NY-HG Strain Clamp for Steel-Cored Aluminium Alloy Conductor
Models: NY-70/40HG – NY-300/70HG (5 sizes) · Conductor: LHBGJ 70–300 mm² · Grip: 63.4–168 kN · Weight: 3.0–6.7 kg

LHBGJ is a steel-cored aluminium alloy conductor: the outer strands are alloy rather than EC-grade aluminium, so the conductor runs hotter and holds more tension for the same sag. NY-HG is its hydraulic dead-end, and it is a short family — five sizes, 70 to 300 mm² — because LHBGJ itself is only made in a handful of constructions.
The clamp is the standard two-crimp body: aluminium barrel at D, steel anchor at D1, palm at the tail. Nothing unusual in the build. What is unusual is what the sheet teaches about sizing.
Grip follows the steel, not the aluminium
Read the five rows in order and the grip column does not climb:
| Model | Conductor | Aluminium | Steel | Grip |
|---|---|---|---|---|
| NY-70/40HG | LHBGJ-70/40 | 70 mm² | 40 mm² | 63.4 kN |
| NY-120/70HG | LHBGJ-120/70 | 120 mm² | 70 mm² | 108.8 kN |
| NY-240/30HG | LHBGJ-240/30 | 240 mm² | 30 mm² | 101.0 kN |
| NY-300/50HG | LHBGJ-300/50 | 300 mm² | 50 mm² | 136.4 kN |
| NY-300/70HG | LHBGJ-300/70 | 300 mm² | 70 mm² | 168.0 kN |
The 120 mm² clamp is rated higher than the 240 mm² clamp, because LHBGJ-120/70 has 70 mm² of steel in it and LHBGJ-240/30 has 30. A dead-end holds the conductor by its core, so the second number in the designation is the one that sets the rating. Twice the aluminium area buys nothing in tension.
This is the reason to quote by full designation and not by area. “240 mm² NY-HG” is ambiguous in a way that “NY-240/30HG” is not.
The two dies
- D — 36 to 52 mm, the aluminium barrel. Four distinct sizes across five models: 36, 45, 50 and 52.
- D1 — 18 to 24 mm, the steel anchor. Note it is not monotonic either: 18, 24, 18, 20, 24. The 120/70 anchor is bigger than the 240/30 anchor, same reason as the grip.
So five models need four barrel dies and three anchor dies. On a mixed order, that is eight dies on site — worth knowing before the crew arrives with one set.
Reading the dimensions
- L — 440 to 680 mm overall. L2, the palm, is 55 to 80 mm.
- D — barrel OD, 36 to 52 mm. Conductor die.
- D1 — anchor OD, 18 to 24 mm. Core die.
- D2 — neck behind the palm, 16 to 24 mm.
- R — eye radius, 11 to 14 mm.
The sheet gives no L1 or L3 column, so there is no jumper tail dimension on this drawing. If the string needs the jumper made off on the dead-end, take it up with the string drawing before ordering — the standard NY carries its jumper on an L3 tail, this one does not document one.
Technical parameters
| Model | Applicable Conductor (mm²) | Main Dimensions (mm) | Grip Strength (kN) | Reference Weight (kg) | |||||
|---|---|---|---|---|---|---|---|---|---|
| L | L2 | D | D1 | D2 | R | ||||
| NY-70/40HG | LHBGJ-70/40 | 440 | 55 | 36 | 18 | 16 | 11 | 63.4 | 3.0 |
| NY-120/70HG | LHBGJ-120/70 | 555 | 55 | 36 | 24 | 16 | 13 | 108.8 | 3.7 |
| NY-240/30HG | LHBGJ-240/30 | 590 | 65 | 45 | 18 | 20 | 12 | 101.0 | 5.0 |
| NY-300/50HG | LHBGJ-300/50 | 670 | 75 | 50 | 20 | 22 | 13 | 136.4 | 6.4 |
| NY-300/70HG | LHBGJ-300/70 | 680 | 80 | 52 | 24 | 24 | 14 | 168.0 | 6.7 |
All dimensions in millimetres, weight per piece. Five models, no optional variants.
Crimping
- Barrel first, then anchor, and mark the core length before you cut anything.
- Strip to the barrel length minus 1–2 mm. The sheet gives L, not L1, so measure the barrel on the fitting rather than working it out from the table.
- Two indents on the anchor, three on the barrel. At 300 mm² go to three and four.
- Do not mix dies between the two crimps. D and D1 are 18 to 28 mm apart; a swapped die will not close, and forcing it cracks the sleeve.
- Alloy conductor, alloy clamp. A standard NY on LHBGJ is dimensioned for EC-grade aluminium and the barrels do not match.
Related
- NY — the ACSR body, with a jumper tail.
- NY-N — heat-resistant alloy conductor, NRLH.
- NYH — welded body for hollow and very large conductors.
- NY-BG — aluminium-clad steel strand.
Note: Quote the full conductor designation, LHBGJ-240/30, not the area. The grip rating belongs to the conductor; this clamp is dimensioned around it.