PF Power Fittings Technical Reference

MGF1 Tubular Busbar End Cap, Damping Type

MGF1 tubular busbar end cap, damping type

Models: 8 sizes · Reference Weight: 0.41–1.80 kg · Function: end cap with a damping conductor

A Cap That Also Damps the Tube

A plain MGF cap closes the tube. This one closes it and carries a short length of ACSR into the bore — that is the “damping conductor” column, LGJ-240 through LGJ-500.

A 20 m length of 150 mm aluminium tube is a light, springy beam with a low bending mode, and a steady cross wind will drive it. A mass on a flexible conductor inside the tube is a tuned absorber for that mode: it moves out of phase with the tube and takes the energy out. One cap at each end is the usual arrangement.

Roughly Twice the Weight of the Plain Cap

Tube Plain MGF MGF1 Ratio
70 mm 0.20 kg 0.41 kg 2.1×
90 mm 0.40 kg 0.90 kg 2.3×
120 mm 1.00 kg 1.71 kg 1.7×
150 mm 1.20 kg 1.80 kg 1.5×

The extra 0.2 to 0.8 kg is the conductor grip and the boss that holds it. It is not a heavy part, but it is at the end of a cantilever, which is where it does the most good and where the tube sees the most stress.

The Conductor Steps in Two Places

Tube sizes Damping conductor Grip bore φ2
70 – 80 mm LGJ-240 22 mm
90 – 110 mm LGJ-300 25 mm
120 – 150 mm LGJ-500 31 mm

Three conductor sizes for eight caps, so the choice is made by tube diameter, not by you. If your specification calls for a different damping conductor, say so — the grip is bored to φ2.

Same Spigot Rule as the Plain Cap

φ1 is the tube inside diameter, and the model number is the tube outside diameter. MGF1-110 has a 100 mm spigot and fits a 110 × 5 tube.

The wall the table assumes: 70 mm → 3 mm, 80 mm → 4 mm, 90 to 120 mm → 5 mm, 130 mm → 7 mm, 150 mm → 7 mm. A heavier wall tube needs a different spigot, so send the OD and the wall when you order.

Technical Parameters

ModelTubular Busbar I.D./O.D.
(mm)
Damping
Conductor
Main Dimensions (mm)Reference Weight
(kg)
ϕ1ϕ2SRHM
MGF₁-7070/64LGJ-2406422701580.41
MGF₁-8080/72LGJ-2407222701580.6
MGF₁-9090/80LGJ-3008025801580.9
MGF₁-100100/90LGJ-30090258015101.0
MGF₁-110110/100LGJ-300100259015101.1
MGF₁-120120/110LGJ-5001103112015101.71
MGF₁-130130/116LGJ-5001163112015101.75
MGF₁-150150/136LGJ-5001363115015101.8

MGF1 damped end cap, section

Plain cap for the same tube: MGF end cap. Damped cap for larger tubes: MGF-Z damping type, 170 to 250 mm. Clamp that anchors the end of the run: MGD end fixing clamp.

Note: φ1 is the tube bore and the model number is the tube OD. Three damping conductors cover the range — LGJ-240, LGJ-300, LGJ-500 — so the cap and the conductor are ordered together.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: