PF Power Fittings Technical Reference

MCG Channel Busbar Spacer

Models: MCG-1 – MCG-3 · Busbar Width: 200–250 mm · Reference Weight: 1.9–2.2 kg

MCG Channel Busbar Spacer

Three Rows, Two Fixed Rules

The sheet carries three sizes and two dimensions that follow the busbar instead of leading it:

  • H equals the busbar width on every row — 200 with 200, 225 with 225, 250 with 250. H is a mirror of the busbar width, not an independent dimension. You cannot order the 250 mm spacer to close a 200 mm gap.
  • C is the horizontal clear opening, and it sits 14 to 19 mm wider than the busbar — but not by a constant. The three gaps are +14, +19 and +14 mm. Do not compute C as “busbar plus 15”.

H1 is the overall height of the clamp stack, including the plates, washers and the bolt heads top and bottom. Subtract H and the stack adds 100 mm on MCG-1, 95 mm on MCG-2 and 130 mm on MCG-3.

That last figure is the interesting one. MCG-3 carries a busbar only 25 mm wider than MCG-1, yet its clamp stack is 35 mm taller. The third size is built on a heavier frame, not a scaled copy of the first two.

Weight Does Not Track Size Evenly

1.9 → 2.1 → 2.2 kg. The first 25 mm step adds 0.2 kg, the second adds 0.1 kg. If you are estimating freight on a mixed order, do not interpolate between MCG-1 and MCG-3 — the two steps are not equal.

Bolt Size Is On The Drawing, Not In The Table

The drawing shows a single M16 bolt running vertically through both pressure plates, with nut and washer at each end. There is no M column, so the bolt does not appear in the printed data — but it is the same M16 on all three sizes. Order M16 hardware for every MCG, or ask us before substituting a smaller stud.

Technical Parameters

MCG Channel Busbar Spacer

ModelBusbar Width (mm)Main Dimensions (mm)Reference Weight (kg)
HH1C
MCG-12002003002141.9
MCG-22252253202442.1
MCG-32502503802642.2

The rectangular version of the same job: MJG rectangular busbar spacer. Stand-off supports built on the same clamp head: MCN and MCW. The expansion joint that goes between two channel runs: MSC.

Note: H is the busbar width on every row, so H cannot be selected separately. C is 14 to 19 mm wider than the busbar and that margin is not constant. H1 − H runs 100, 95 and 130 mm, so MCG-3 sits on a taller clamp stack than its busbar width alone would suggest. One M16 bolt top and bottom throughout.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: