NXL Wedge Insulated Strain Clamp

The NXL anchors overhead insulated aluminum conductor — or bare aluminum — on the angle and terminal poles of 10 kV and below distribution lines. It is the stripped pattern: the insulation comes off over a set length, the bare conductor goes into the wedge, and a matching insulation cover closes over the whole thing afterwards to restore the dielectric. Five bodies carry 35 to 400 mm², with rated failure loads from 7.5 kN to 61 kN.

Technical Parameters
| Universal Design Model | Applicable Conductor (Overhead Insulated Aluminum Conductor) (mm2) | Stripping Length (mm) | Grip Force (kN) | Nominal Failure Load (kN) | Matching Insulation Cover |
|---|---|---|---|---|---|
| NXL-1 | 35 | 245 | 3.4 | 7.5 | NXL-1 (25~50) |
| 50 | 4.6 | ||||
| NXL-2 | 70 | 245 | 6.7 | 14.5 | NXL-2 (70~95) |
| 95 | 8.9 | ||||
| NXL-3 | 120 | 255 | 11.3 | 22.0 | NXL-3 (120~150) |
| 150 | 13.7 | ||||
| NXL-4 | 185 | 300 | 17.3 | 36.4 | NXL-4 (185~240) |
| 240 | 22.5 | ||||
| NXL-5 | 300 | 320 | 28.2 | 61.0 | NXL-5 (300~400) |
| 400 | 39.8 |
Note: Cast in high-strength aluminum alloy with no magnetic hysteresis loss. The wedge structure keeps installation simple, and the large arc contact area spreads the grip so the conductor does not slip. Dimensions may vary slightly with manufacturing tolerance.
The Stripping Length Is the Installation
245, 245, 255, 300, 320 mm — that column is not a detail, it is the job. The insulation has to come back exactly that far, no more and no less: too short and the wedge cannot seat on bare metal, too long and you have exposed conductor that the cover will not close over.
The length grows with the body because the wedge does. NXL-1 and NXL-2 both strip 245 mm, NXL-3 needs 10 mm more, and by NXL-5 you are stripping 320 mm of a 400 mm² cable on a pole. Mark the length on the sheath with a wrap of tape before you cut — it is faster than measuring twice at height.
Where the cover covers more than the body. Read the last column carefully: the NXL-1 cover is listed as 25~50, but the body table lists only 35 and 50 mm². The cover is specced wider than the parameter table — 25 mm² fits the same clamp and the same cover, it is simply not carried as a catalogue row. Every other body matches its cover exactly (7095, 120150, 185240, 300400), so NXL-1 is the one place where the table understates what the clamp does.
If you have 25 mm² insulated cable, it is an NXL-1 with the NXL-1 cover; ask us and we will confirm the grip figure rather than leave you guessing at it.
Grip and Load, Body by Body
Grip strength runs 3.4, 4.6, 6.7, 8.9, 11.3, 13.7, 17.3, 22.5, 28.2 and 39.8 kN across the ten conductor sizes, but rated failure load steps once per body: 7.5, 14.5, 22.0, 36.4 and 61.0 kN. Each body covers two conductor sizes, and the bigger of the two sets the rating.
The jump from NXL-4 to NXL-5 is the one that matters in practice: 36.4 kN to 61.0 kN, a 67 % increase, and the body grows with it. If a line is designed around 40 kN, there is no NXL that sits between — you take NXL-5 and accept the larger clamp, or you go to a compression dead-end.
Stripped or Not
This page is the stripped version. If the crew would rather not cut insulation at height, the NXL-J wedge clamp does the same job on the same cable with no stripping at all — but note that its model numbers do not line up with these, and its range stops at 240 mm². For steel-cored JKLGYJ cable, the NXLJ wedge clamp is the one rated for the higher tensions that conductor carries.
Material and Finish
- Body: high-strength cast aluminum alloy, no magnetic hysteresis loss
- Wedge: aluminum alloy, large arc contact face
- Insulation cover: matched polymer cover, ordered by clamp model
- Hardware: hot-dip galvanized steel
- Galvanizing: ISO 1461 / ASTM A153 / IEC 61284, minimum coating 65 μm
- Inspection: dimensional check, coating thickness to ISO 2178, grip test on samples; mill test certificates on request