PF Power Fittings Technical Reference

MGG Tubular Busbar Fixed Support Clamp

MGG tubular busbar fixed support clamp

Models: 21 sizes · Reference Weight: 2.1–18.0 kg · Function: fixed support — no axial movement

Two Variables, Not One

Every model is MGG-<busbar OD> or MGG-<busbar OD>(<D>), and there are two things to select:

Variable Values What it decides
Busbar OD 50 – 250 mm The clamp bore
Foot size D 140, 225, 250, 280 mm The base plate and the anchor pattern

D is not a tolerance or a variant — it is the foot: the plate the clamp is bolted down through, dimensioned across the plate in the catalogue’s own view, with the anchor slots in it. The same busbar is offered on up to four of them, which is why the table has 21 rows and only 13 busbar sizes.

Four Feet

D Busbar sizes Bolt C Weight band
140 mm 50 – 170 (11 sizes) 14 mm 2.1 – 9.0 kg
225 mm 80 – 130 (6 sizes) 18 mm 4.8 – 8.5 kg
250 mm 150 – 200 (3 sizes) 18 mm 10.0 – 12.0 kg
280 mm 250 (1 size) 22 mm 18.0 kg

The 140 mm foot is the standard one and covers the whole small range. The bigger feet are for the heavier end of the bus and for structures whose anchor pattern is already fixed in the steel — a wider foot spreads the same overturning moment over a wider bolt pattern.

Bolt size C follows the foot, not the busbar: 14 mm at D 140, 18 mm at 225 and 250, 22 mm at 280. The bigger foot exists to take the bigger anchor.

Same Busbar, Different Foot, Different Weight

Two rows for 80 mm and two for 150 mm make the point:

Model D H Weight
MGG-80 140 mm 98 mm 4.0 kg
MGG-80(225) 225 mm 98 mm 4.8 kg
MGG-150 140 mm 150 mm 8.4 kg
MGG-150(250) 250 mm 150 mm 10.0 kg

Same bore, same H, 0.8 and 1.6 kg heavier. H does not change with D; only the plate under it does. An MGG-80 and an MGG-80(225) put the bus at exactly the same level and differ only in the foot.

That is the single most common confusion on this page: H is the bus level above the base plate, D is the size of the foot. Only H moves the bus.

Fixed Means Fixed

MGG grips the busbar hard — no axial freedom. Use it:

  • At the midpoint of a bus run, where thermal expansion is zero by symmetry
  • At one end of a short run where there is no expansion joint and no need for one
  • Where the bus is anchored against fault current forces

Do not use MGG everywhere on a long run. A tubular bus expands and contracts with temperature and the clamps have to let it. One fixed clamp plus sliding supports either side is the normal arrangement — the sliding version is MGG1.

MGG tubular busbar fixed support clamp, base

Technical Parameters

ModelTubular Busbar O.D.
(mm)
Main Dimensions (mm)Reference Weight
(kg)
ØDHC
MGG-50505014080142.1
MGG-60606014090142.5
MGG-70707014090142.8
MGG-80808014098144.0
MGG-909090140102144.3
MGG-100100100140114144.7
MGG-110110110140120145.0
MGG-120120120140122145.3
MGG-130130130140135147.3
MGG-150150150140150148.4
MGG-170170170140170149.0
MGG-80(225)808022598184.8
MGG-90(225)9090225102185.3
MGG-100(225)100100225114185.5
MGG-110(225)110110225120186.0
MGG-120(225)120120225122186.4
MGG-130(225)130130225135188.5
MGG-150(250)1501502501501810.0
MGG-170(250)1701702501701810.9
MGG-200(250)2002002502001812.0
MGG-250(280)2502502802502218.0

Sliding support: MGG1 sliding support clamp. Alternative fixed body: MGG2 fixed support clamp. Taller Z-frame version: MGG-Z fixed clamp. Busbar expansion joint: MGGD expansion clamp.

Note: State busbar OD and foot size D — the same bore exists in up to four feet, and the foot sets the anchor pattern.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: