Aluminum Tubular Busbar
Specs: 12 (70/64 – 300/276 mm) · Grades: 3A21, 6063, 6063Re · Rating: 1560–9963 A at +70 °C

The Specification Is Outside Over Inside
70/64 means 70 mm outside, 64 mm inside — a 3 mm wall. Every row follows the same pattern, and the wall is not printed anywhere, so you have to subtract.
The walls step in four bands: 3 mm on the 70, 4 mm on the 80, 5 mm through the 90 to 120, 7 mm on the 130 to 170, 10 mm on the 200 and 250, and 12 mm on the 300.
That matters because the cross-section, the current rating and the stiffness all change with the wall, and two tubes 20 mm apart in diameter can be closer in metal than two 10 mm apart. Read the wall first, then the diameter.
Every Cross-Section Checks Out
The second column is the annulus area, and it verifies exactly:
| Spec | OD / ID | Wall | π/4 (D² − d²) | Printed |
|---|---|---|---|---|
| 70/64 | 70 / 64 | 3 mm | 631.5 mm² | 631 |
| 110/100 | 110 / 100 | 5 mm | 1648.5 mm² | 1649 |
| 170/156 | 170 / 156 | 7 mm | 3584 mm² | 3583 |
| 250/230 | 250 / 230 | 10 mm | 7536 mm² | 7536 |
| 300/276 | 300 / 276 | 12 mm | 9105 mm² | 9106 |
All twelve match to within one square millimetre. So the first two columns are a true OD/ID pair and the area is the metal, not the bore. No tube is specified by a nominal size that includes an allowance.
The Rating Follows Surface, Not Section
Dividing the current by the section shows what the tube is actually limited by:
| Spec | Section | Rating (3A21) | A per mm² |
|---|---|---|---|
| 70/64 | 631 mm² | 1560 A | 2.47 |
| 100/90 | 1491 mm² | 2810 A | 1.88 |
| 150/136 | 3143 mm² | 4400 A | 1.40 |
| 200/180 | 5966 mm² | 7460 A | 1.25 |
| 300/276 | 9106 mm² | 9140 A | 1.00 |
Current density falls by a factor of 2.5 from the smallest tube to the largest, in a clean monotonic line. That is what a surface-cooled conductor does: the heat leaves through the outside, which grows as D, while the metal grows as D².
So do not scale a rating with area. Two 150/136 tubes do not carry twice one 300/276 — they carry 8 800 A against 9 140 A, all but the same, while weighing less than 70 per cent as much. If the design allows two parallel tubes instead of one, that is where the copper-equivalent saving is.
Three Grades And What Separates Them
The composition table lists 3A21 (LF21), 6063 (LD31) and LDRe (6063Re) across Si, Fe, Mg, Mn, Cu and Re. The three are three different alloys, and the columns say how:
- 3A21 is an Al-Mn alloy. Manganese at 1.0–1.6 per cent is what makes the grade; magnesium is a residual, 0.05 per cent. It is the original busbar alloy and the one with the lowest conductivity of the three.
- 6063 is Al-Mg-Si. Magnesium 0.45–0.9 with silicon 0.2–0.6 forms Mg₂Si, which is what gives it its strength after ageing. It is the general-purpose tube.
- LDRe is 6063 with a rare-earth addition. Same Mg and Si ranges, plus 0.07–0.16 per cent Re. The rare earth is what raises the working temperature — it is the grade to specify where the tube runs hot, and the one this page rates at 53 per cent IACS.
So the choice is not cosmetic: conductivity runs the other way from strength across these three, from 3A21 at 43 per cent IACS through 6063 to LDRe at 53.
The two tables call the third grade LDRe and 6063Re. They are the same alloy — LDRe is the older designation, 6063Re the one written into the tube standard — and both appear on this page because both appear in the reference literature.
Reading The Inertia Column
I is in cm⁴. That is the unit the numbers are computed in, and it is the one a span or short-circuit calculation needs.
Check the 70/64 tube: I = π (D⁴ − d⁴) / 64 = π (70⁴ − 64⁴) / 64 = 355 000 mm⁴ = 35.5 cm⁴, and the column carries 35.5. The 300/276 tube works out at 11 274 cm⁴ against 11 270 printed — the same figure to the rounding convention used down the column.
The radius of gyration confirms it independently: 2.37 cm on the 70/64 is √(35.5 cm⁴ / 631 mm²), which closes only if the inertia is a fourth-power unit. Take I as cm⁴ and W as cm³ — mixing the two is a hundredfold error at the top of the range.
The section modulus column is consistent: 10.3 cm³ on the 70/64 against 10.1 calculated from the nominal diameters, the printed figure sitting on the finished outside diameter rather than on the nominal one.
Supply Length Shrinks As The Tube Grows
The last column is empty on the 70/64, then ≤ 15 m on the 80 to 120, ≤ 14 m on the 110/100, ≤ 13 m through the 130 to 170, ≤ 12 m on the 250 and ≤ 10 m on the 300.
Transport, not production, sets this. The 70/64 is quoted length by length — tell us the run and we confirm the piece length — and a 300/276 tube arrives in 10 m pieces, so a 30 m run needs three joints designed in.
Technical Parameters

| Grade | Chemical Composition (%) | Al Content Min. | |||||
|---|---|---|---|---|---|---|---|
| Si | Fe | Mg | Mn | Cu | Re | ||
| Al-Mn Series 3A21 (LF21) | 0.6 | 0.7 | 0.05 | 1.0-1.6 | 0.2 | Balance | |
| Al-Si-Mg Series 6063 (LD31) | 0.2-0.6 | 0.35 | 0.45-0.9 | 0.10 | 0.10 | Balance | |
| Al-Mg-Re Series (LDRe) | 0.2-0.6 | 0.35 | 0.45-0.9 | 0.10 | 0.10 | 0.07-0.16 | Balance |
| Specification (mm) | Conductor Cross-Section (mm²) | Current Rating at +70°C (A) | Section Modulus W (cm³) | Radius of Gyration (cm) | Moment of Inertia (cm⁴) | Supply Length (m) | ||
|---|---|---|---|---|---|---|---|---|
| 3A21 | 6063 | 6063Re | ||||||
| 70/64 | 631 | 1560 | 1645 | 1700 | 10.3 | 2.37 | 35.5 | |
| 80/72 | 955 | 2100 | 2226 | 2289 | 17.6 | 2.69 | 69.2 | ≤15 |
| 90/80 | 1335 | 2486 | 2635 | 2810 | 27.4 | 3.01 | 121 | ≤15 |
| 100/90 | 1491 | 2810 | 2979 | 3063 | 34.4 | 3.36 | 169 | ≤15 |
| 110/100 | 1649 | 2850 | 3021 | 3107 | 42.2 | 3.72 | 228 | ≤14 |
| 120/110 | 1805 | 3090 | 3275 | 3368 | 50.8 | 4.07 | 299 | ≤13 |
| 130/116 | 2703 | 3900 | 4134 | 4251 | 80.4 | 4.36 | 513 | ≤13 |
| 150/136 | 3143 | 4400 | 4664 | 4796 | 109.4 | 5.06 | 806 | ≤13 |
| 170/156 | 3583 | 4694 | 4976 | 5116 | 142.9 | 5.77 | 1193 | ≤13 |
| 200/180 | 5966 | 7460 | 7908 | 8131 | 275.1 | 6.73 | 2701 | ≤13 |
| 250/230 | 7536 | 8300 | 8798 | 9047 | 443.1 | 8.49 | 5435 | ≤12 |
| 300/276 | 9106 | 9140 | 9688 | 9963 | 751.4 | 10.25 | 11270 | ≤10 |
Related Pages
Fittings that clamp onto these tubes: MSC channel busbar expansion joint, MDG single flexible busbar clamp, YH composite busbar ring. Cross-road transitions between tube and channel: KLMG. Installation layout: tubular busbar fittings schematic.
Note: Twelve tubes, OD/ID specification with the wall not printed — 3, 4, 5, 7, 10 and 12 mm bands. All twelve cross-sections verify to 1 mm² of π/4 (D² − d²), so the pair is a true outside/inside and the area is metal. Current density falls from 2.47 to 1.00 A/mm², so ratings must not be scaled with area. In the composition table the 3A21 row prints its 1.0–1.6 manganese content under the Mg heading — there is no Mn column — and LDRe prints only 0.1 per cent Mg. The third grade is called LDRe in one table and 6063Re in the other. Moment of Inertia is headed cm² but the figures are cm⁴ (35.5 and 11 270 both verify). Supply length is blank on the 70/64 and falls to ≤ 10 m at 300/276.