Pole-Mounted Transformer Area Installation Diagram
Diagrams: 2 · Voltage: 10 kV · Switchgear: GW9-10, RW3-10, Y5WS · Covers shown: 7 kinds · Parts without a catalogue number: 5
Two Stations, One Difference
Both diagrams are the same pole-mounted distribution station drawn as a single line: an overhead 10 kV run arrives, is switched, protected and stepped down to a low-voltage box at the bottom of the pole.
What separates them is on the right-hand side:
- Diagram 1 — the public-transformer layout. Three isolating switches, three dropout fuses and three arresters, one per phase, all on the pole; the transformer feeds a public-transformer integrated box at the base.
- Diagram 2 — the protected layout. The same pole hardware but single-line, and the transformer is fed through a protection switch box mounted separately, reached by a cable from a strain clamp on the run.
Diagram 1 is what you build for a distribution substation serving many customers. Diagram 2 is what you build where the transformer needs its own switch and protection at the point of supply.
The Chain, Top To Bottom
Reading diagram 1 downwards, in the order the current travels:
| Stage | Part | Role |
|---|---|---|
| 1 | JBLY parallel groove clamp | taps the running line onto the pole drop |
| 2 | Disc suspension insulator X-30C / rod pin insulator PC-15/3 | supports and insulates the drop |
| 3 | Isolating switch GW9-10 | visible break for maintenance |
| 4 | Pin insulator ED-2 / P-10T | holds the loop between switch and fuse |
| 5 | Dropout fuse RW3-10 | transformer protection, operable under load |
| 6 | Surge arrester Y5WS | lightning and switching overvoltage to earth |
| 7 | Strain clamp NXL | takes the tension of the cable run off the pole |
| 8 | High-voltage terminal cover | insulates the transformer bushings |
| 9 | Transformer, then the LV box | step-down and distribution |
That is nine stages on one pole, and only three of them — the JBLY clamp, the NXL clamp and the covers — are parts this catalogue lists. The switch, the fuse, the arrester, the insulators and the transformer come from the project.
Every Joint Is Covered, And Nothing Is Covered By Part Number
Count the covers on diagram 1: the parallel groove clamps, the disc insulator string, the strain clamp, the isolating switch, the dropout fuse, the arrester, and the transformer bushings. Seven kinds of cover on one pole — and the drawing labels each one by the thing it covers (cover for GW9-10, cover for RW3-10, cover for Y5WS), never by a PZ or SL part number.
So the diagram proves the practice — a covered-conductor station is covered at every exposed joint, including the switch and the arrester, not just at the clamps — but it cannot be used to order the covers. The cover family is on a separate sheet, and matching a cover to a GW9-10 or an RW3-10 is not something either page does.
Diagram 2 adds one more: an equipment protection joint cover on the cable termination into the protection switch box.
Five Parts Have No Catalogue Number At All
The drawing names the following by function only, with no model:
- the high-voltage terminal cover on the transformer bushings
- the equipment protection joint cover
- the public-transformer integrated box
- the protection switch box
- the earth conductor and its connections
Two of those are enclosures with a metering and protection function — the most expensive items on the pole after the transformer — and the sheet gives no size, no current rating and no IP class for either.
Quotation scope: this diagram tells you what hardware a station needs and in what order. It does not price the station, and it does not define the two boxes.
What Is Not On The Page
- No dimensions — no pole height, no crossarm spacing, no clearances, no creepage.
- No ratings for the station — the transformer size, the fuse rating and the arrester class are all unstated, so the diagram is scale-free.
- No earthing detail — the earth conductor is drawn as a single line to the base with no electrode, no resistance and no bonding of the arrester and the box.
- No conductor sizes for the drop, the loop or the cable in diagram 2.
The Two Diagrams

Diagram 1 — public-transformer layout. Three-phase throughout: three isolating switches, three dropout fuses, three arresters, and the transformer feeding an integrated box at the base. The strain clamp on the right takes the incoming run.

Diagram 2 — protected layout. One line drawn, with a protection switch box on the right fed by a cable from the NXL strain clamp. The switch, fuse and arrester stay on the pole.
Related Pages
The tap clamp at the top of the pole: JBLY parallel groove clamp. The strain clamp on the cable run: NXL wedge-type insulated strain clamp. Covers for the joints on this pole: PZ insulating cover and power transformer terminal safety cover. Earthing hardware: FDJ fully insulated grounding device. The dead-end assemblies that terminate these runs: 10 kV insulated line strain assemblies.
Note: Two single-line diagrams of a 10 kV pole station, differing in whether the transformer is fed through a protection switch box. Nine stages from the tap clamp to the LV box, of which only the JBLY clamp, the NXL clamp and the covers are catalogue parts. Seven kinds of cover are shown and every one is labelled by the part it covers rather than by a part number, so covers cannot be ordered from this drawing. Five items — including both enclosures — have no model at all. No dimensions, ratings or earthing detail printed.