C Type Copper Connection Clamp(CCT)

Models: CCT-10 – CCT-700 (17 sizes) · Conductor: 7.5–700 mm²
The CCT clamp is a C-shaped copper body that clamps two copper conductors together without cutting either of them. One bolt pulls the body closed around both conductors, so the joint is made with a single spanner in the time it takes to tighten one bolt — which is why it is the usual fitting for copper taps, earthing bonds and small conductor junctions where a compression joint would need a press and a die.
It is a copper fitting. On an aluminium conductor the copper body becomes the cathode of a galvanic cell and the aluminium corrodes; use a bimetal clamp for that combination instead.
The one thing to understand about the size column
The table’s conductor column is titled Applicable Copper Strand Cross-Section Sum, and that word sum is the whole selection rule: the model is chosen by the combined cross-section of the two conductors, not by the larger one.
So CCT-240 takes 120 + 120 mm², or 150 + 95 mm², or 185 + 55 mm² — any pair whose sections add up inside 191–240 mm². Teams that read the number as “the largest conductor” order a clamp two or three sizes too big, and an oversized C body does not close evenly on small conductors.
Once the sum is inside the right bracket, check the two conductors individually: the C is not symmetric, and a very uneven pair (a 185 mm² running into a 16 mm² earth tail, for example) may not seat properly even though the sum is right. If the pair is badly uneven, a two-groove clamp is the better part.
Choosing the model
- CCT-10 to CCT-44 (7.5–44 mm² total) — control wiring, small earth bonds, instrument and panel work.
- CCT-60 to CCT-122 (45–122 mm² total) — distribution taps and earthing on LV installations.
- CCT-154 to CCT-365 (123–365 mm² total) — substation earthing and main copper taps.
- CCT-450 to CCT-700 (366–700 mm² total) — heavy busbar and earthing connections, where the body is bolted down rather than hand-held.
Reading the dimension table
- B / A / H (mm) — overall width, depth and height of the C body; check them against the lug or busbar space you are working in.
- L (mm) — length along the conductor.
- C (mm) — the jaw opening, the figure that tells you whether the pair physically fits. A high sum with a low C means two fat conductors that will not close.
- T (mm) — body wall thickness. It is what carries the clamp force; a thin body deforms permanently under torque and never grips again.
Standards
Made to GB/T 2314 for materials and finish, with the joint judged by the tests in DL/T 758 (splicing fittings) and IEC 61284: DC resistance, temperature rise, thermal cycling and mechanical load. For a copper joint the resistance requirement is the same as any other connection fitting — across the clamp, no more than the resistance of an equal length of the conductor, and the same again after cycling.
The body is copper, with tin plating optional. On indoor panel work bare copper is normal; for outdoor, coastal or galvanised-steel-adjacent installations the tinned version is worth the difference in price, because it is the surface that decides how the joint ages, not the bulk metal.
Installation
- Clean both conductors to bright metal. Copper oxide is a poor conductor and it re-forms within hours in damp air, so paste the joint if it will be exposed.
- Seat both conductors fully in the C, one in each jaw, with the required length of each inside the body.
- Tighten the bolt to the figure marked on the clamp, with a torque wrench rather than by feel — the C body gives very little feedback before it starts to deform.
- Re-check after the first load cycle if the joint is on a feeder; copper settles under clamping pressure.
- Wrap or tape the joint if it is exposed, and mark the bolt with torque paint for the next inspection.
Where these joints fail
- Sizing by the largest conductor instead of the sum. The most common ordering error, and it produces a joint that never closes properly.
- A copper clamp on an aluminium conductor. Corrosion of the aluminium, from the contact face outward.
- Over-torque on a thin body. The C takes a permanent set, the jaw opening grows, and the joint cannot be tightened again — the clamp has to be replaced, not re-tightened.
- Re-using a clamp that has been deformed. The same problem as above; a distorted C never regains its grip.
- Bare copper in a coastal or chemical atmosphere. Nothing wrong with the clamp; the surface was the wrong choice.
FAQ
What does the number mean — the total of both conductors? Yes. The column is the sum of the two conductor cross-sections. CCT-190 covers pairs adding up to 155–190 mm².
Can CCT be used on aluminium conductors? No. Use a bimetal (copper-aluminium) clamp. For parallel aluminium conductors, an APG clamp is the equivalent part.
Why would I choose tinned copper? For outdoor, coastal or humid locations, and wherever the joint sits against galvanised steel. Tin slows the surface oxidation that raises contact resistance over years.
Is it suitable for earthing and bonding? Yes — that is a large part of its use, particularly in substations, where the C body can be bolted to a steel structure as well as clamped to a conductor.
Can it be re-used? Only if the body has not been deformed and the bolt and nut are sound. Replace the bolt if the threads or plating are damaged.
Technical Parameters

| Model | Applicable Copper Strand Cross-Section Sum (mm2) | Main Dimensions (mm) | |||||
|---|---|---|---|---|---|---|---|
| B | A | H | L | C | T | ||
| CCT-10 | 7.5~14 | 9.5 | 6.3 | 6.2 | 12 | 4.0 | 1.6 |
| CCT-16 | 14.5~16 | 11.8 | 7.8 | 7.8 | 13 | 5.0 | 2.0 |
| CCT-20 | 16.5~20 | 12.8 | 8.6 | 9.7 | 13 | 5.4 | 2.9 |
| CCT-26 | 21~26 | 14.7 | 10.2 | 10.0 | 16 | 6.5 | 3.2 |
| CCT-44 | 27~44 | 19.0 | 13.4 | 14.4 | 20 | 8.5 | 4.0 |
| CCT-60 | 45~60 | 21.0 | 15.4 | 15.4 | 22 | 9.7 | 4.0 |
| CCT-76 | 61~76 | 24.4 | 17.3 | 17.6 | 22 | 10.8 | 5.0 |
| CCT-98 | 77~98 | 27.8 | 20.8 | 18.8 | 25 | 12.8 | 5.0 |
| CCT-122 | 99~122 | 29.8 | 22.1 | 21.2 | 26 | 13.5 | 5.5 |
| CCT-154 | 123~154 | 34.0 | 25.7 | 24.4 | 28 | 17.0 | 6.0 |
| CCT-190 | 155~190 | 37.0 | 28.5 | 25.4 | 35 | 17.4 | 6.0 |
| CCT-240 | 191~240 | 40.0 | 30.2 | 28.5 | 40 | 19.0 | 7.0 |
| CCT-288 | 241~288 | 44.5 | 34.7 | 34.1 | 45 | 22.3 | 7.0 |
| CCT-365 | 289~365 | 47.5 | 37.7 | 34.0 | 50 | 24.8 | 7.0 |
| CCT-450 | 366~450 | 57.0 | 42.5 | 41.0 | 60 | 28.0 | 10.0 |
| CCT-560 | 451~560 | 62.0 | 46.0 | 44.0 | 65 | 31.0 | 11.0 |
| CCT-700 | 561~700 | 73.0 | 58.0 | 48.5 | 70 | 44.0 | 12.0 |
Note: Body and palms are copper; tin plating is available on request — specify it for outdoor, coastal or humid locations, where the surface decides how the joint ages.