PF Power Fittings Technical Reference

NYH Strain Clamp with Drainage Clamp

Models: NYH-600K/600K – NYH-1440/1440/135N (10 sizes) · Conductor: LGKK, LGJQT, NRLH58GJ, NAHLGJQ · Grip: 96–232 kN

NYH welded strain clamp with drainage clamp

This is the same welded body as the plain NYH, supplied with the jumper tapping clamp specified alongside it. The difference is in the model code, and the code is the reason this page exists.

Two designations in one code

Read NYH-1400/1400/120:

  • NYH-1400/1400/120 — body, for LGJQT-1400/120.
  • The second 1400 — the tapping clamp that comes with it, sized for the same conductor.

The sheet doubles the designation on every row: NYH-600K/600K, NYH-900K/900K, NYH-500/65N/500N, NYH-1440/1440/120N. Body on the left, tapping clamp on the right.

Why it matters: a plain NYH-600K and an NYH-600K/600K are not the same purchase order. One is a dead-end. The other is a dead-end plus a parallel-groove clamp for the jumper. If a customer sends the doubled code and we quote the single, the clamp is missing from the box and the string cannot be made off.

The sheet prints one code short — the last row appears as NYH-1440/1440135N, with the third slash dropped. It is NYH-1440/1440/135N, and that is how we quote it.

The tapping clamp is not in the weight

Every dimension and every weight on this sheet is identical to the plain NYH sheet:

NYH-600K NYH-600K/600K
L 530 mm 530 mm
L1 75 mm 75 mm
d1 76 mm 76 mm
Grip 100 kN 100 kN
Weight 7.4 kg 7.4 kg

L does not grow, because the tapping clamp bolts to the welded pad on the side of the body rather than extending it. And the weight does not grow either, which means the weight column is the body only. The tapping clamp is quoted as a separate line, and it has to be, because its size follows the jumper conductor, not the main one.

That is worth saying out loud on any quotation: the 7.4 kg figure is not the shipping weight of the assembly.

NYH with drainage clamp, outline drawing

Technical parameters

ModelApplicable Conductor ModelMain Dimensions (mm)Grip Strength (kN)Reference Weight (kg)
d1d2d3LL1R
NYH-600K/600KLGKK-60076-2053075151007.4
NYH-900K/900KLGKK-90076-2455585151367.0
NYH-1400K/1400KLGKK-140076-2464070201887.3
NYH-1400/1400/120LGJQT-1400/1207630246751002021410.2
NYH-1400/1400/135LGJQT-1400/1357630246751002023210.2
NYH-500/65N/500NNRLH58GJ-500/656022226607015969.5
NYH-630N/630NNRLH58GJ-630/8070242671080171228.5
NYH-1000/125N/1000NRLH58GJ-1000/1257632247601002018812.0
NYH-1440/1440/120NNAHLGJQ-1440/1208034247601002021011.8
NYH-1440/1440/135NNAHLGJQ-1440/1358034247601002022811.8

All dimensions in millimetres. Weight is the body, per piece, tapping clamp excluded. Body and current-carrying parts in aluminium; everything else hot-dip galvanised steel.

What the columns tell you

  • d1 — 60 to 80 mm. Seven of the ten are 76 mm, so one die covers most of a 500 kV string.
  • d2 — dash on the three LGKK rows. Hollow expanded conductor, no steel core, one crimp instead of two.
  • d3 — 20 to 26 mm, the bore at the conductor end.
  • L1 — 70 to 100 mm, the crimp length at the tail.
  • R — 15 to 20 mm.

There is no a/h column here, although the plain NYH sheet has one. The pad is still on the body — it is what the tapping clamp bolts to — but the sheet measures the tapping clamp instead of the pad.

Fitting it

  • Crimp the body as a plain NYH. Barrel at d1, core at d2 where there is one, two or three indents from the pad end.
  • Bolt the tapping clamp to the pad, not to the barrel. A clamp on the barrel crushes the crimp.
  • Two bolts on the tapping clamp, tightened after the jumper is run and re-checked at final tension, because the jumper moves the joint as it swings.
  • Do not substitute a generic parallel-groove clamp for the one in the code. The pad is drilled for that clamp’s bolt centres.
  • NYH — the plain body, same dimensions, no tapping clamp.
  • NZ — terminal version, no pad at all.
  • NY — ACSR body with an integral jumper tail, 50 to 800 mm².
  • JBL and CAPG — the parallel-groove clamps normally used for the tap.

Note: Quote the doubled code in full. If only the body is wanted, order the plain NYH. The weight on this sheet excludes the tapping clamp.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: