PF Power Fittings Technical Reference

MGH-T Type Adjustable Damping Ring

MGH-T adjustable damping ring

Models: 4 sizes · Reference Weight: not published · Function: adjustable ring on a hollow-core conductor

This One Is Built Around LGKK-600

The A and B versions of this ring use LGJ-240/30 — a stranded conductor, 21.6 mm. This one uses LGKK-600, the hollow-core aluminium tube, and its grip is 51 mm:

Busbar Conductor Grip Ø1
150 mm LGKK-600 51 mm
170 mm LGKK-600 51 mm
200 mm LGKK-600 51 mm
250 mm LGKK-600 51 mm

A 51 mm hollow tube is a much stiffer damping element than a 21.6 mm stranded conductor of the same mass, and it carries current while it damps. That is the reason to specify this version rather than the A.

The LGKK Trap

LGKK-600 is 51 mm. LGKK-900 is 49 mm — the 900 is thinner, not thicker. That is true of this conductor family and it catches people out on every page where it appears.

So a 51 mm grip fits LGKK-600 and will not fit LGKK-900. If your run uses the 900, tell us before ordering; this fitting is dimensioned for the 600.

Range and What Is Missing

Four busbar sizes, 150 to 250 mm — the same four as MGH-A and MGH-B. Nothing below 150 mm.

As on those pages, the table publishes no weight and no H. Only the bore, the conductor and the grip are given, so clearance, freight and load all have to come from us.

Technical Parameters

ModelTubular Busbar O.D. (mm)Applicable Flexible Conductor TypeMain Dimensions (mm)
ØØ1
MGH-150T150LGKK-60015051
MGH-170T170LGKK-60017051
MGH-200T200LGKK-60020051
MGH-250T250LGKK-60025051

Ring on a stranded conductor: MGH-A, MGH-B. Fixed 550 mm rings: MGTA-1, MGTA-2. Supports: MGG, MGG1.

Note: Built for LGKK-600 at a 51 mm grip — and LGKK-900 is 49 mm, so it will not fit the larger conductor. No weight or height published.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: