Tubular Busbar Fittings Installation Schematic
What it is: a setting-out sheet, not a part · Drawings: 6 · Decides: pad heights, pad size, connection direction
This Page Is A Measuring Sheet, Not A Part
Nothing here is ordered as drawn. The six drawings exist to fix the geometry of a tubular busbar run between two pieces of equipment, and the fittings that come out of it — clamps, spacers, transition pieces, terminal pads — are specified from the measurements the customer takes off the installation.
That is why the page has no dimension table. The dimensions are on the site, not in the catalogue, and the drawings are the form in which they have to be sent to us.
What The Elevation Asks For
The first drawing is an elevation of the two equipment terminals with the busbar between them. It carries three questions, marked on the drawing itself:
- The height above ground of the instrument transformer terminal pad
- The height above ground of the circuit breaker terminal pad
- The height difference between the two pads
The third is not a derived convenience — it is asked separately because it sets the vertical offset the busbar has to absorb, and that is what decides whether the run is straight, stepped or needs a flexible element.
Below the elevation the same drawing shows the terminal pad in two orientations, each with its length (a) and width (b) marked. So there are four numbers to take at each terminal: height, pad length, pad width, and which way the pad faces.
What The Section View Numbers, And What Is Missing
The second drawing is a section through one clamp assembly: two clamps on the tube, suspension rods below them, yoke plates and turnbuckles distributing the load, and a numbered balloon view at the right.
The balloons read 1, 2, 3, 4, 6 and 7 — there is no balloon 5, and no parts list accompanies the page. So the numbering on the drawing cannot be resolved to part numbers from anything printed here.
If you are working to this drawing, ask us for the parts list that goes with it. Reading the balloons by position is guesswork, and one of them is not there at all.
The Ordering Checklist Has Four Items Missing
The page tells you to send “the dimensions shown in the above diagram and the following information”, and then lists them:
| Item | Given on this page |
|---|---|
| a | Connection direction of the transformer terminal pad — horizontal or vertical |
| b – e | not printed |
| f | Circuit breaker terminal pad material — copper or aluminium |
The list jumps from a to f. Four items between them are absent from the page, and they are exactly the ones a fabricator needs before a drawing can be released: the pad sizes, the phase spacing, and the busbar size are the obvious candidates, but this page does not say.
Send us the heights, the pad sizes and the pad orientation, and the full checklist comes back with the offer. A quotation built on the two printed items alone comes back as a redesign.
Read It In This Order
The drawings are best used as a sequence rather than a set:
- Elevation — the two pad heights and the difference between them. This sets the run.
- Section — the clamp and suspension assembly at one support, which sets the fittings count.
- Plan and spacer details — the phase spacing and where the spacers fall.
- Transition and terminal details — how the tube meets the equipment pad, and in which direction.
Get the elevation wrong and everything downstream is wrong; the section and the details are consequences of it.
What The Page Cannot Answer
- No dimensions and no part numbers — the drawings are illustrative, and the fittings they show are specified on their own pages.
- No rated current or short-circuit figure — which the terminal pad items on the checklist depend on.
- No material or finish schedule — the standards below cover hot-dip galvanising, but nothing on the page says which parts are steel, aluminium or copper.
- No span lengths — a support spacing is a design decision this sheet leaves to the project.
The Fittings The Drawings Refer To
The assembly is built from parts specified elsewhere:
- Tubes — aluminum tubular busbar, in OD/ID pairs from 70/64 to 300/276
- Supports and spacers — MCN, MCW, JS double busbar spacer, YH composite busbar ring
- Expansion and transition — MSC, KLMG cross-road transition
- Suspension hardware — GD attachment point fitting, YL / YLP extension rod, BL yoke plate, DB adjusting plate
Drawings

Standards Referenced
| Standard | Scope |
|---|---|
| IEC 61284 | Overhead line fittings — requirements and tests, corrosion protection included |
| ISO 1461 | Hot-dip galvanized coatings on iron and steel articles |
| ASTM A153 | Zinc coating (hot-dip) on iron and steel hardware |
| GB/T 2314 | General requirements for overhead line fittings |
| GB/T 2317 | Mechanical testing methods for overhead line hardware |
| DL/T 765.2 | Suspension and strain hardware for overhead power lines |
Note: A setting-out sheet, not a product page. The first drawing asks for the height above ground of the instrument transformer pad, the height above ground of the circuit breaker pad, the height difference between them, and the pad length and width in both orientations. The section view is numbered 1, 2, 3, 4, 6 and 7 with no balloon 5 and no parts list on the page. The ordering checklist on this page runs a, then f — items b to e are missing, so treat it as a fragment and ask for the full list before quoting. No dimensions, ratings or material schedule are printed here.