PF Power Fittings Technical Reference

MGC Suspended Tubular Busbar Clamp

MGC suspended tubular busbar clamp

Models: 8 shallow-drop sizes, 9 deep-drop · Reference Weight: 4.6–24.0 kg · Function: hangs the busbar from above

Hanging Instead of Standing

Every other support in this section is bolted down — the bus sits on a pedestal. MGC is the opposite: it clamps the tube and hangs it from a structure above, which is how you run a tubular busbar under a roof truss or across a span where there is nothing to stand on.

That changes which dimension matters. H sets how low the bus hangs, and it is a clamp property, not a site adjustment. The family is made in two drop depths, and they are not interchangeable at the same level:

Shallow body (A / C) Deep body (B)
Bore range 100 – 250 mm 80 – 200 mm
H 140 – 230 mm 220 – 370 mm
Weight 6.9 – 24.0 kg 4.6 – 22.0 kg
Sizes 8 9

A 250 mm bus hangs 90 mm lower than a 100 mm one on the same structure.

The Shallow Body, A and C

The shallow body is made in two letters, A and C. The table is identical for both, row for row — same bores, same H, same C, same M, same weights. The letter describes how the clamp is hung from the structure, not how big it is, so both occupy the same box.

Order the letter your drawing names. If it names neither, state the bore and we supply the standard hanging arrangement.

Bore 100 110 120 130 150 170 200 250
H 140 150 150 150 165 172 190 230

The 250 mm bus hangs 90 mm lower than the 100 mm one. If the clearance under the bus is tight, H is the number to check — and it is why this family does not simply scale.

The Bolt Column Drops to 26 mm at 170

C runs 18, 18, 18, 27, 29, 26, 30, 30 mm down the shallow table. It steps up at 130 mm, up again at 150, then drops to 26 at 170 mm before climbing to 30.

At the same row M jumps the other way, 18 → 27, so at 170 mm the jaw steps down while the bolt steps up. On that size specify both the jaw and the bolt, and we confirm them on the drawing — the figure is on the casting drawing, not in the dimensioned envelope.

The Deep Body, B

MGC-B does the same job with a deeper drop between the hanger and the bus:

Bore Shallow H Deep H Deep hangs lower by
100 mm 140 mm 250 mm 110 mm
120 mm 150 mm 270 mm 120 mm
150 mm 165 mm 310 mm 145 mm
200 mm 190 mm 370 mm 180 mm

The gap widens with bore, from 110 to 180 mm. That is the whole reason the deep body exists: a run that has to clear a deep roof beam, a cable tray or equipment underneath needs the bus hung further down, and you cannot make up 180 mm with a spacer on a clamp designed for 190.

The deep body runs 80 to 200 mm against 100 to 250 mm for the shallow one. So the small end of the range exists only in the deep body, and the large end only in the shallow — a 250 mm bus cannot be hung on the deep body, and an 80 or 90 mm bus cannot be hung on the shallow one.

On the deep body, C and M step together at the same two places, clean and monotonic — 18/16 to 120 mm, 20/18 to 170, then 24/22 at 200.

The Weight Steps Hardest at the Top

Step Weight change H change
120 → 130 +2.0 kg 0 mm
150 → 170 +1.0 kg +7 mm
170 → 200 +1.5 kg +18 mm
200 → 250 +8.5 kg +40 mm

The last step is more than five times any other in the table, on 40 mm of extra height. A 250 mm suspended clamp is 24 kg — a two-person lift, and a point load on the truss that has to be checked.

Compare the two bodies at 200 mm: the shallow one is 15.5 kg at H 190, the deep one 22.0 kg at H 370. Deeper drop, more steel, and 6.5 kg more on the truss.

Technical Parameters

Shallow body, MGC-A / MGC-C — one table, two letters

ModelBusbar Width (mm)Main Dimensions (mm)Reference Weight (kg)
ØHCM
MGC-100A(C)10010014018166.9
MGC-110A(C)11011015018167.5
MGC-120A(C)12012015018189.0
MGC-130A(C)130130150271811.0
MGC-150A(C)150150165291813.0
MGC-170A(C)170170172262714.0
MGC-200A(C)200200190302715.5
MGC-250A(C)250250230302724.0

MGC suspended clamp, dimensions

Deep body, MGC-B — 110 to 180 mm lower

ModelBusbar Width (mm)Main Dimensions (mm)Reference Weight (kg)
ØHCM
MGC-80B808022018164.6
MGC-90B909023018166.2
MGC-100B10010025018167.0
MGC-110B11011026018168.3
MGC-120B120120270201810.0
MGC-130B130130290201813.5
MGC-150B150150310201814.0
MGC-170B170170340201819.2
MGC-200B200200370242222.0

MGC-B suspended clamp MGC-C suspended clamp

Standing supports: MGG, MGG1, MGG-Z. Bracket under a suspended run: MGU, MGJ. Channel busbar suspension: MCD.

Note: Two drop depths — the shallow body (A/C) at H 140-230 mm for 100-250 mm bores, the deep body (B) at H 220-370 mm for 80-200 mm. A and C share one table and one set of weights; the letter is set by your specification. The 200 → 250 step is +8.5 kg.

Sizing data behind this page

A tubular busbar fitting is matched to the tube's outside diameter and wall, not to a conductor area. The twelve tubes are specified outside over inside in millimetres — 70/64 through 300/276 — and the wall, section, stiffness and current rating that follow from each are in: