Suspension and Tension String Assembly

A line does not use fittings one at a time. They are assembled into a string — the chain that runs from the tower to the conductor — and the string is what the design is actually about. The four drawings on this page cover almost all of it, with the factory’s own part codes marked, so you can match what is on your drawing to what is on this site.
The Two Kinds of String
A suspension string hangs the conductor. It carries the vertical weight of the span and the transverse load from wind, and the clamp at its foot holds the conductor without gripping it — the conductor must be free to creep lengthwise, because that is how a suspension point survives differential ice.
A tension string, or dead-end, terminates the conductor. It carries the full tension of the span, and the clamp at its foot grips permanently. Every conductor section has two of them, one at each end; everything in between is a suspension point.
The count tells the story: on a typical line there are roughly eight suspension strings for every two tension strings. Suspension hardware is bought by the thousand and tension hardware by the dozen — but it is the dozen that decides whether the line stays up.
What the Numbers in the Codes Mean
The drawings are labelled with codes like U-7, XP-7, WS-7, and on the tension assembly U-16, QP-16, WS-16.
That trailing number is the rated mechanical class in tonnes. A −7 fitting is the 7 tonne class, roughly 70 kN; a −16 fitting is 16 tonnes, roughly 160 kN. So the drawings here show a 70 kN string and a 160 kN string, and you can tell them apart from the part codes alone.
This is worth knowing when you are checking someone else’s schedule: a string that mixes −7 and −16 codes has a weak link, and the failure will be at the joint rather than in the middle of a fitting.
1. The V String
The drawing at the top of this page. Two insulator legs meeting at a yoke below the cross-arm, with one clamp under the yoke carrying the conductor.
The V does two things a single string cannot. It shares the load between two legs, so each insulator carries about half — and at a line angle it resists the transverse pull that would otherwise swing a single string out of position. That is why V strings appear on angle towers, on exposed sections, and wherever the conductor has to be held against wind rather than allowed to swing.
Read it from the tower down: U-7 at the attachment, then the clevis group (PH-7, DB-7, Z-7, QP-7, XP-7), then the insulator FJ-660, then WS-7 and the yoke SZ-7, and finally the clamp QZ-2500 on the conductor.
That stack of five fittings between the tower and the insulator is not padding. Each one takes out a degree of freedom, so the string can align itself with the load instead of bending a single component until it cracks.
2. The V String With a Twin Clamp

The same two legs and the same clevis group, but a longer insulator (FJV-1300×1200) and a different foot: a yoke plate LB-1240, a U-bolt clevis UB-7-50, and two CS-51 clamps instead of one.
This is the twin-bundle version. Two clamps on a common yoke hold the pair at the spacing the plate sets, which is why the yoke plate part number matters — the bundle spacing is cast into a plate, and it does not appear anywhere else on the drawing.
If you are building this assembly, the clamp is our CS suspension clamp and the U-bolt clevis is the UB clevis. Note that the plate and the clevis are both −7 class and 70 kN: the string rating is set by its weakest element, and in this assembly that is the hardware, not the clamps.
3. The Single Suspension String

One leg, vertical. U-7 at the top, QP-7 below it, the insulator FJV-1060×660, then WS-7, the yoke arm LBD-0740, the U-bolt clevis UB-7-50 and a single CS-51 clamp.
This is the cheapest string there is and by far the most common: a straight run, no angle, conductor free to swing. The single clamp holds the conductor in a groove, and the whole assembly rotates about the tower pin, so the conductor hangs where its own weight puts it.
The trade is swing. A single string lets the conductor move laterally under wind, which is fine on a straight span and not fine where the clearance to the next phase is tight — that is when you go to the V.
4. The Tension String

Now the class changes. U-16, QP-16, XP-16, WS-16 — the whole clevis group is 16 tonne, and the insulator is FJ-760×660D with a longer shed profile.
At the foot there is no yoke and no groove. There is a compression strain clamp, NYH-1400, with its barrels running down to grip the conductor and the steel core.
Everything about the drawing is different because the duty is different:
- The clamp grips. No creep, no sliding. The conductor’s full tension passes through it.
- The insulators are stronger and there are more of them. A 160 kN string is normal on a real span; a 70 kN one would not survive the ice case.
- The hardware is heavier. U-16 instead of U-7 is not a small step — every pin, every plate and every cotter in the chain is sized for more than twice the load.
The strain clamp here is our NYH welded strain clamp. The same duty is covered by the NY hydraulic compression type and the JY range for other conductor constructions.
Reading a String Drawing
Three things to check first, in this order:
- The class. Are all the codes −7, or all −16? A mixed string has a weak link, and it will not be where you expect.
- The clamp. Is it a suspension clamp with a groove, or a strain clamp with a compression barrel? The two are not interchangeable, and a drawing does not always make the difference obvious.
- The yoke. On a twin bundle, the yoke plate sets the spacing and its part number is the only place that dimension appears. Get the plate wrong and the clamps are right and the bundle is wrong.