MGD Tubular Busbar End Fixing Clamp

Models: 11 sizes · Reference Weight: 1.37–3.80 kg · Function: clamps the tube at its end
A Support, but at the End of the Run
MGD grips the tube where the run finishes rather than part way along it. It takes the same foot sizes and the same anchor bolts as MGG, so it bolts to the same steel — but it is not the same height.
| Bore | MGG H | MGD H | Difference |
|---|---|---|---|
| 50 mm | 80 mm | 55 mm | −25 mm |
| 60 mm | 90 mm | 58 mm | −32 mm |
| 90 mm | 102 mm | 100 mm | −2 mm |
| 120 mm | 122 mm | 120 mm | −2 mm |
| 150 mm | 150 mm | 130 mm | −20 mm |
MGD is lower than MGG at every bore, by as little as 2 mm and as much as 32 mm. If you put an MGD at the end of a run carried on MGG supports, the last span steps down. Check the two H values before you mix them.
Two Heights in the Table
MGD publishes H and H1, both taken up from the base plate:
- H — to the top of the clamp body, 55 to 130 mm
- H1 — to the shoulder below it, 35 to 50 mm
The pair moves in steps rather than smoothly: H1 is 35 mm at 50 mm bore, 40 mm from 60 to 100, 45 at 110 and 120, 50 at 130 and 150. Those steps are the body sizes.
Two Feet, and a Narrower Range
| Foot D | Busbar sizes | Anchor φ1 | Weight |
|---|---|---|---|
| 140 mm | 50 – 100 (6 sizes) | 14 mm | 1.37 – 2.50 kg |
| 225 mm | 100 – 150 (5 sizes) | 18 mm | 2.80 – 3.80 kg |
The 140 mm foot stops at 100 mm here, where MGG carries it to 170 mm. Above 100 mm there is only the 225 mm foot.
MGD-100 exists on both feet — 2.50 kg on the 140 and 2.80 kg on the 225 — so the model number alone does not tell you which you are buying. The 0.30 kg is the bigger plate underneath.
A Weight Step That Does Not Match the Height Step
Reading down the table:
- 60 → 70 mm: H jumps 58 → 85 mm but the weight only moves 1.43 → 1.50 kg
- 70 → 80 mm: H moves 85 → 90 mm but the weight jumps 1.50 → 2.20 kg
The tallest single height step carries almost no weight, and the next 5 mm of height carries 0.70 kg. That is the pattern of a casting change at one row and a heavier section at the next, and it is worth knowing if you are estimating from the table rather than weighing the part.
Technical Parameters
| Model | Tubular Busbar O.D. (mm) | Main Dimensions (mm) | Reference Weight (kg) | ||||
|---|---|---|---|---|---|---|---|
| Ø | H | H1 | ϕ1 | D | |||
| MGD-50 | 50 | 50 | 55 | 35 | 14 | 140 | 1.37 |
| MGD-60 | 60 | 60 | 58 | 40 | 14 | 140 | 1.43 |
| MGD-70 | 70 | 70 | 85 | 40 | 14 | 140 | 1.50 |
| MGD-80 | 80 | 80 | 90 | 40 | 14 | 140 | 2.20 |
| MGD-90 | 90 | 90 | 100 | 40 | 14 | 140 | 2.40 |
| MGD-100 | 100 | 100 | 105 | 40 | 14 | 140 | 2.50 |
| MGD-100(225) | 100 | 100 | 105 | 40 | 18 | 225 | 2.80 |
| MGD-110(225) | 110 | 110 | 105 | 45 | 18 | 225 | 3.00 |
| MGD-120(225) | 120 | 120 | 120 | 45 | 18 | 225 | 3.20 |
| MGD-130(225) | 130 | 130 | 120 | 50 | 18 | 225 | 3.40 |
| MGD-150(225) | 150 | 150 | 130 | 50 | 18 | 225 | 3.80 |

Related Fittings
Standard support at MGG height: MGG fixed support clamp. Sliding support: MGG1. Cap that closes this end of the tube: MGF end cap. Z frame: MGG-Z.
Note: MGD sits 2 to 32 mm lower than MGG at the same bore, and the 140 mm foot stops at 100 mm. MGD-100 is sold on both feet at different weights, so state the foot when ordering.