PF Power Fittings Technical Reference

MGG1 Tubular Busbar Sliding Support Clamp

MGG1 tubular busbar sliding support clamp

Models: 20 sizes · Reference Weight: 2.5–15.0 kg · Function: sliding support — allows axial thermal movement

Why a Busbar Needs to Slide

A tubular busbar 40 m long grows about 55 mm between 0 °C and 60 °C in aluminium — 40 000 mm × 23 × 10⁻⁶ per K × 60 K. If every support grips it, that movement goes into the supports as a compressive load and into the bus as a bending stress, and on a switchyard gantry it shows up as cracked welds at the fittings.

A sliding support carries the weight and lets the bus travel. The normal arrangement is one fixed clamp at the middle of the run and sliding clamps either side, so each half moves about 27 mm in one direction and the expansion joint goes at the far end of each half, where the travel accumulates.

Sliding Costs Height and Weight

Compare the same busbar in both versions:

Fixed MGG Sliding MGG1
50 mm, D 140 H 80 mm, 2.1 kg H 90 mm, 2.5 kg
100 mm, D 225 H 114 mm, 5.5 kg H 135 mm, 6.2 kg
130 mm, D 225 H 135 mm, 8.5 kg H 155 mm, 9.4 kg
150 mm, D 250 H 150 mm, 10.0 kg H 160 mm, 10.8 kg

The sliding version is 10 to 25 mm taller, because the sliding plate and its guides have to sit between the clamp and the pedestal. The extra height is not evenly distributed — it is 10 mm at 50–60 mm, 20 to 25 mm through 70–130 mm, and back to 10 mm from 150 mm up.

The weight does not follow the height. Across the whole range the difference runs from 0.1 kg lighter to 1.3 kg heavier: at 80 mm the sliding clamp is actually the lighter of the two (3.9 vs 4.0 kg) and at 130 mm it is 1.3 kg heavier (8.6 vs 7.3 kg). Treat the two as different parts, not as a version of each other.

That extra height matters: if you are swapping a fixed clamp for a sliding one on an existing structure, the bus rises by 10–25 mm and the whole run has to be re-levelled.

Three Feet, and a Gap

D Busbar sizes Bolt C
140 mm 50 – 130 (9 sizes) 14 mm
225 mm 100 – 200 (7 sizes) 18 mm
250 mm 150 – 250 (4 sizes) 18 mm

Note the difference from the fixed range: MGG1 has no 280 mm foot and its 140 mm foot stops at 130 mm where MGG goes to 170. The sliding plate assembly does not exist in those combinations.

The ranges overlap deliberately — a 150 mm busbar can take the 225 or the 250 foot, and a 200 mm can take either. The overlap is your choice of anchor pattern for the steel you already have; it is not a way to change the bus level, because H is fixed by the bore.

H Is the Bus Level, D Is the Foot

The two are independent:

  • H — bus axis above the bottom of the base plate, 90 to 220 mm. Set by the bore and by the sliding body, not by D.
  • D — the foot: base plate size and anchor pattern, 140 to 250 mm.

MGG1-150(225) and MGG1-150(250) both put the bus at H 160 mm, but one sits on a 225 mm foot and the other on 250 mm. 1.0 kg apart for 25 mm more plate beneath.

MGG1 tubular busbar sliding support clamp, slide plate

Technical Parameters

ModelTubular Busbar O.D.
(mm)
Main Dimensions (mm)Reference Weight
(kg)
ØDHC
MGG1-50505014090142.5
MGG1-606060140100142.9
MGG1-707070140115143.6
MGG1-808080140120143.9
MGG1-909090140125145.1
MGG1-100100100140135145.3
MGG1-110110110140145145.9
MGG1-120120120140145146.2
MGG1-130130130140155148.6
MGG1-100(225)100100225135186.2
MGG1-110(225)110110225145186.9
MGG1-120(225)120120225145187.4
MGG1-130(225)130130225155189.4
MGG1-150(225)150150225160189.8
MGG1-170(225)1701702251801810.2
MGG1-200(225)2002002252101810.9
MGG1-150(250)1501502501601810.8
MGG1-170(250)1701702501801811.2
MGG1-200(250)2002002502101812.5
MGG1-250(250)2502502502201815.0

Fixed version: MGG fixed support clamp. Sliding Z-frame: MGGH-Z sliding fixed clamp. Fixed Z-frame: MGG-Z fixed clamp. Expansion joint to absorb the travel: MGGD expansion clamp.

Note: Sliding clamps are 10–21 mm taller than the fixed equivalent — check the level of the run. No 280 mm base in this range.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: