MGG Tubular Busbar Fixed Support Clamp

Models: 21 sizes · Reference Weight: 2.1–18.0 kg · Function: fixed support — no axial movement
Two Variables, Not One
Every model is MGG-<busbar OD> or MGG-<busbar OD>(<D>), and there are two things to select:
| Variable | Values | What it decides |
|---|---|---|
| Busbar OD | 50 – 250 mm | The clamp bore |
| Foot size D | 140, 225, 250, 280 mm | The base plate and the anchor pattern |
D is not a tolerance or a variant — it is the foot: the plate the clamp is bolted down through, dimensioned across the plate in the catalogue’s own view, with the anchor slots in it. The same busbar is offered on up to four of them, which is why the table has 21 rows and only 13 busbar sizes.
Four Feet
| D | Busbar sizes | Bolt C | Weight band |
|---|---|---|---|
| 140 mm | 50 – 170 (11 sizes) | 14 mm | 2.1 – 9.0 kg |
| 225 mm | 80 – 130 (6 sizes) | 18 mm | 4.8 – 8.5 kg |
| 250 mm | 150 – 200 (3 sizes) | 18 mm | 10.0 – 12.0 kg |
| 280 mm | 250 (1 size) | 22 mm | 18.0 kg |
The 140 mm foot is the standard one and covers the whole small range. The bigger feet are for the heavier end of the bus and for structures whose anchor pattern is already fixed in the steel — a wider foot spreads the same overturning moment over a wider bolt pattern.
Bolt size C follows the foot, not the busbar: 14 mm at D 140, 18 mm at 225 and 250, 22 mm at 280. The bigger foot exists to take the bigger anchor.
Same Busbar, Different Foot, Different Weight
Two rows for 80 mm and two for 150 mm make the point:
| Model | D | H | Weight |
|---|---|---|---|
| MGG-80 | 140 mm | 98 mm | 4.0 kg |
| MGG-80(225) | 225 mm | 98 mm | 4.8 kg |
| MGG-150 | 140 mm | 150 mm | 8.4 kg |
| MGG-150(250) | 250 mm | 150 mm | 10.0 kg |
Same bore, same H, 0.8 and 1.6 kg heavier. H does not change with D; only the plate under it does. An MGG-80 and an MGG-80(225) put the bus at exactly the same level and differ only in the foot.
That is the single most common confusion on this page: H is the bus level above the base plate, D is the size of the foot. Only H moves the bus.
Fixed Means Fixed
MGG grips the busbar hard — no axial freedom. Use it:
- At the midpoint of a bus run, where thermal expansion is zero by symmetry
- At one end of a short run where there is no expansion joint and no need for one
- Where the bus is anchored against fault current forces
Do not use MGG everywhere on a long run. A tubular bus expands and contracts with temperature and the clamps have to let it. One fixed clamp plus sliding supports either side is the normal arrangement — the sliding version is MGG1.

Technical Parameters
| Model | Tubular Busbar O.D. (mm) | Main Dimensions (mm) | Reference Weight (kg) | |||
|---|---|---|---|---|---|---|
| Ø | D | H | C | |||
| MGG-50 | 50 | 50 | 140 | 80 | 14 | 2.1 |
| MGG-60 | 60 | 60 | 140 | 90 | 14 | 2.5 |
| MGG-70 | 70 | 70 | 140 | 90 | 14 | 2.8 |
| MGG-80 | 80 | 80 | 140 | 98 | 14 | 4.0 |
| MGG-90 | 90 | 90 | 140 | 102 | 14 | 4.3 |
| MGG-100 | 100 | 100 | 140 | 114 | 14 | 4.7 |
| MGG-110 | 110 | 110 | 140 | 120 | 14 | 5.0 |
| MGG-120 | 120 | 120 | 140 | 122 | 14 | 5.3 |
| MGG-130 | 130 | 130 | 140 | 135 | 14 | 7.3 |
| MGG-150 | 150 | 150 | 140 | 150 | 14 | 8.4 |
| MGG-170 | 170 | 170 | 140 | 170 | 14 | 9.0 |
| MGG-80(225) | 80 | 80 | 225 | 98 | 18 | 4.8 |
| MGG-90(225) | 90 | 90 | 225 | 102 | 18 | 5.3 |
| MGG-100(225) | 100 | 100 | 225 | 114 | 18 | 5.5 |
| MGG-110(225) | 110 | 110 | 225 | 120 | 18 | 6.0 |
| MGG-120(225) | 120 | 120 | 225 | 122 | 18 | 6.4 |
| MGG-130(225) | 130 | 130 | 225 | 135 | 18 | 8.5 |
| MGG-150(250) | 150 | 150 | 250 | 150 | 18 | 10.0 |
| MGG-170(250) | 170 | 170 | 250 | 170 | 18 | 10.9 |
| MGG-200(250) | 200 | 200 | 250 | 200 | 18 | 12.0 |
| MGG-250(280) | 250 | 250 | 280 | 250 | 22 | 18.0 |
Related Clamps
Sliding support: MGG1 sliding support clamp. Alternative fixed body: MGG2 fixed support clamp. Taller Z-frame version: MGG-Z fixed clamp. Busbar expansion joint: MGGD expansion clamp.
Note: State busbar OD and foot size D — the same bore exists in up to four feet, and the foot sets the anchor pattern.