AAC Conductor (LJ)
16 rows · 16 to 800 mm² · GB 1179-83 · no steel core
AAC is the international name: All Aluminium Conductor, to ASTM B231 and IEC 61089. In GB 1179-83 the same strand is LJ, and GB/T 1179-2008 keeps that designation. Bare all-aluminium strand, used where tension is low and corrosion from a steel core is not wanted — short spans, low-voltage distribution, jumpers and busbar connections. There is no steel in any row, so the table is one structure column instead of two and one section column instead of three.
| Nominal Section (mm2) | Structure Strands/Dia.(mm) | Calculated Section (mm2) | Outer Dia.(mm) | DC Resistance Not Greater Than(Ω/km) | Calculated Breaking Load (N) | Calculated Weight (kg/km) | Delivery Length Not Less Than (m) |
|---|---|---|---|---|---|---|---|
| 16 | 7/1.70 | 15.89 | 5.10 | 1.802 | 2840 | 43.5 | 4000 |
| 25 | 7/2.15 | 25.41 | 6.45 | 1.127 | 4355 | 69.6 | 3000 |
| 35 | 7/2.50 | 34.36 | 7.50 | 0.8332 | 5760 | 94.1 | 2000 |
| 50 | 7/3.00 | 49.48 | 9.00 | 0.5786 | 7930 | 135.5 | 1500 |
| 70 | 7/3.60 | 71.25 | 10.80 | 0.4018 | 10950 | 195.1 | 1250 |
| 95 | 7/4.16 | 95.14 | 12.48 | 0.3009 | 14450 | 260.5 | 1000 |
| 120 | 19/2.85 | 121.21 | 14.25 | 0.2373 | 19420 | 333.5 | 1500 |
| 150 | 19/3.15 | 148.07 | 15.75 | 0.1943 | 23310 | 407.4 | 1250 |
| 185 | 19/3.50 | 182.80 | 17.50 | 0.1574 | 28440 | 503.0 | 1000 |
| 210 | 19/3.75 | 209.85 | 18.75 | 0.1371 | 32260 | 577.4 | 1000 |
| 240 | 19/4.00 | 238.76 | 20.00 | 0.1205 | 36260 | 656.9 | 1000 |
| 300 | 37/3.20 | 297.57 | 22.40 | 0.09689 | 46850 | 820.4 | 1000 |
| 400 | 37/3.70 | 397.83 | 25.90 | 0.07247 | 61150 | 1097 | 1000 |
| 500 | 37/4.16 | 502.90 | 29.12 | 0.05733 | 76370 | 1387 | 1000 |
| 630 | 61/3.63 | 631.30 | 32.67 | 0.04577 | 91940 | 1744 | 800 |
| 800 | 61/4.10 | 805.36 | 36.90 | 0.03588 | 115900 | 2225 | 800 |
The Stranding Rule Holds On Every Row
The outer diameter is not chosen, it is built. Count the layers and the diameter follows:
- 7 wires — 16 to 95 mm² — three wire diameters across. 7/1.70 prints 5.10 mm, which is 3 × 1.70.
- 19 wires — 120 to 240 mm² — five diameters. 19/2.85 prints 14.25 mm, which is 5 × 2.85.
- 37 wires — 300 to 500 mm² — seven diameters. 37/3.20 prints 22.40 mm.
- 61 wires — 630 and 800 mm² — nine diameters. 61/3.63 prints 32.67 mm.
Every row on the page follows the rule to the printed decimal, which is how the table was confirmed: the diameter column is geometry, not a rounding of something else.
The weights were checked the same way. Section in mm² times 2.703 g/cm³ gives kg/km, and all 16 rows land within 3 per cent — 16 mm² prints 43.5 against 42.9 calculated, 800 mm² prints 2225 against 2177. The small excess is consistent across the table and is the difference between theoretical and commercial weight, not an error in a row.
At The Same Nominal Section, LJ And ACSR Are Not Interchangeable
The two tables share the nominal sections 120, 150, 185 and 240, and that is where the resemblance stops:
- LJ-120 is 19/2.85, 121.21 mm², 14.25 mm across, breaking load 19,420 N, weight 333.5 kg/km.
- LGJ-120/20 is 26/2.38 over 7/1.85, 134.49 mm², 15.07 mm across, breaking load 41,000 N, weight 466.8 kg/km.
So at the same nominal figure the all-aluminium conductor carries 47 per cent of the load, is 0.8 mm smaller in diameter and is 29 per cent lighter. A clamp selected for one will not necessarily fit the other, and a span designed for one will not hold with the other. The nominal section is the only thing the two have in common.
What This Table Assumes
- Hard-drawn aluminium at 2.703 g/cm³. The resistance column is a maximum, so a real drum runs slightly better than printed.
- No coating, no grease, no wrapping. There is no note about anti-corrosion treatment anywhere on the page, and no column to record it.
- Delivery length falls with size — 4000 m at 16 mm², 800 m at 630 and 800 mm². The 120 mm² row steps back up to 1500 m, which is the only non-monotonic entry in the column.
Related Pages
Sleeves and repair tubes for all-aluminium conductor: JY-L aluminium splice, JT-L mechanical splice. Clamps for the same conductor: JBLY parallel groove clamp. The steel-cored table next door: ACSR LGJ / LGJF. Back to the designation reference.
Note: Sixteen rows with no steel core, so one structure column and one section column. All sixteen weights return from their own section at 2.703 g/cm³ within 3 per cent, and the outer diameter follows the layer count exactly — three wire diameters at 7 strands, five at 19, seven at 37 and nine at 61. Compared with ACSR at the same nominal 120 mm², the all-aluminium conductor carries 47 per cent of the load and is 0.8 mm narrower, so the two are not interchangeable in either a clamp or a span.