PF Power Fittings Technical Reference

Expanded Diameter Conductor (LGKK)

3 sizes · 587, 900 and 1400 mm² · centre support metal hose

GB/T 1179-2008 lists two expanded types: LGJK, supported by round wires, and LGKK, supported by a flexible metal hose. The three sizes here are LGKK.

An expanded diameter conductor is built around a hollow metal hose so that the outside diameter can be much larger than the aluminium section needs. The larger surface reduces the electric field at the conductor, which is why the type exists on high-voltage lines where corona and radio interference set the bundle geometry rather than the current.

This is the only table in the appendix that is transposed — the three models run across the top and the properties run down the side. It is also the only one that prints elastic modulus and coefficient of expansion, which makes it the only table here you can run a sag-tension calculation from.

Model & SpecificationLGKK-587LGKK-900LGKK-1400
ConductorOuter Dia.(mm)514957
Calculated Cross-Sectional Area (mm2)aluminum586.7906.41387.8
steel49.584.83106.0
Total636.2991.231493.8
ConductorStructure Strands/Dia.(mm)Center Support Metal Hose Outer Dia.39.027.027.0
Inner Layeraluminum35/3.018/3.015/3.0
steel7/3.012/3.015/3.0
Secondary Inner Layer, Aluminum48/3.028/4.028/4.0
Secondary Outer Layer, Aluminum/34/4.034/4.0
Outermost Layer, Aluminum//40/4.0
Calculated Total Breaking Load (kN)137205289
Elastic Modulus (kN/mm2)71.5458.758.02
Linear Expansion Coeff. (10-6/°C)20.620.420.8
DC Resistance (20°C Ω/km)0.05140.033170.02163
Current Carrying Capacity (70°C A)75010201290
Unit Weight (kg/km)271136505159

Diameter Does Not Follow Section

The three sizes are not a progression, and the table shows why:

  • LGKK-587 has a 39.0 mm support hose, two conductor layers and an outside diameter of 51 mm.
  • LGKK-900 has a 27.0 mm hose and an outside diameter of 49 mm — 2 mm smaller than the 587, on a conductor with 55 per cent more aluminium.
  • LGKK-1400 goes back up to 57 mm, on the same 27 mm hose but with four layers.

So the diameter is set by the hose and the layer build, not by the section. Anyone who assumes “bigger number, bigger conductor” will order the wrong one: LGKK-900 is the narrowest of the three.

What The Table Gives That The Others Do Not

Four properties appear here and nowhere else in this appendix, and they are the four a line designer needs:

  • Elastic modulus — 71.54, 58.7 and 58.02 kN/mm². The 587 is the stiffest by a wide margin, because its hose takes up a larger share of the section.
  • Coefficient of linear expansion — 20.6, 20.4 and 20.8 ×10⁻⁶ per °C. Effectively the same on all three, so sag differences between them come from modulus rather than expansion.
  • Current carrying capacity at 70 °C — 750, 1020 and 1290 A. This is the one bare conductor table here with a rating at all.
  • Unit weight — 2711, 3650 and 5159 kg/km.

With modulus, expansion, weight and breaking load on one row, a sag-tension calculation can be run from this page alone. For every other conductor in the appendix it cannot.

Two Cautions

  • The section splits into aluminium and steel, and the total is not the sum of the two nominal figures. LGKK-587 has 586.7 mm² of aluminium and 49.5 mm² of steel for a total of 636.2 mm², so the model number refers to the aluminium part.
  • The layer list has empty entries written as a slash. LGKK-587 shows / for its secondary outer and outermost layers, which means those layers do not exist on that size rather than that the data is missing. Reading the slash as “not published” would suggest a four-layer build where there are only two.

The fittings that terminate tubular and expanded conductors: tubular busbar fittings installation, KLMG cross-road transition, GGJ tubular transition joint. The solid ACSR range: LGJ table. Back to the designation reference.

Note: Three sizes in a transposed table. Diameter is set by the support hose, not the section — the 900 mm² conductor is 49 mm across against 51 mm for the 587. This is the only table in the appendix with elastic modulus, expansion coefficient and a current rating, so it is the only one a sag-tension calculation can be run from. Layer entries shown as a slash mean the layer does not exist on that size, not that the figure is unpublished.