PF Power Fittings Technical Reference

MGS Tubular Busbar Expansion Joint

MGS tubular busbar expansion joint

Models: 11 sections · Nominal Failure Load: 0.8–2.4 kN · Function: flexible joint between two busbar ends

This Table Is Not Measured in Bore

Every other page in this section is organised by tube diameter. This one is not. The model number is two section figures, B and A, and the last column is a failure load in kilonewtons, not a weight.

That tells you what it is: a flexible element between two rigid busbar ends, sized by how much copper or aluminium is in the strap, not by what it clamps onto.

Three Sections, Symmetrical

The joint has three parts — an end section, a middle section, and an end section again:

MGS expansion joint, left middle right sections

  • L1 — the two end sections, identical to each other on every row
  • L2 — the middle section, 170 mm on all eleven rows
  • A — the width. This is the figure after the multiplication sign in the model number.

L1 Has No Rule, and You Should Not Assume One

L1 is 110, 120 or 170 mm, and it does not follow A, it does not follow B, and it moves in both directions:

Model A B L1
MGS-10×120 120 mm 10 110 mm
MGS-12×120 120 mm 12 170 mm
MGS-10×125 125 mm 10 170 mm
MGS-12×125 125 mm 12 120 mm

Same width, opposite L1. L1 decides the overall length of the joint, so read it off the row you are ordering rather than scaling from a nearby size.

The Failure Load Tracks the Section

On nine of the eleven rows the nominal failure load falls between 1.1 and 1.6 kN per 1000 units of B × A:

Model B × A Failure load kN per 1000
MGS-8×80 640 0.8 kN 1.25
MGS-12×120 1440 2.0 kN 1.39
MGS-12.5×125 1563 2.2 kN 1.41
MGS-12×150 1800 2.4 kN 1.33

Two rows sit outside that band, and in opposite directions: MGS-10×120 gives 1.9 kN from 1200 units (1.58 per 1000, the highest in the table) while MGS-15×100 gives 1.8 kN from 1500 units (1.20, the lowest). So a smaller section is rated above a larger one.

These are nominal failure loads, not working loads. Design to a fraction of them; we will not quote a safety factor for you without knowing the duty.

Technical Parameters

LeftMiddleRightWidth
L1L2L1A
ModelMain Dimensions (mm)Nominal Failure Load(kN)
AL1L2HB
MGS-8×80801701703580.8
MGS-10×808017017035100.9
MGS-10×10010011017035101.4
MGS-15×10010011017035151.8
MGS-10×12012011017035101.9
MGS-12×12012017017035122.0
MGS-10×12512517017035102.0
MGS-12×12512512017035122.1
MGS-12.5×1251251201703512.52.2
MGS-10×15015012017035102.3
MGS-12×15015012017035122.4

Expansion clamp on a support foot: MGS expansion joint with foot. Joint on the Z frame: MGSS-A, MGSS-B. Support-type expansion clamps: MSZD single, MSZS double.

Note: Dimensioned by section (B and A), not by tube bore. L1 varies 110 to 170 mm with no rule — read it per row. The failure load is nominal, and two rows break the trend.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: