PF Power Fittings Technical Reference

MTM Tubular Busbar T Connector

MTM tubular busbar T connector

Models: MTM-70/70 to MTM-200/200 (10 sizes) · Reference Weight: 7.5–35.0 kg · Body: aluminium

Both Sides the Same Size

MTM-70/70 joins a 70 mm busbar to a 70 mm busbar. Every model in the range has the same number on both sides — there is no reducing size on this page. Ø1 and Ø2 both equal the model value.

That is the defining feature: MTM is for busbar-to-busbar tees where the two runs are the same tube, not for busbar-to-conductor drops (which is the MTL and MTLY job).

Model Ø1 = Ø2 Weight
MTM-70/70 70 mm 7.5 kg
MTM-80/80 80 mm 8.5 kg
MTM-90/90 90 mm 9.5 kg
MTM-100/100 100 mm 11.0 kg
MTM-110/110 110 mm 11.0 kg
MTM-120/120 120 mm 12.0 kg
MTM-130/130 130 mm 15.0 kg
MTM-150/150 150 mm 20.0 kg
MTM-170/170 170 mm 23.0 kg
MTM-200/200 200 mm 35.0 kg

Two Pairs of Sizes Share a Weight

MTM-100/100 and MTM-110/110 are both 11.0 kg, with only the bore differing. Then MTM-120/120 jumps to 12.0 kg.

One possibility is that 100 and 110 share a casting with two bore sizes; another is that the 110 figure was carried across. The rest of the column climbs smoothly, and 11.0 kg appearing twice on adjacent rows is the only interruption.

It does not change the selection — you order the bore you need — but it does mean the 110 mm fitting is not heavier than the 100 mm one, which is the opposite of what a weight-based cost model would assume.

Weight Doubles Between 130 and 200

The upper end is where the mass is:

  • 70 to 120 mm — 7.5 to 12.0 kg, roughly linear
  • 130 to 170 mm — 15.0 to 23.0 kg
  • 200 mm — 35.0 kg

From 170 to 200 mm the weight goes up 12 kg for 30 mm of bore. At that size the body is a substantial casting, and 35 kg on a busbar is a load the support has to be designed for. If you are working at 200 mm and mass matters, check whether the tee can be split into a clamp plus a bolt-on saddle rather than one casting.

Where MTM Is Used

  • Busbar tee-offs between two runs of the same tube — the classic switchyard bus layout
  • Loop connections where a bus turns through 90° into another bay
  • Busbar extensions where a new section ties into an existing one of the same size

It is not for conductor drops. If one side is a conductor rather than a tube, you want MTL or MTLY.

MTM tubular busbar T connector, dimensioned

Technical Parameters

ModelTubular Busbar O.D. (mm)Main Dimensions (mm)Reference Weight (kg)
Ø1Ø2
MTM-70/707070707.5
MTM-80/808080808.5
MTM-90/909090909.5
MTM-100/10010010010011.0
MTM-110/11011011011011.0
MTM-120/12012012012012.0
MTM-130/13013013013015.0
MTM-150/15015015015020.0
MTM-170/17017017017023.0
MTM-200/20020020020035.0

Busbar-to-conductor tee: MTL busbar T clamp and MTLY. Angled 0/30/90° tees: MG/MR T connector. Busbar expansion joint: MGGD expansion clamp. Busbar support: MGG fixed support clamp.

Note: Equal diameter only — both sides of the model are always the same number. 100 and 110 mm share a weight.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: