PF Power Fittings Technical Reference

JS Double Busbar Spacer

Models: JS-400N/120 – JS-57/400 (16 rows in two tables) · Conductor: 27.4–56 mm · Lengths: 120, 200, 400 mm

JS Double Busbar Spacer

L Is The Spacer Length, And The Model Says So

The number after the slash is L, the distance between the two conductor clamps: 120, 200 or 400 mm. Every row agrees with it — JS-400N/120 has L 120, JS-51/400 has L 400, JS-630N/200 has L 200.

So the model reads conductor code / spacing. Once you know that, the sheet is easy to search: pick the spacing first, then the conductor.

The first table holds the three 120 mm spacers and the second holds thirteen rows mixing 200 and 400 mm — which is why the second table looks longer than it is. Sorted by length it is seven at 200 mm, six at 400 mm, and three at 120 mm.

R Is The Conductor Radius Plus Half A Millimetre

Every row without exception:

Conductor dia Half of it Printed R Clearance
27.4 13.7 14.0 0.3
35.0 17.5 18.0 0.5
42.1 21.1 21.5 0.4
49.0 24.5 25.0 0.5
52.0 26.0 26.0 0.0
56.0 28.0 28.5 0.5

R is the radius of the conductor groove, cut 0.3 to 0.5 mm over the conductor it is meant for. That is a machined fit, not a range: the clamp will seat properly on a 27.4 mm conductor and will not close on a 30 mm one.

So there is no “applicable diameter range” on this sheet — the column is a single diameter per row, and you must match it. A spacer is not interchangeable across conductors of similar size.

Two Numbering Schemes In The Same Table

The leading number is not always the same kind of quantity:

  • Area codes — JS-400, 400N, 630N, 900K, 1000. These name a conductor class, and the actual diameter is in its own column: 400 and 400N are both 27.4 mm, 630N is 35.0, 900K is 49.0, 1000 is 42.1.
  • Diameter codes — JS-51 and JS-57. These are close to the conductor outside diameter: 51 goes with 52.0 mm, 57 with 56.0 mm.

The result is that a bigger number does not mean a bigger conductor. JS-900K/200 (49.0 mm) takes a larger conductor than JS-1000/200 (42.1 mm), and JS-57/200 (56.0 mm) is the largest on the sheet while JS-1000 sits below it.

Match on the diameter column, never on the model number.

The 120 mm Part Is One Clamp, Not Two

The same conductor at the three lengths:

Conductor 120 mm 200 mm 400 mm 120 → 200 200 → 400
400N (27.4 mm) 0.7 kg 1.6 kg 2.0 kg +0.9 +0.4
900K (49.0 mm) 0.7 kg 1.7 kg 2.3 kg +1.0 +0.6
51 (52.0 mm) 0.9 kg 1.9 kg 2.5 kg +1.0 +0.6

Going from 120 to 200 mm adds 80 mm and roughly 1 kg. Going from 200 to 400 mm adds 200 mm and only 0.4 to 0.6 kg.

A bar cannot explain that. The extra 80 mm of an aluminium bar weighs about 0.2 kg; the extra 200 mm about 0.5 kg. The 120 mm rows are one clamp on a short bar; the 200 and 400 mm rows are two clamps on a bar. That is why 120 mm costs 0.7 to 0.9 kg and 200 mm costs 1.5 to 2.0 — the step is the second clamp, not the bar.

So the two lengths are two different parts, not a short and a long version of one: order a 120 mm spacer where you need a single clamp, and a 200 mm one where you need to hold two tubes apart. Cost and weight follow the part.

At 200 mm, JS-400 has a 60 mm frame and weighs 1.5 kg, while JS-400N has a 50 mm frame and weighs 1.6 kg — two frames, not a light and a heavy version of one. Order by the code, and read A as the frame the two busbars sit in.

A Is The Frame, And It Does Not Follow The Conductor

A runs 50, 60, 65, 70, 75 mm and does not track the diameter: a 27.4 mm conductor appears with A 50 (400N) and A 60 (400), and the 56 mm conductor uses 75.

A is the width across the frame that carries the two clamps, so it sets the clearance between the two busbars, not the grip. If the two tubes are fixed at a spacing, A is the column that has to match — and the same conductor is offered with two different frames, which means the spacing is a design choice, not a consequence of the conductor.

GHB Is A Different Clamp For The Same Code

JS-51/400GHB sits next to JS-51/400 and is not the same part:

Model Conductor A R Weight
JS-51/400 52.0 mm 60 26.5 2.5 kg
JS-51/400GHB 51.0 mm 70 26.0 2.8 kg

The conductor is 1 mm smaller, the frame 10 mm wider, and the part 0.3 kg heavier. The same “51” code means 52.0 mm on one row and 51.0 mm on the other — so GHB is a variant clamp, not a finish or a packing option, and the two are not interchangeable on the same conductor.

What To Send With The Enquiry

  • The conductor diameter, not the area code — the clamp is cut to one diameter, and the area codes overlap.
  • The spacing — 120, 200 or 400 mm, and whether you need one clamp or two on the bar.
  • The frame A, where two tubes are fixed at a spacing.
  • The short-circuit current, if the run is being checked for fault force: it is not a catalogue column, so we confirm it against the type test for the size you order.
  • Torque and bolt size come on the packing list, not in the table.

Technical Parameters

JS Double Busbar Spacer Drawing JS Double Busbar Spacer Clamp JS Double Busbar Spacer Assembly

ModelApplicable Conductor Diameter (mm)Main Dimensions (mm)Reference Weight (kg)
ALR
JS-400N/12027.45012014.00.7
JS-51/12052.06012026.50.9
JS-900K/12049.05012025.00.7
ModelApplicable Conductor Diameter (mm)Main Dimensions (mm)Reference Weight (kg)
ALR
JS-400/20027.46020014.01.5
JS-400N/20027.45020014.01.6
JS-630N/20035.06520018.01.8
JS-900K/20049.05020025.01.7
JS-1000/20042.16020021.51.8
JS-51/20052.06020026.01.9
JS-57/20056.07520028.52.0
JS-400N/40027.45040014.02.0
JS-630N/40035.06540018.02.2
JS-900K/40049.05040025.02.3
JS-51/40052.06040026.52.5
JS-51/400GHB51.07040026.02.8
JS-57/40056.07540028.53.0

JS Double Busbar Spacer Application JS Double Busbar Spacer Installation

Clamps that hold a single tube: MDG single flexible busbar clamp, MSG double flexible busbar clamp. The tubes themselves: aluminum tubular busbar. Channel-section spacers: MCG, MCN.

Note: L is the spacer length and the model suffix states it — 120, 200 and 400 mm. R is the conductor radius plus 0.3 to 0.5 mm on every row, so each spacer fits one diameter and there is no applicable range. Two numbering schemes coexist — area codes (400/400N/630N/900K/1000) and diameter codes (51/57) — so JS-900K takes a larger conductor than JS-1000. The 120 mm length is one clamp on a short bar (0.7–0.9 kg); the 200 and 400 mm lengths are two clamps on a bar (1.5–2.0 and 2.0–3.0 kg). JS-51/400GHB is 51.0 mm against 52.0 mm for JS-51/400, with a wider frame and more weight.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: