Models: 13 sizes · Reference Weight: 0.14–2.90 kg · Function: closes the open end of a tubular busbar
The Model Number Is the Tube, the Ø Is the Bore
This is the one thing to get right on this page. The model number is the tube outside diameter; the Ø column is the spigot that goes into the tube, which is the tube’s inside diameter.
| Model | Tube OD | Spigot Ø | Wall it assumes |
|---|---|---|---|
| MGF-50 | 50 mm | 45 mm | 2.5 mm |
| MGF-80 | 80 mm | 72 mm | 4 mm |
| MGF-100 | 100 mm | 90 mm | 5 mm |
| MGF-150 | 150 mm | 136 mm | 7 mm |
| MGF-200 | 200 mm | 180 mm | 10 mm |
| MGF-250 | 250 mm | 230 mm | 10 mm |
The cap only fits if your tube has the wall the table assumes. A 200 mm tube with an 8 mm wall has a 184 mm bore and an MGF-200 will be loose in it. Send us the outside diameter and the wall, and we will confirm the spigot size.
The Dome Is There for the Field, Not the Rain
A domed cap does two jobs:
- It closes the tube. An open tube takes water, and a tube that freezes splits along its length.
- It rounds off the cut end. The sawn end of a 250 mm aluminium tube is a sharp edge, and a sharp edge at busbar potential is where corona starts. A dome with a large radius spreads that field.
The SR column is the radius of the dome, and it stays close to the tube outside diameter across the range — so the cap is roughly hemispherical. Two rows are noticeably flatter than the rest: MGF-100 and MGF-110 have SR 80 mm on tubes of 100 and 110 mm.
Reading the Rest of the Table
- H — the skirt height, 10 mm at 50 mm, 15 mm from 60 to 170 mm, 25 mm at 200 and 250. This is how deep the cap sits into the tube.
- M — 8 mm up to 100 mm and 10 mm above. In the section drawing it measures an internal feature, not an outside surface. The catalogue does not label it, and it is not a dimension you order by.
Technical Parameters
| Model | Tubular Busbar I.D./O.D. (mm) | Main Dimensions (mm) | Reference Weight (kg) | |||
|---|---|---|---|---|---|---|
| Ø | SR | H | M | |||
| MGF-50 | 50/45 | 45 | 50 | 10 | 8 | 0.14 |
| MGF-60 | 60/54 | 54 | 65 | 15 | 8 | 0.17 |
| MGF-70 | 70/64 | 64 | 70 | 15 | 8 | 0.20 |
| MGF-80 | 80/72 | 72 | 70 | 15 | 8 | 0.32 |
| MGF-90 | 90/80 | 80 | 80 | 15 | 8 | 0.40 |
| MGF-100 | 100/90 | 90 | 80 | 15 | 8 | 0.43 |
| MGF-110 | 110/100 | 100 | 80 | 15 | 10 | 0.61 |
| MGF-120 | 120/110 | 110 | 120 | 15 | 10 | 1.00 |
| MGF-130 | 130/116 | 116 | 120 | 15 | 10 | 1.10 |
| MGF-150 | 150/136 | 136 | 150 | 15 | 10 | 1.20 |
| MGF-170 | 170/156 | 156 | 160 | 15 | 10 | 1.30 |
| MGF-200 | 200/180 | 180 | 200 | 25 | 10 | 2.40 |
| MGF-250 | 250/230 | 230 | 250 | 25 | 10 | 2.90 |

Related Fittings
Damped caps for the same tube: MGF1 damping type from 70 to 150 mm, MGF-Z damping type from 170 to 250 mm. The clamp that anchors the end of the run: MGD end fixing clamp. Supports: MGG, MGG1.
Note: Order by tube outside diameter and wall — the spigot is bored to the inside diameter, so a heavier wall tube needs a different cap.