PF Power Fittings Technical Reference

MXT Tubular Busbar Jumper Fitting

MXT tubular busbar jumper fitting

Models: 5 sizes · Reference Weight: not published · Function: jumper take-off with a stated current rating

The Only Fitting Here With an Ampere Rating

Every other jumper fitting on this site tells you what conductor it takes. This one tells you how much current it carries — 3150 to 7800 A — and that is a much more useful number when you are sizing a run.

Bore L Conductors Current rating
130 mm 2000 mm 4 3150 A
150 mm 2000 mm 4 3150 A
170 mm 4000 mm 6 4800 A
200 mm 5000 mm 6 7800 A
250 mm 5000 mm 6 7800 A

The Length Doubles at 170 mm

L goes 2000, 2000, 4000, 5000, 5000. The step from 150 to 170 is +2000 mm in one size — the same as the whole length of the two smallest fittings.

That is not a scaling artefact. Between 150 and 170 mm the conductor count goes from 4 to 6, the length doubles and the rating goes up by half. It is a different assembly, not a bigger one. If you are working in a tight bay, the 170 is twice the fitting the 150 is.

The Rating Is Not the Conductor Count

170 mm and 200 mm both carry six conductors, yet one is rated 4800 A and the other 7800 A — 62 % more current on the same number of conductors.

So the rating is not a function of how many conductors there are. Something else changes — the conductor size, or the number of parallel paths inside the fitting — and the catalogue does not say which. Size by the ampere figure, not by the conductor count, and tell us the conductor you intend to use.

The Header Is Mislabeled

The column group is titled “Main Dimensions (mm)”, and it covers four columns, two of which are not millimetres: the number of conductors (4 or 6) and the current rating (3150 to 7800 A).

We print the table with the header as the catalogue has it. Read L as the length and the last two columns as counts and amperes.

No Weight

The weight column is empty on all five rows. For fittings that range up to a 5 m arm, that is the figure you need for lifting and for the load at the support, so ask us before you plan either.

Technical Parameters

ModelTubular Busbar O.D. (mm)Main Dimensions (mm)Reference Weight (kg)
ØLNo. of ConductorsCurrent Rating (A)
MXT-130130130200043150
MXT-150150150200043150
MXT-170170170400064800
MXT-200200200500067800
MXT-250250250500067800

Two and three conductor fittings with published weights: MGTS2, MGTS3. Single size for 250 mm: MGGT. Clamps for the run: MGG, MGG1.

Note: The length doubles from 150 to 170 mm, and the rating rises 62 % between 170 and 200 on the same conductor count — size by amperes. No weights published.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: