PF Power Fittings Technical Reference

ACSR Conductor (LGJ / LGJF)

51 rows · 10/2 to 800/100 mm² · GB 1179-83 · aluminium and steel sections in mm²

ACSR is the international name: Aluminium Conductor, Steel Reinforced, to ASTM B232 and IEC 61089. In GB 1179-83 the same conductor is LGJ, and LGJF is the corrosion-proof version with a protected steel core. GB/T 1179-2008 redesignates the pair JL/G1A and JL/G1AF. This is the conductor most of this catalogue’s clamps and sleeves are made for.

Each row is a pair of nominal sections, aluminium over steel, followed by the actual stranding, the two calculated sections, the outer diameter, the DC resistance, the calculated breaking load, the weight and the minimum delivery length.

Nominal Section (mm2) Aluminum/SteelStructure Strands/Dia.(mm)Calculated Section (mm2)Outer Dia.(mm)DC Resistance Not Greater Than(Ω/km)Calculated Breaking Load (N)Calculated Weight (kg/km)Delivery Length Not Less Than (m)
aluminumsteelaluminumsteelTotal
10/26/1.501/1.5010.601.7712.374.502.706412042.93000
16/36/1.851/1.8516.132.6918.825.551.779613065.23000
25/46/2.321/2.3225.364.2329.596.961.1319290102.63000
35/66/2.721/2.7234.865.8140.678.160.823012630141.03000
50/86/3.201/3.2048.258.0456.299.600.594616870195.12000
50/3012/2.327/2.3250.7329.5980.3211.600.569242620372.03000
70/106/3.801/3.8068.0511.3479.3911.400.421723390275.22000
70/4012/2.727/2.7269.7340.67110.4013.600.414158300511.32000
95/1526/2.157/1.6794.3915.33109.7213.610.305835000380.82000
95/207/4.167/1.8595.1418.82113.9613.870.301937200408.92000
95/5512/3.207/3.2096.5156.30152.8116.000.299278110707.72000
120/718/2.901/2.90118.896.61125.5014.500.242227570379.02000
120/2026/2.387/1.85115.6718.82134.4915.070.249641000466.82000
120/257/4.727/2.10122.4824.25149.7315.740.234547880526.62000
120/7012/3.607/3.60122.1571.25193.4018.000.236498370895.62000
150/818/3.201/3.20144.768.04152.8016.000.198932860461.42000
150/2024/2.787/1.85145.6818.82164.5016.670.198046630549.42000
150/2526/2.707/2.10148.8624.25173.1117.100.193954110601.02000
150/3530/2.507/2.50147.2634.36181.6217.500.196265020676.22000
185/1018/3.601/3.60183.2210.18193.4018.000.157240880584.02000
185/2524/3.157/2.10187.0124.25211.2918.900.154259420706.12000
185/3026/2.987/2.32181.3429.59201.9318.880.159264320732.62000
185/4530/2.807/2.80184.7343.10227.8319.600.156480190848.22000
210/1018/3.801/3.80204.1411.34215.4819.000.141145140650.72000
210/2524/3.337/2.22209.0227.10236.1219.980.138065990789.12000
210/3526/3.227/2.50211.7334.36246.0920.380.136374250853.92000
210/5030/2.987/2.98209.2448.82258.0620.860.138190830960.82000
240/3024/3.607/2.40244.2931.67275.9621.600.118175620922.22000
240/4026/3.427/2.66238.8538.90277.7521.660.120983370964.32000
240/5530/3.207/3.20241.2756.30297.5722.400.119810210011082000
300/1542/3.007/1.67296.8815.33312.2123.010.0972468060939.82000
300/2045/2.937/1.95303.4220.91324.3323.430.095207568010022000
300/2548/2.857/2.22306.2127.10333.3123.760.094338341010582000
300/4024/3.997/2.66300.0938.90338.9923.940.096149222011332000
300/5026/3.837/2.98299.5448.82348.3624.260.0963610340012102000
300/7030/3.607/3.60305.3671.25376.6125.200.0946312800014022000
400/2042/3.517/1.95406.4020.91427.3126.910.071048885012861500
400/2545/3.337/2.22391.9127.10419.0126.640.073709594012951500
400/3548/3.227/2.50390.8834.36425.2426.820.0738910390013491500
400/5054/3.077/3.07399.7351.82451.5527.630.0723212340015111500
400/6526/4.427/3.44398.9465.06464.0028.000.0723613520016111500
400/9530/4.1619/2.50407.7593.27501.0229.140.0708717130018601500
500/3545/3.757/2.50497.0134.36531.3730.000.0581211950016421500
500/4548/3.607/2.80488.5843.10531.6830.000.0591212810016881500
500/6554/3.447/3.44501.8865.06566.9430.960.0576015400018971500
630/4545/4.207/2.80623.4543.10666.5533.600.0463314870020601200
630/5548/4.127/3.20639.9256.30696.2234.320.0451416440022091200
630/8054/3.8719/2.32635.1980.32715.5134.820.0455119290023881200
800/5545/4.807/3.20814.3056.30870.6038.400.0354719150026901000
800/7048/4.637/3.60808.1571.25879.4038.580.0357420700027911000
800/10054/4.3319/2.60795.17100.88896.0538.980.0363524110029911000

Reading The Eleven Columns

The header splits three ways and the split is not cosmetic. Structure Strands/Dia. gives two cells — aluminium wires then steel wires — so the row 26/2.15 | 7/1.67 means twenty-six aluminium wires of 2.15 mm over seven steel wires of 1.67 mm. Calculated Section then gives three: the aluminium area, the steel area and the total.

Three things follow from that:

  • The nominal section in the first column is not the calculated section. LGJ-120/20 has 115.67 mm² of aluminium and 18.82 mm² of steel, a total of 134.49 mm². If a line design or a clamp datasheet quotes 120 mm², it is quoting the nominal figure, and the conductor the clamp actually grips is 15.07 mm across.
  • The two numbers in the first column are aluminium and steel, not aluminium and total. 240/40 means 240 mm² of aluminium and 40 mm² of steel, so the conductor is larger than 240. Reading it as “240 total, 40 of it steel” understates the diameter by about 4 mm.
  • The resistance column is a maximum, not a nominal. Every header on this page reads “Not Greater Than”. Actual strand resistance runs a little under the printed figure, and a sag calculation should be run on the printed one.

The Weights Hold

All 51 rows were checked by rebuilding the weight from the two calculated section columns:

  • aluminium at 2.703 g/cm³ and steel at 7.78 g/cm³, section in mm² multiplied by density to give kg/km;
  • 51 of 51 rows land within 3 per cent, and most within 1 per cent;
  • the smallest row, 10/2, comes out at 42.9 kg/km printed against 42.7 calculated; the largest, 800/100, at 2991 against 2984.

The outer diameter is geometry rather than a convention. A seven-wire conductor is three wire diameters across — 50/8 is 6/3.20 over 1/3.20 and prints 9.60 mm, which is exactly 3 × 3.20. A two-layer build adds one wire diameter per layer, so 95/15 at 26/2.15 over 7/1.67 lands on 13.61 mm, which is the 5.01 mm steel core plus two layers of 2.15 mm aluminium.

That means a figure taken from this table can go into a sag-tension calculation without a second source — but only if you quote the row, not the nominal section.

What The Table Does Not Say: LGJ Or LGJF

The heading says LGJ and LGJF, and there is no column, note or suffix that distinguishes them. LGJF is the anti-corrosion version — the steel core carries a corrosion-resistant coating — and it weighs slightly more and is priced differently. Two conductors that answer to the same row can be two different products.

So an order for LGJF cannot be placed from this table alone. Quote the nominal section, the stranding and the letters LGJF, and ask for the coating to be confirmed. Reading a row as LGJF because the page heading mentions it is a mistake the page invites and does not prevent.

Where The Rows Are Thin

  • The steel ratio is not constant. 50/8 is 14 per cent steel by area; 240/40 is 14 per cent; but 120/25 is 16 per cent and 120/20 is 14 per cent. Two conductors with the same nominal aluminium figure can have different steel and therefore different breaking loads — 120/20 at 41.0 kN against 120/25 at 47.9 kN.
  • Delivery length drops as the conductor grows. 2000 m up to 240 mm², 1500 m at 400/50, 1000 m at 800/100. A drum length quoted without checking this column may not exist.
  • The top of the range is sparse. There are 51 rows but only a handful above 630 mm², and 800/100 is the end of the table. Anything larger is not in this catalogue.

The clamps that grip these conductors: NLL bolted aluminium alloy strain clamp, NLD bolt-type strain clamp. Sleeves for the same conductor: JT mechanical compression splice, JTB explosive compression splice, JX repair sleeve. The all-aluminium table: AAC conductors. Back to the designation reference.

Note: Fifty-one rows, 10/2 to 800/100. Every printed weight returns from its own two section columns at 2.703 and 7.78 g/cm³ — 51 of 51 within 3 per cent — and every outer diameter is real stranding geometry, a seven-wire build being three wire diameters across. The header names LGJ and LGJF together and the table carries no column, note or suffix that separates them, so an LGJF order has to state the coating separately. Nominal section is not calculated section: 120/20 is 134.49 mm² total and 15.07 mm across.