PF Power Fittings Technical Reference

JB Parallel Groove Clamp, Aluminium Strand and ACSR

Conductor: 16 to 630 mm² · Sizes: JB-0 to JB-6 · Bolts: 2, 3 or 4

JB parallel groove clamp for aluminium strand and ACSR JB parallel groove clamp, drawing

JB is the mainstay parallel groove clamp for aluminium strand and ACSR — the one used to tap a service or to join two conductors where there is no press and no room for one. Two grooves in a body, a cover plate, two to four bolts.

Seven sizes cover 16 mm² to 630 mm², which is the full range from a small service tap to a 630 mm² sub-transmission conductor.

Materials

The factory note: “the clamp body and cover plate are aluminium alloy, other parts are hot-dip galvanised steel.”

The two parts that grip the conductor are aluminium alloy; the bolts and washers are galvanised steel. So on a coastal or industrial site the bolts are what you will be replacing first, and the aluminium body is the conductive path — the steel only provides clamping force.

Technical parameters

ModelApplicable conductor (mm²)Main dimensions (mm)Bolts
LBHRM
JB-016~257037403.5102
JB-135~507844455.0122
JB-270~9511252557.0123
JB-3120~15013862608.5163
JB-4185~240142716511.0163
JB-5300~4002151008015.5204
JB-6500~6302301109018.5204

All dimensions in millimetres. No weight is published for JB — do not quote freight off this table.

R is a radius, so double it to get the conductor

The section ranges only tell you which conductor the clamp is sold for. R tells you what will physically fit, because R is the radius of the conductor groove — not a diameter, not a bolt size.

Double R and you have the outside diameter of the largest conductor the clamp takes:

Model R (mm) 2R, the conductor diameter it will take
JB-0 3.5 7.0 mm
JB-1 5.0 10.0 mm
JB-2 7.0 14.0 mm
JB-3 8.5 17.0 mm
JB-4 11.0 22.0 mm
JB-5 15.5 31.0 mm
JB-6 18.5 37.0 mm

That matters because the catalogue sells JB by section area and the clamp fits by diameter. A 185 mm² conductor is 18.9 mm as ACSR but a different figure in another stranding, and the section range 185–240 does not tell you whether it will sit in R = 11.

The clamps where the sheet does work in diameter confirm the rule: the two General Design rows below are specified as 10.8–14.0 mm and 14.5–17.5 mm against R values of 7.0 and 8.5, which is exactly 2R.

JB-2 and JB-3 exist in two designs

The second table on the factory sheet is a General Design variant of the same two codes, and it is not the same drawing:

General design modelApplicable conductor diameter (mm)Main dimensions (mm)Bolts
LBRM
JB-210.8~14.0114507.0123
JB-314.5~17.5140628.5163

Compare with the main table and both differ:

Model Main design L / B General design L / B
JB-2 112 / 52 114 / 50
JB-3 138 / 62 140 / 62

So the general design is 2 mm longer on both, and 2 mm narrower on JB-2. R and M are unchanged. That is small enough to be missed on a drawing check and large enough to matter on a bolt length or a cover plate that has to land squarely.

When you quote a JB-2 or JB-3, say which design. The factory lists both under the same code.

Bolts step up with size

The count and the thread both climb, and they do not climb together:

  • Two bolts on JB-0 and JB-1.
  • Three bolts on JB-2, JB-3 and JB-4 — the middle of the range gets length without width.
  • Four bolts on JB-5 and JB-6.

Threads go M10, M12, M12, M16, M16, M20, M20. So JB-1 and JB-2 share a thread and differ in bolt count; JB-3 and JB-4 share M16.

Fitting it

  • R has to match the conductor you actually have, not the section on the schedule. Check 2R against a real conductor diameter.
  • Clean and grease both conductors before closing. Aluminium oxide is the contact resistance.
  • Pull the bolts down evenly. A cover plate tightened from one end traps the conductor on that side and leaves the other groove open — on a three- and four-bolt clamp this is the usual cause of a hot joint.
  • Re-torque after the first load cycle. A bolted aluminium joint relaxes as it warms.
  • Current, not tension. JB crosses a joint; it does not hold a span.

The rest of the family

  • JBG — the smaller bolted clamp, 4.5 to 22 mm.
  • JBB — the steel strand version, GJ-25 to GJ-240.
  • JB-N — the two large sizes for heat-resistant conductor.
  • JBTL — the shaped-body version, up to 400 mm².

Note: Quote the model, the conductor, and which design — JB-3, general design, LGJ-150. The two JB-3 drawings are not interchangeable.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: