045/2.937/1.9523.430.100127214010026978501084
300/2548/2.857/2.2223.760.099207983010586988511085
300/4024/3.997/2.6623.940.101118988011337008581090
300/5026/3.837/2.9824.260.1013510100012107028611105
300/7030/3.607/3.6025.200.0995212500014027188821134
400/2042/3.517/1.9526.910.074718627012868169981275
400/2545/3.337/2.2226.640.077519041012958179991276
400/3548/3.227/2.5026.820.077729851013498199981270
400/5054/3.077/3.0727.630.0760611790015118219981269
400/6526/4.427/3.4428.000.07610130400161182610151270
400/9530/4.1619/2.5029.140.07453166000186086310651374
500/3545/3.757/2.5030.000.06112114600164294411561481
500/4548/3.607/2.8030.000.06218123300168894811571480
500/6554/3.447/3.4430.960.06058148000189795011591478
630/4545/4.207/2.8033.600.048731406002060108313251701
630/5548/4.127/3.2034.320.047471561002209108813281700
630/8054/3.8719/2.3234.820.047861879002386109113311698
800/5545/4.807/3.2038.400.037311818002690126815592012
800/7048/4.637/3.6038.580.037591973002791126515572010
800/10054/4.3319/2.638.980.038232316002991125115081933
1000/12054/4.8419/2.943.540.030602888003733143217442230
1440/12084/4.6719/2.851.360.021143446004898187123523093

The Three Rules At The Foot Of The Third Table

The sheet prints its own conversion rules, and the tables obey them:

  • Resistance. An NRLH60GJ wire of the same section has the NRLH58GJ resistance divided by 1.03449. The 400/50 row proves it: 0.0761 ÷ 0.07370 = 1.0326, within a fifth of a per cent of the stated 1.03449.
  • Weight. The printed weight is the bare conductor — section times density, which is how the rows close on this page. Where the steel core or the inner aluminium-steel layers carry the anti-corrosion coating, add the standard allowance: 2 per cent on a coated core, 5 per cent on coated inner layers.
  • Current. At the same specification the 60 per cent conductor carries 1.0171 times the current of the 58 per cent one. That is 1.7 per cent, not the 3.4 per cent the resistance improves by, because the rating is limited by surface temperature rather than by conductor loss alone.

Traps In This Family

The IACS percentage is not in any table. It is in the heading and nowhere else, so a row copied without its heading loses the only thing that separates it from the other version — and the two are otherwise identical in every visible column except resistance.

The 60 per cent table prints 400/50 twice, on two different strandings:

  • 400/50 A — 54/3.07 + 7/3.07, 451.55 mm², 27.63 mm, 0.07370 Ω/km, 1511 kg/km.
  • 400/50 B — 24/4.60 + 7/3.00, 448.34 mm², 27.40 mm, 0.07345 Ω/km, 1489 kg/km.

Both are NRLH60GJ 400/50, and they differ in stranding, section, diameter, resistance, breaking load and weight. A nominal section alone does not identify this conductor — quote the stranding.

The 58 per cent table has a 300/50 row and the 60 per cent table does not. The smallest size in the 58 per cent version is 300/50 at 24.26 mm; the 60 per cent version starts at 400/50. If a project specifies 60 per cent and 300 mm², this family cannot supply it.

One row in the 58 per cent table is 198 kg short. For 630/80 both tables carry the same stranding (54/3.87 + 19/2.32), the same section (715.51 mm²) and the same diameter (34.82 mm). The conductor weighs 2342 kg/km before coating — 635.3 mm² of aluminium at 2.703 plus 80.3 mm² of steel at 7.78 — and with the 2 per cent core-coating allowance, 2388 kg/km. The 60 per cent table prints 2388; the 58 per cent table prints 2190, eight per cent low.

Every other size agrees between the two tables to within 2 kg — 400/50 at 1513 and 1511, 500/65 at 1899 and 1897, 800/100 at 2995 and 2991, 1440/120 at 4928 and 4930. Quote 630/80 at 2388 kg/km, which is what a drum of it weighs.

What The Third Table Actually Gives

  • 43 rows, 50/8 to 1440/120, so it covers the lower range the two conductivity tables skip.
  • Current at 90, 110 and 150 °C — for 1440/120 that is 1871, 2352 and 3093 A. The gain from 90 to 150 °C is 65 per cent, which is the entire commercial case for the alloy.
  • Resistance at 58 per cent only. The column heading says 58 per cent, so the rating columns are for the 58 per cent conductor; applying them to a 60 per cent wire understates the current by 1.7 per cent.
  • No modulus, no expansion coefficient, no sag data. Current alone does not design a span.

Sleeves for this conductor: JY-BG splice for aluminium-clad steel, JT splice. The ordinary steel-cored range it replaces: ACSR LGJ table. Back to the designation reference.

Note: Three tables for one family: six sizes at 58 per cent, six at 60 per cent, and a 43-row table with 90/110/150 °C ratings. The IACS figure appears only in the headings. The 60 per cent table prints 400/50 on two strandings, so nominal section does not identify the conductor — quote the stranding. It also omits the 300/50 size the 58 per cent table has. On 630/80 the conductor computes to 2388 kg/km with the coating allowance and the 60 per cent table prints exactly that; the 58 per cent table’s 2190 is the row to disregard.