APG Aluminum Parallel Groove Clamp(PG Clamp)

Models: APG-A1 – APG-C4 (10 sizes) · Conductor: 16–300 mm² · Bolt Qty: 1–3
The APG clamp joins two parallel conductors without cutting either of them. Both conductors sit in the two grooves of the same body, and a single set of bolts presses the two halves together — there is no separate keeper, wedge or compression tool involved. That is what makes it the usual choice for a branch tap, a jumper loop at a tension tower, or a temporary bridge over a damaged span: one spanner, five minutes, and the main line stays in service.
It is a connection fitting, not a tension fitting. The joint carries current and keeps the two conductors in contact; it is not designed to hold the full mechanical tension of the line. Where a conductor has to be terminated or dead-ended, use a strain clamp instead — see the strain assemblies in 10 kV overhead insulated line diagrams.
Choosing the model
Start from conductor size, then from how much load cycling the joint will see.
- APG-A1 / A2 (1 bolt, 16–150 mm²) — small distribution taps and service drops, where the joint is lightly loaded and the priority is fitting speed.
- APG-B1 to B4 (2 bolts, 16–240 mm²) — the general distribution case. Two bolts spread the clamping force along the groove, which matters as conductor size grows.
- APG-C1 to C4 (3 bolts, 16–300 mm²) — joints that will see repeated load cycles, or conductors at the top of the range. Three bolts keep the contact pressure more even when the aluminium expands and contracts.
The range in the table is groove capacity, not a guarantee that any two conductors inside it will fit together. When the two conductors differ in diameter — 50 mm² tapping 185 mm², for example — check that the smaller conductor still fills enough of the groove to be gripped along its length. A conductor touching the groove at one edge only will never develop the contact pressure the joint needs, however hard the bolts are tightened.
Reading the dimension table
Four of the columns decide whether the clamp fits your conductor; the other three are envelope dimensions.
- R — groove radius (mm). The largest conductor the groove can seat is roughly 2R in diameter. At R 11.5 (APG-C4) that is about 23 mm OD, which covers 300 mm² aluminium and the ACSR equivalents at that size. This is the column to check first against a conductor you have not used before.
- M — bolt thread. M8 for the A and B1/B2 sizes, M10 from APG-B3 upward. It tells you which torque value applies and which spanner the crew needs.
- L / B / H (mm) — overall length, width and height, for clearance checks against the insulator string or the tower hardware.
- Bolt quantity — one, two or three, as discussed above.
Standards and what is actually tested
The clamp is made to the Chinese general specification for overhead line fittings, and the joint performance is judged by the same tests used for splicing fittings generally:
- GB/T 2314 — general technical requirements for electric power fittings (materials, galvanising, tolerances).
- DL/T 758 — splicing fittings; the current edition is DL/T 758-2021, which replaced the 2009 edition. It is written around 110 kV and above, with lower voltages referring to it.
- GB/T 2317.1 / 2317.3 — mechanical test methods, and the thermal-cycle and resistance test.
- IEC 61284 — the international counterpart; a summary of what each test actually proves is in the IEC 61284 fittings testing guide.
The two numbers worth remembering when comparing quotations:
- Resistance ratio. The DC resistance across the joint, measured over the clamp length, must not exceed that of an equal length of the conductor itself — a ratio of 1.0 or less. A clamp that measures above 1.0 is a heater, not a joint.
- Resistance after thermal cycling. The same ratio has to hold after the joint has been current-cycled to operating temperature repeatedly. This is where a light body or a short groove shows up: it may pass a cold resistance test and still drift above 1.0 once the aluminium has expanded and settled a few hundred times.
Surface finish is hot-dip galvanised steel for the bolts and nuts to ISO 1461, with an aluminium alloy body; the two are electrically compatible with an aluminium conductor, which is why no bimetallic insert is needed on an all-aluminium joint.
Installation
- Clean both conductors back to bright metal over the length of the groove with a wire brush. Aluminium oxide is an insulator; the clamp cannot make contact through it.
- Apply contact paste to the cleaned conductor and the groove faces. On aluminium this is not optional — it excludes air and slows the re-oxidation that pushes resistance up over the first year.
- Seat both conductors fully in the grooves, flush at both ends, so the same length of each conductor is inside the clamp.
- Fit the bolts finger-tight first, then tighten in stages, alternating between bolts so the two body halves close evenly rather than tilting.
- Torque to the figure marked on the clamp or in the packing note. As a field reference for galvanised steel bolts, M8 is typically 20 N·m and M10 typically 40 N·m; if the marking and the reference disagree, the marking wins. Use a calibrated torque wrench — this is the only source of contact pressure in the whole joint.
- Inspect: no conductor strand splayed outside the groove, no gap between the body halves at either end, bolts marked with torque paint so the next patrol can see whether anything has moved.
Where these joints fail
- Under-torque. The single most common cause. The joint runs warm, the warm joint oxidises faster, resistance rises, and the process accelerates until the clamp burns off. Nothing about the clamp looks wrong from the ground until it does.
- Aluminium against copper without a bimetallic barrier. Copper and aluminium in contact with moisture present corrode galvanically; the aluminium side loses material and the joint loosens. Use the copper-aluminium version — CAPG parallel groove clamp — for that combination.
- Used as a tension joint. A PG clamp will hold a conductor under light pull, which is exactly why it gets used wrongly on a dead-end. Under full tension and wind vibration the conductor pulls through the groove.
- Re-using a deformed clamp. The body takes a permanent set when it is first torqued. Refitting it to a smaller conductor leaves a gap that no amount of torque will close; fit new bolts and a new body.
FAQ
Is a parallel groove clamp the same as a wedge clamp? No. A wedge clamp develops its pressure from a wedge driven in by an impact tool and holds it with spring action; a PG clamp develops pressure only from bolt torque. The wedge type tolerates vibration better and is faster to fit with the right tool; the PG type needs nothing but a spanner and can be re-opened for reconfiguration.
Can it join aluminium to copper? Not with an all-aluminium body. Use a bimetallic clamp rated for the transition, or a copper-aluminium parallel groove clamp.
Does it need contact paste? On aluminium, yes — cleaned metal and paste together. Skipping it does not fail immediately; it fails after a season.
Can it be removed and re-used? Yes, provided the body has not been deformed and the bolts are replaced if the threads or the galvanising are damaged. Re-torque to the same figure on refitting.
Which series do I need for ACSR? The aluminium-body series clamps ACSR as well as plain aluminium strand, since the outer layers are aluminium; size it on the overall conductor diameter (2R) rather than on the nominal mm². For steel-cored or all-steel strand, use the steel-strand version, JBB parallel groove clamp. For plain aluminium strand where a lighter body is enough, the JB series covers the same job.
Technical Parameters

| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | Bolt Qty | ||||
|---|---|---|---|---|---|---|---|
| L | B | H | R | M | |||
| APG-A1 | 16~70 | 25 | 42 | 45 | 5.5 | 8 | 1 |
| APG-A2 | 16~150 | 25 | 42 | 45 | 7.5 | 8 | 1 |
| APG-B1 | 16~35 | 40 | 42 | 45 | 5.5 | 8 | 2 |
| APG-B2 | 16~70 | 50 | 45 | 50 | 7.5 | 8 | 2 |
| APG-B3 | 16~150 | 64 | 65 | 60 | 9.5 | 10 | 2 |
| APG-B4 | 25~240 | 96 | 65 | 70 | 11.5 | 10 | 2 |
| APG-C1 | 16~70 | 60 | 42 | 45 | 5.5 | 8 | 3 |
| APG-C2 | 16~150 | 75 | 45 | 50 | 7.5 | 8 | 3 |
| APG-C3 | 25~240 | 96 | 65 | 60 | 9.5 | 10 | 3 |
| APG-C4 | 35~300 | 104 | 65 | 70 | 11.5 | 10 | 3 |
Note: Dimensions are nominal and subject to normal casting and machining tolerance. Check R against your actual conductor diameter and M against the torque value you intend to apply before ordering; both are given above.