PF Power Fittings Technical Reference

MGT-C Type Vertical Terminal Clamp

MGT-C vertical terminal clamp

Models: 13 sizes · Reference Weight: 2.0–19.5 kg · Function: terminates a busbar vertically at equipment

Vertical, Not Horizontal

The MGP clamp presents its terminal pad sideways. This one presents it downward or upward, which is what you need where the connection leaves the bus vertically — into a transformer top, a wall bushing, or a disconnector mounted below the run.

Same job, same body, different exit direction:

Bore MGP MGT-C Difference
50 mm 1.6 kg 2.0 kg +0.4 kg
100 mm 2.4 kg 3.8 kg +1.4 kg
150 mm 4.8 kg 8.2 kg +3.4 kg
200 mm 8.5 kg 13.9 kg +5.4 kg
250 mm 11.0 kg 19.5 kg +8.5 kg

The A, H and B columns are identical on both pages, row for row. So the two are the same clamp and differ only in the terminal: the vertical pad has to carry the connection’s weight in bending, and that is what the growing weight difference is buying.

One Row Breaks the Weight Progression

The gap to MGP rises steadily and then stumbles:

Bore 130 150 170 200
MGT-C 7.2 kg 8.2 kg 8.5 kg 13.9 kg
Gap to MGP +2.9 +3.4 +1.5 +5.4

At 170 mm the vertical clamp is only 1.5 kg heavier than the horizontal, where at 150 mm it is 3.4 kg and at 200 mm 5.4 kg — the shape of the casting at that size, where the vertical body gains least. If the mass matters on a 170 mm terminal, we weigh one with the quotation.

Thirteen Sizes, Two Small Bodies

MGT-C runs the full 50 to 250 mm in thirteen steps — a wider range than most of this section. MGT-50C gets its own smaller body at A 50 / H 80 / B 14, then the 60 to 80 band is 80 / 85 / 16.

If you are sizing down from a 60 mm clamp, the 50 is a different fitting, not a scaled one.

Also Used on the Damping Ring Clamps

The same body appears twice more on this site with a damping ring added: MGT-CD and MGT-CS. Both use these A/H/B figures unchanged.

Technical Parameters

ModelTubular Busbar O.D.
(mm)
Main Dimensions (mm)Reference Weight
(kg)
ØAHB
MGT-50C50505080142.0
MGT-60C60608085162.3
MGT-70C70708085162.5
MGT-80C80808085162.7
MGT-90C9090100105183.3
MGT-100C100100100105183.8
MGT-110C110110100105185.2
MGT-120C120120100105185.4
MGT-130C130130125130207.2
MGT-150C150150125130208.2
MGT-170C170170150160228.5
MGT-200C2002001501702213.9
MGT-250C2502501501702419.5

Horizontal terminal: MGP. With a damping ring: MGT-CD, MGT-CS. Supports: MGG, MGG1.

Note: Same clamp body as MGP with a vertical terminal pad — 0.4 to 8.5 kg heavier, and the 170 mm row breaks the progression at +1.5 kg.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: