MGGT Type Jumper Clamp

MGGT jumper clamp

Model: MGGT-250 · Reference Weight: 57.0 kg

One Size, One Model

There is exactly one MGGT in this catalogue: a jumper clamp for a 250 mm tubular busbar, 57.0 kg, with the jumper arm reaching 880 mm.

If your busbar is 130 to 200 mm, this page is not your part — MGTS2, MGTS3 and MXT cover that range. MGGT exists only for the largest tube.

The Two Lengths

Ø L L1
250 mm 1120 mm 880 mm

L is the overall length, L1 is the jumper arm — the distance the conductors run out from the clamp before they leave the fitting. The 240 mm difference is the clamp body and its bolts on the busbar side.

That 880 mm matters on site: the jumper has to clear the busbar, the grading ring and anything else at that support, and the arm is what buys that clearance. Check it against your arrangement before ordering, because there is no longer or shorter MGGT to fall back on.

Where It Sits Against the Others

Busbar sizes Weight Conductors
MGGT 250 mm only 57.0 kg not stated
MGTS2 130 – 250 mm 62.6 – 150.5 kg 2 × NAHLGJQ-1440
MGTS3 130 – 250 mm 71.7 – 159.6 kg 3 conductors
MXT 130 – 250 mm not published 4 or 6, 3150 – 7800 A

MGGT is the lightest 250 mm option on the site by a wide margin — 57 kg against 150.5 for MGTS2 at the same bore. That is because it is a clamp and an arm, not a conductor assembly: the jumper itself is supplied separately.

The table does not state how many conductors the arm carries, and we are not going to assume. Tell us what the jumper is and we will confirm the arm will take it.

Technical Parameters

ModelTubular Busbar O.D. (mm)Main Dimensions (mm)Reference Weight (kg)
ØLL1
MGGT-250250250112088057.0

MGGT jumper clamp — dimension drawing

Two and three conductor fittings: MGTS2, MGTS3. Current-rated: MXT. Clamps for the same bus: MGG, MGG1, MGT-C.

Note: One size only — 250 mm. The 880 mm arm is fixed, so check clearance before ordering. The number of conductors it carries is not stated in the catalogue.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: