PF Power Fittings Technical Reference

YZ Live Line Clamp

Models: YZ-1 – YZ-3 · Busbar: LGJ-35 to LGJ-500 mm² · Weight: 0.32–0.45 kg

YZ Live Line Clamp

Three Sizes, And The Third Has No Down Lead

A live-line clamp taps a down lead onto a busbar without taking the circuit out. That needs two conductor ranges per row — the busbar it clamps and the lead it carries.

YZ-3 prints one. Its down-lead cell is blank. The largest size on the sheet covers a 300–500 mm² busbar and does not say what it can carry away from it. As printed, YZ-3 cannot be selected for a tap.

That is the whole top of the range: if the busbar is 300 mm² or bigger, the sheet has a clamp for it and no way to specify the lead. Ask us for the down-lead range of YZ-3 before designing around it — it is a printing omission, not a missing product.

The Down Lead Changes Conductor Family Halfway

Look at the type of the down lead, not just its size:

Model Busbar Down lead
YZ-1 LGJ-35~95 LJ-25~70
YZ-2 LGJ-120~240 LGJ-35~70
YZ-3 LGJ-300~500 not printed

YZ-1 carries an all-aluminium lead (LJ); YZ-2 carries an ACSR lead (LGJ). Same product family, two different conductor types on adjacent rows.

So the two sizes are not interchangeable even where the sizes overlap — a 70 mm² lead is at the top of both ranges, but on YZ-1 it is LJ-70 and on YZ-2 it is LGJ-70, which is a different diameter over a different core. Match the lead type to the row, not just the square millimetres.

d1 And d2 Do Not Move

Both are constant across the whole sheet: d1 = 12 mm, d2 = 4 mm, from a 35 mm² busbar to a 500 mm² one.

Neither can be a conductor dimension. A 25 mm² all-aluminium conductor — the smallest thing on the page — is about 6 mm outside, already well above d2’s 4 mm, and the busbar goes from roughly 8 mm to 30 mm across the three rows while d1 stays at 12.

So d1 and d2 are features of the fitting, not of the conductor: most likely the hot-stick socket and the lead’s fixing hole. The sheet does not name them, and with the two conductor ranges already in the table there is no column left that describes the mechanical interface. Ask for the drawing before you check the clamp against a stick or a terminal.

L1 Is Not Part Of L

On YZ-1, L is 30 mm and L1 is 32 mm — L1 is longer than the dimension it would normally be a portion of. On YZ-2 and YZ-3 the two are equal (40 and 40, 50 and 50).

So L1 is not a take-up section the way it is on the tension clamps elsewhere in this catalogue; it is an independent overall dimension, and on YZ-1 it stands 2 mm off L because one of the two is rounded. Do not subtract them and assume a 2 mm gap.

R is the only dimension that grows cleanly: 8, 12, 16 mm across the three sizes, in step with the busbar.

The Weight Barely Moves

Three sizes, 0.32, 0.40 and 0.45 kg — steps of +25 and +12.5 per cent while L grows by 10 mm each time and R by 4 mm.

The third size adds half the metal of the second for the same dimensional growth, and it covers a busbar range 40 per cent wider. A clamp that takes a 500 mm² busbar at 0.45 kg is a light part for the duty; worth checking against the drawing if the line has short-circuit forces to withstand, because the sheet prints no rated current, no short-circuit rating and no clamping force.

What “Live Line” Would Require

The title says live line, and the table does not show it. There is no eye, no socket, no tool fitting and no rated voltage printed anywhere on the page.

A clamp worked with a hot stick needs a defined interface for the stick, a shape that will not drop the lead during the operation, and a rated voltage for the insulation distance. None of the three appears here. If the clamp is to be installed live, ask us to confirm the stick fitting and the voltage rating in writing — the drawing is the only place they can come from.

Technical Parameters

YZ Live Line Clamp Drawing YZ Live Line Clamp Application

ModelApplicable ConductorMain Dimensions (mm)Reference Weight (kg)
Busbar (mm2)Down Lead(mm2)
d1d2RLL1
YZ-1LGJ-35~95LJ-25~70124830320.32
YZ-2LGJ-120~240LGJ-35~701241240400.40
YZ-3LGJ-300~5001241650500.45

Stud terminals rather than busbar taps: SBG, SBT. Bolted service clamps for a span: JKG / JKL. Insulated piercing clamps: JCD meter box clamp.

Note: Three sizes; YZ-3 prints no down-lead range, so the largest busbar size cannot be specified as a tap. The down-lead family changes between rows — LJ-2570 on YZ-1, LGJ-3570 on YZ-2 — so overlapping sizes are not interchangeable. d1 (12 mm) and d2 (4 mm) are constant across a 35 to 500 mm2 busbar range and cannot be conductor dimensions; a 25 mm2 all-aluminium lead is already about 6 mm outside. L1 exceeds L on YZ-1 (32 against 30). Weight moves only 0.32 to 0.45 kg, and the sheet prints no rated current, no short-circuit rating and no hot-stick fitting despite the title.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: