PF Power Fittings Technical Reference

NYH Welded Strain Clamp

Models: NYH-600K – NYH-1440/135N (10 sizes) · Conductor: LGKK, LGJQT, NRLH58GJ, NAHLGJQ · Grip: 96–232 kN · Weight: 7.0–12.0 kg

NYH welded strain clamp

NYH is the dead-end for the conductors that are too big or too hollow for a one-piece tube. Three of the ten models are for LGKK — hollow, expanded-diameter conductor, the kind used on 500 kV and 750 kV lines to keep the corona gradient down — and the rest are for large cored conductor up to 1440 mm².

The body is welded rather than cast in one piece, which is what lets it take a barrel that big, and the tail carries a welded flat pad for the jumper.

Seven models, one barrel die

The most useful number on this sheet is not the biggest one. Look down the d1 column: 76, 76, 76, 76, 76, 60, 70, 76, 80, 80.

Seven of the ten clamps have a 76 mm barrel. On a 500 kV string where the conductor steps from LGKK-600 to LGJQT-1400, the press and the die are the same for the whole run. Two models need an 80 mm die, and NYH-500/65N and NYH-630N are the only two that sit outside the pattern at 60 and 70 mm.

That is the opposite of the small NY family, where nearly every model has its own pair. It is a consequence of the conductors: LGKK and LGJQT are built to a fixed outside diameter band, so the clamp is too.

d2 is blank because there is no steel core

The second diameter, d2, is 22 to 34 mm on the seven cored models — and a dash on all three LGKK models. That dash is not a missing value. LGKK is a hollow expanded conductor: aluminium and steel strands laid over a core that is not a solid steel strand, so there is no steel core to anchor and no second crimp. One die, one crimp, barrel only.

That is also why the grip figures read the way they do:

Clamp Conductor d2 Grip Weight
NYH-600K LGKK-600 — 100 kN 7.4 kg
NYH-900K LGKK-900 — 136 kN 7.0 kg
NYH-1400K LGKK-1400 — 188 kN 7.3 kg
NYH-1400/120 LGJQT-1400/120 30 214 kN 10.2 kg

The hollow clamps hold 100 to 188 kN at around 7 kg each. Adding a steel core for the same conductor jumps the mass by 3 kg and the grip by 26 kN.

One row on that table does not sit right: NYH-900K at 7.0 kg is lighter than NYH-600K at 7.4 kg while being 25 mm longer and 4 mm bigger in d3. Every other dimension climbs with size. Treat it as a catalogue slip and weigh the first article.

NYH welded strain clamp outline drawing

Reading the drawing

  • L — overall length, 530 to 760 mm.
  • L1 — the crimp length at the tail, 70 to 100 mm. Short, because the tail is the pad end, not a second barrel.
  • d1 — barrel OD, 60 to 80 mm. This is the die, and seven of ten are 76 mm.
  • d2 — steel anchor OD, 22 to 34 mm; dash on the three hollow LGKK models.
  • d3 — bore at the conductor end, 20 to 26 mm.
  • R — body radius, 15 to 20 mm.
  • a × h — the welded flat pad at the tail, in millimetres. It is square on every row: 120 × 120, 125 × 125 or 150 × 150.

The pad is where the jumper terminal or the drainage clamp lands. The size steps with the string rather than the conductor: 120 mm square on the three LGKK models and the two LGJQT-1400 models, 125 mm on the 500/65N and 630N, and 150 mm on the three largest.

Technical parameters

ModelApplicable Conductor (mm2)Main Dimensions (mm)Grip Strength (kN)Reference Weight (kg)
d1d2d3LL1Rah
NYH-600KLGKK-60076-2053075151201201007.4
NYH-900KLGKK-90076-2455585151201201367.0
NYH-1400KLGKK-140076-2464070201501501887.3
NYH-1400/120LGJQT-1400/1207630246751002012012021410.2
NYH-1400/135LGJQT-1400/1357630246751002012012023210.2
NYH-500/65NNRLH58GJ-500/656022226607015125125969.5
NYH-630NNRLH58GJ-630/8070242671080171251251228.5
NYH-1000/125NNRLH58GJ-1000/1257632247601002015015018812.0
NYH-1440/120NNAHLGJQ-1440/1208034247601002015015021011.8
NYH-1440/135NNAHLGJQ-1440/1358034247601002015015022811.8

All dimensions in millimetres, weight per piece. The sheet’s own note: body and current-carrying parts in aluminium, everything else hot-dip galvanised steel.

Welded body, and what that means on site

  • Do not heat it. The body is welded; a torch on the weld or on the pad undoes the joint. If a pad has to be re-drilled, drill it cold.
  • Crimp from the pad end toward the mouth, two or three indents, so the strands are not pushed back out of the barrel.
  • The pad bolts, it does not crimp. Torque to the string schedule and re-check after the jumper is tensioned.
  • One die for most of the range — but confirm 76 mm against the actual model before the crew leaves, because the 500/65N and 630N are 60 and 70.

NYH or NZ

The NZ terminal clamp uses the same body dimensions for the six conductors the two sheets share, and weighs 0.8 to 3.4 kg less. The difference is the tail: NYH carries the welded pad, NZ does not. If the tower is a terminal and nothing taps off, NZ is the honest choice and the lighter one.

  • NY — the ACSR body, with a jumper tail, 50 to 800 mm².
  • NYH with drainage clamp — the same body with the tapping clamp specified in the model code.
  • NZ — terminal version, no pad.
  • NY-BG — aluminium-clad steel strand.

Note: Quote by conductor and state whether the tail carries a jumper. Where the drawing matters — 1400 mm² and above — send the string drawing; the pad size is not in the model code.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: