PF Power Fittings Technical Reference

MGGD Tubular Busbar Expansion Clamp

MGGD tubular busbar expansion clamp

Models: 10 sizes · Reference Weight: not published — ask us · Function: takes the thermal travel of the run

What the Clamp Does

A tubular busbar grows about 1.4 mm per metre per 10 °C. A 30 m run swings through 80 mm between a cold night and a hot afternoon. Something in the run has to absorb that, and this is the fitting that does it: the tube ends inside the clamp and slides, so the travel is taken here instead of being pushed into the supports and the post insulators.

Put one at each end of a run, or at the end of each half if the run is fixed at the middle. Every other support in between is a sliding clamp.

Length Follows the Tube, Not the Travel

L Busbar sizes
400 mm 70 – 100 (4 sizes)
450 mm 120 – 150 (3 sizes)
500 mm 170 – 250 (3 sizes)

There is no option to buy a longer clamp for a longer run — the length is fixed by the bore. If your travel demand exceeds what the L for your size allows, tell us and we will look at a different arrangement; do not assume the clamp will take any amount of movement.

Three Feet, and a Different Split From the Other Families

Foot D Busbar sizes H
140 mm 70 – 120 (5 sizes) 110 – 145 mm
225 mm 130 – 200 (4 sizes) 155 – 210 mm
250 mm 250 (1 size) 250 mm

The 140 mm foot covers a different range in every family on this site — 50 to 170 in MGG, 50 to 100 in MGD, and 70 to 120 here. Do not carry a foot size across from one table to another.

MGGD also sits higher than the support it sits between: 10 to 23 mm above MGG at the same bore (20 mm at 70 mm, 10 mm from 150 mm up). That is the one place a run will not be level unless you plan for it.

No Weights, and a Wall That Does Not Match the Caps

The weight column in this table is empty for all ten rows. Freight and structural load both need that figure, so ask us and we will weigh one.

One more thing worth catching before you order: this table prints MGGD-120 as 120/112, a 4 mm wall, and the wall sequence down the column runs 3, 4, 5, 5, 4, 7, 7, 7, 10, 10 mm. The caps print the same 120 mm tube as 120/110, a 5 mm wall — MGF and MGF1. MGGD-120 is drilled for 120/112, a 4 mm wall, where the MGF and MGF1 caps print the same tube at 120/110, a 5 mm wall. Confirm the tube you have and order the clamp to it — the wall sequence down the MGGD column runs 3, 4, 5, 5, 4, 7, 7, 7, 10, 10 mm.

Technical Parameters

ModelTubular Busbar O.D./I.D. (mm)Main Dimensions (mm)Reference Weight (kg)
ØLDH
MGGD-7070/6470400140110
MGGD-8080/7280400140115
MGGD-9090/8090400140125
MGGD-100100/90100400140135
MGGD-120120/112120450140145
MGGD-130130/116130450225155
MGGD-150150/136150450225160
MGGD-170170/156170500225180
MGGD-200200/180200500225210
MGGD-250250/230250500250250

Other MGGD variant: MGGD-WP. Expansion clamp with published weights: MDS / MDSG. Supports either side: MGG and MGG1.

Note: No published weights. L is fixed by the bore, not by the travel you need. The 120 mm row prints a 4 mm wall where four other tables print 5 mm — confirm your tube.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: