PF Power Fittings Technical Reference

MCW Channel Busbar Support

Models: MCW-100 – MCW-250 · Busbar Width: 100–250 mm · Reference Weight: 5.6–6.5 kg

MCW Channel Busbar Support

The Same Head On A Longer Base

Put the MCW sheet beside the MCN and the first thing to notice is that the seven H values are identical, cell for cell: 132, 157, 182, 212, 245, 270, 300. The clamp head that grips the busbar is the same part. What changes is underneath it:

  • L — 250 mm instead of 200 mm, so the base reaches 50 mm further.
  • L1 — 140 mm, a column the MCN does not print at all.
  • M — still M16, unchanged.

So this is not a stronger clamp. It is the same clamp on a longer base plate, and the extra 50 mm is what you are paying for.

L1 Is A Fixed 140 mm

L1 does not move across the seven sizes — it is 140 mm on every row, from the 100 mm busbar to the 250 mm busbar. That makes it a base feature, not a busbar dimension: two parallel channel runs sit 140 mm apart regardless of how wide the busbars are.

Because L1 is constant, it cannot be used to order. If a layout needs a different centre distance between the two runs, the MCW is not adjustable and you need to ask us for a special.

The Weight Gap Is Not Constant

MCW minus MCN, size by size:

Busbar MCN MCW Difference
100 3.9 5.6 1.7
125 4.0 5.7 1.7
150 4.1 5.8 1.7
175 4.2 6.0 1.8
200 4.3 6.1 1.8
225 4.4 6.3 1.9
250 4.6 6.5 1.9

1.7 kg at the small end, 1.9 kg at the large end. The longer base costs proportionally more steel as the busbar grows, which is why the two curves diverge instead of running parallel.

The practical consequence is a 41 to 44 % weight penalty for the same busbar size. If the layout only needs one run and 200 mm of base will do, the MCN saves close to half a tonne on a thousand-piece order — do not specify MCW simply because it appears first in a catalogue.

Technical Parameters

MCW Channel Busbar Support MCW Channel Busbar Support

ModelBusbar Width (mm)Main Dimensions (mm)Reference Weight (kg)
HLL1M
MCW-100100132250140165.6
MCW-125125157250140165.7
MCW-150150182250140165.8
MCW-175175212250140166.0
MCW-200200245250140166.1
MCW-225225270250140166.3
MCW-250250300250140166.5

The short-base version of the identical clamp: MCN channel busbar support. The spacer that holds two busbars apart rather than supporting them: MCG. Expansion joints for the same run: MSC.

Note: H is identical to the MCN row for row — this is the same clamp head. L is 250 mm instead of 200 and L1 is a fixed 140 mm that does not change with busbar size. The weight gap over the MCN widens from 1.7 to 1.9 kg, a 41 to 44 % penalty.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: