PF Power Fittings Technical Reference

MDS / MDSG Tubular Busbar Expansion Clamp — 0°, 30° and 90°

MDS MDSG tubular busbar expansion clamp

Models: 10 sizes · Reference Weight: 7.0–39.5 kg · Body types: MDS aluminium, MDSG copper-aluminium · Angle: 0°, 30° or 90°

A Terminal Clamp That Takes Expansion

MDS closes one tube end onto a terminal and takes the expansion travel between them. It is made with the terminal end at 0°, 30° or 90°, and the angle is the letter in the model number — A = 0°, B = 30°, C = 90°, per DL/T 683.

All three angles share one table, row for row: same bores, same a, same H, same b, same weights for MDS and MDSG. The body is one casting and only the terminal end is turned, so the letter does not change any dimension on the drawing.

Angle Type letter Where it is used
0° A Terminal end straight along the tube axis — the run carries on in the same direction.
30° B The terminal end eases off line, to reach a pad that is not square to the tube.
90° C Terminal end square to the tube, taking the connection off to the side.

Two Bodies in One Table

Every row carries two weights. MDS is the first, MDSG the second, and the difference is exactly 0.5 kg on all ten sizes:

Bore 70 80 90 100 120 130 150 170 200 250
MDS 7.0 7.5 8.0 8.5 14.5 15.5 16.0 24.0 36.0 39.0
MDSG 7.5 8.0 8.5 9.0 15.0 16.0 16.5 24.5 36.5 39.5

A uniform 0.5 kg across a range that itself runs from 7 to 39 kg means the two bodies differ by one small part, not by a change of construction — MDS is aluminium, MDSG is the copper-aluminium terminal. No dimension is printed separately for the two, so they occupy the same envelope.

This Is the Only Expansion Clamp With Published Weights

The other two expansion clamps in this section print an empty weight column:

Weights Foot / height
MDS / MDSG published, 7.0 – 39.5 kg no foot column
MGGD empty foot 140 / 225 / 250, H 110 – 250
MGGD-WP empty none

So if you are estimating freight or closing a structural calculation on a run, this is the expansion clamp you can actually cost from the catalogue.

No Foot: This Is a Joint, Not a Support

There is no base plate and no anchor bolt in this table. MDS does not bolt to steel; it joins one tube end to the next and takes the travel between them. MGGD is dimensioned with a foot because it also carries the bus down to the structure.

That matters when you lay a run out: the expansion clamp goes between two supports, not in place of one.

Five Envelope Bands, Not Ten

The clamp body is made in five sizes and bored for ten tube diameters. That is why a and H repeat:

Band Busbar sizes a H b
1 70, 80 80 mm 85 mm 16 mm
2 90, 100, 120 100 mm 105 mm 18 mm
3 130, 150 125 mm 130 mm 20 mm
4 170 150 mm 160 mm 22 mm
5 200, 250 150 mm 170 mm 22 / 24 mm

b is a clean 2 mm ladder — 16, 18, 20, 22, 24, one step per band — which is the bolt size going up with the body.

a stops growing at 150 mm while H carries on to 170 mm. So the two largest clamps are the same length along the tube and differ only in height and bore.

The 120 mm Size Weighs 6 kg More Than the 100

90, 100 and 120 mm all use the 100 / 105 / 18 body, yet the weights run 8.0, 8.5 and 14.5 kg. The clamp jaws are thicker for the bigger bore, which the a/H/b columns do not show. Do not estimate the 120 from the 100 — it is 70 % heavier, not 6 %.

State the Wall, Not Just the Bore

The bore column prints outside and inside diameter, and the wall it assumes is not the same down the list:

Bore 70 80 90 100 120 130 150 170 200 250
Wall 3 4 5 5 4 7 7 7 10 10

The 120 mm row prints 120/112, a 4 mm wall, in a column that steps from 5 mm to 7 mm either side of it. MGGD prints the same 112 there; the MGF caps print 110.

The clamp is bored to the tube, so the wrong wall is the wrong part. Give us the outside diameter and the wall, for example “150 × 7”, and we will match it.

Technical Parameters

ModelTubular Busbar O.D./I.D. (mm)Main Dimensions (mm)Reference Weight (kg)
ØaHbMDS TypeMDSG Type
MDS-70A(B/C)70/64708085167.07.5
MDS-80A(B/C)80/72808085167.58.0
MDS-90A(B/C)90/8090100105188.08.5
MDS-100A(B/C)100/90100100105188.59.0
MDS-120A(B/C)120/1121201001051814.515.0
MDS-130A(B/C)130/1161301251302015.516.0
MDS-150A(B/C)150/1361501251302016.016.5
MDS-170A(B/C)170/1561701501602224.024.5
MDS-200A(B/C)200/1802001501702236.036.5
MDS-250A(B/C)250/2302501501702439.039.5

MDS MDSG expansion clamp, 30 degree MDS MDSG expansion clamp, 90 degree

Expansion clamp with a foot plate: MGGD, MGGD-WP. Supports either side: MGG, MGG1. Tube-to-conductor version: MGS / MGSG expansion connector.

Note: A, B and C share one table — order by the angle your drawing shows. MDSG is a flat 0.5 kg over MDS on every size. No foot column: this clamp joins tube ends, it does not carry the bus to steel. State the wall with the bore.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: