CAPG Copper-Aluminium Parallel Groove Clamp

One aluminium body, two grooves of different radius: one side seats an aluminium conductor, the other a copper one, and the two metals never touch. That is the whole product.
It exists because a bolted copper-to-aluminium joint is a galvanic cell. In wet air the aluminium side corrodes, the joint loosens, resistance climbs, and the connection cooks itself. A bimetal clamp puts a welded copper-aluminium barrier into the current path so the dissimilar metals are separated by a factory-made transition instead of by a joint made on a pole.
Typical jobs: an aluminium overhead line tapping into a copper jumper, an aluminium service conductor landing on copper equipment leads, a pole-top transition where the two sides are different metals.

For an aluminium-to-aluminium joint the APG clamp is the same body without the copper and costs less. Do not buy the bimetal clamp for a joint that does not need it.
All nine sizes
| Model | Conductor (mm²) Al / Cu | Dimensions (mm) | R (mm) Al / Cu | Bolt | Bolts | ||
|---|---|---|---|---|---|---|---|
| L | B | H | |||||
| CAPG-A1 | 16~70 / 6~50 | 25 | 42 | 45 | 5.5 / 4.5 | M8 | 1 |
| CAPG-A2 | 25~150 / 10~95 | 25 | 42 | 45 | 7.5 / 6 | M8 | 1 |
| CAPG-B1 | 16~70 / 6~50 | 40 | 42 | 45 | 5.5 / 4.5 | M8 | 2 |
| CAPG-B2 | 25~150 / 10~95 | 50 | 45 | 50 | 7.5 / 6 | M8 | 2 |
| CAPG-B3 | 35~200 / 25~185 | 64 | 65 | 60 | 9.5 / 9 | M10 | 2 |
| CAPG-C1 | 16~70 / 6~50 | 60 | 42 | 45 | 5.5 / 4.5 | M8 | 3 |
| CAPG-C2 | 25~150 / 10~95 | 75 | 45 | 50 | 7.5 / 6 | M8 | 3 |
| CAPG-C3 | 35~200 / 25~185 | 96 | 65 | 60 | 9.5 / 9 | M10 | 3 |
| CAPG-C4 | 35~300 / 35~240 | 104 | 65 | 70 | 11.5 / 10 | M10 | 3 |
The letter is the bolt count
Read the codes down and the system is not obvious until you line up the last column:
| Letter | Bolts | Models |
|---|---|---|
| A | 1 | A1, A2 |
| B | 2 | B1, B2, B3 |
| C | 3 | C1, C2, C3, C4 |
The digit after the letter is the conductor class, not a size in square millimetres:
| Digit | Aluminium / copper |
|---|---|
| 1 | 16 |
| 2 | 25 |
| 3 | 35 |
| 4 | 35 |
So CAPG-C3 is a three-bolt clamp for 35200 aluminium against 25185 copper. Class 4 exists only as C4 — there is no one-bolt or two-bolt clamp above 200 mm².
R carries two numbers, and both are checkable
5.5 / 4.5 means the aluminium groove radius is 5.5 mm and the copper groove radius 4.5 mm. Twice each radius is the outside diameter of the largest bare conductor that groove seats — and it lines up with the conductor range in the same row:
| Model | R Al / Cu | 2R in mm | Largest bare conductor | Its actual OD |
|---|---|---|---|---|
| A1, B1, C1 | 5.5 / 4.5 | 11 / 9 | LJ-70 / TJ-50 | 10.8 / 9.0 |
| A2, B2, C2 | 7.5 / 6 | 15 / 12 | LJ-150 / TJ-95 | 15.75 / 12.4 |
| B3, C3 | 9.5 / 9 | 19 / 18 | LJ-200 / TJ-185 | 18.5 / 17.5 |
| C4 | 11.5 / 10 | 23 / 20 | LJ-300 / TJ-240 | 22.7 / 20.0 |
Eight rows out of eight, within half a millimetre. So the R column is not decoration — it tells you the physical size of the hole, which is what matters when the copper side is a flexible cable rather than a solid conductor, or when your conductor is a non-standard diameter at the top of its range.
The aluminium radius is always the larger of the two on the same row, because aluminium needs about 1.6 times the area of copper to carry the same current.
Two bolts do not always mean the same size
The body only changes with the conductor class, not with the bolt count:
| Conductor class | A | B | C |
|---|---|---|---|
| 16 |
25 / 42 / 45 | 40 / 42 / 45 | 60 / 42 / 45 |
| 25 |
25 / 42 / 45 | 50 / 45 / 50 | 75 / 45 / 50 |
| 35 |
— | 64 / 65 / 60 | 96 / 65 / 60 |
Three things fall out of that:
- The 16~70 class has one body for all three bolt counts — 42 wide, 45 high — and only L grows: 25, 40, 60. A bolt costs 15 mm, then 20 mm.
- The 25~150 class keeps the A1 body for the single-bolt version (42 / 45) but goes up to 45 / 50 as soon as you want two or three bolts. So
CAPG-A2andCAPG-B2are not the same clamp with an extra bolt; the B2 is taller and wider. - The 35~200 class only exists from two bolts up, and there L grows by 32 mm for the third bolt.
If you are checking clearance and you have been quoted a two-bolt clamp on the strength of a one-bolt drawing, the width and height can be different. Check B and H, not just L.
Bolts and torque
M8 on conductor classes 1 and 2, M10 on classes 3 and 4. The break is at B3, not at the bolt count.
Torque to the figure marked on the clamp body. Where nothing is marked, ask us and we will give the figure for the bolt grade supplied — we do not publish a single number for the range here, because it depends on the grade and on whether the bolts are lubricated, and a wrong figure on a bimetal joint is how the contact resistance problem starts. Fit finger-tight and torque in stages, alternating between bolts, so the two halves close evenly.
Installation
- Clean both conductors to bright metal over the groove length.
- Paste the aluminium side. On aluminium this is not optional; the copper side is cleaned and may be left dry.
- Seat both conductors so the ends sit flush at both ends of the clamp — a conductor pushed too far on one side lifts the other.
- Torque in stages, alternating between bolts.
- Mark the bolts with torque paint and re-check after the first load cycle.
Standards
The general requirements for this class of fitting are set out in GB/T 2314 and the test methods in the GB/T 2317 series; IEC 61284 is the international equivalent. Whether a particular batch is tested to one of them is a contract matter, not a property of the catalogue page — if your specification calls up a standard, tell us and we will quote against it and supply the test report.
The number that decides acceptance is the resistance ratio: across the joint, DC resistance must stay at or below that of an equal length of conductor, cold and after thermal cycling. On a bimetal clamp there is a second failure mode — the copper-aluminium transition itself. A sound one has a continuous metallurgical bond; a poor one shows as a resistance step exactly at the interface, which is why the measurement is taken across the whole body rather than from bolt to bolt.
Where these joints fail
- A bolted copper-aluminium joint instead of a bimetal clamp. The failure this product exists to prevent. It corrodes from the interface outward and looks fine until it does not.
- Wrong groove pairing. Forcing an oversized conductor into the copper groove deforms the body and leaves the aluminium side under-clamped.
- Under-torque on the aluminium side. The copper side feels tight early, so crews stop there. The aluminium groove is the one that needs the full figure.
- Steel strand. Neither groove is sized for it — use the JBB steel strand clamp.
- A cable lug in the groove. Only if the barrel actually fits. For cable to busbar, the correct part is a DTL copper-aluminium transition terminal.
When it is the wrong part
For two aluminium conductors, buy the APG. For two copper conductors, the JBT is cheaper and just as good. For a copper-aluminium joint that has to be mechanically stronger than a bolted groove — a tension position, or a joint that will be cycled hard — the JBTL shaped bimetallic clamp or the JBTL flash-welded clamp is the right family, and this clamp is not.