PF Power Fittings Technical Reference

MGH Adjustable Damping Ring for Tubular Busbar

MGH adjustable damping ring

Models: MGH-150A(B) to -250A(B), 4 sizes · Conductor: LGJ-240/30 · Grip: 21.6 mm

Adjustable Means Position, Not Size

All four sizes take the same conductor, LGJ-240/30, at the same 21.6 mm grip. Nothing in the table varies with the busbar except the bore it clamps to:

Busbar Conductor Grip D
150 mm LGJ-240/30 21.6 mm
170 mm LGJ-240/30 21.6 mm
200 mm LGJ-240/30 21.6 mm
250 mm LGJ-240/30 21.6 mm

So the ring is one size for the whole range, and “adjustable” is about where on the tube it sits, not about the ring changing size. That is the useful part: you move the damping mass to the point that actually oscillates, instead of accepting where a fixed clamp puts it.

A and B Are One Table

The ring is catalogued as MGH-A and MGH-B, and the two letters share one table, row for row — same busbar range, same conductor, same 21.6 mm grip. Nothing in the dimensions separates them.

Order the letter your drawing carries. If it names neither, state the busbar diameter and we supply the standard adjustable ring; the code goes on the quotation either way.

The Ring Diameter Comes With the Drawing

The table gives the bore, the conductor and the grip. It does not give three figures a layout needs:

  • Ø1, the ring diameter — the biggest object on the fitting, so clearance to a wall, another phase or a live part cannot be checked from this page.
  • The weight — no freight figure and no mass for the tube load.
  • The height — where the ring sits relative to the busbar centre line.

All three travel with the outline drawing that ships with the quotation. Ask for it before the layout is frozen, and we will put Ø1, the height and the weight on it for the size you are buying.

Compare the MGTA-1 static contact ring, which publishes a 550 mm ring on every size. That ring is a different fitting, not a substitute for this one.

Four Sizes, All Large Tube

150 to 250 mm. There is no small version: an 80 or 100 mm tube uses the MGTA static contact rings instead, which cover the small end. For the hollow-core LGKK conductor, the MGH-T takes the same ring on a different grip.

Technical Parameters

ModelTubular Busbar O.D. (mm)Applicable Flexible Conductor TypeMain Dimensions (mm)
ØD
MGH-150A(B)150LGJ-240/3015021.6
MGH-170A(B)170LGJ-240/3017021.6
MGH-200A(B)200LGJ-240/3020021.6
MGH-250A(B)250LGJ-240/3025021.6

MGH-B adjustable damping ring

For the hollow-core conductor: MGH-T. Static contact rings: MGTA-1, MGTA-2. Rings built onto a T clamp: MGT-CS, MGT-CD.

Note: One conductor and one grip across all four sizes — the adjustment is the position on the tube. A and B share the table. Ask for the drawing to get Ø1, the height and the weight.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: