JBTL Shaped Bimetallic Parallel Groove Clamp

An aluminium clamp body with copper laid into the grooves, so that a copper conductor sits on copper and an aluminium conductor sits on aluminium in the same fitting. That is what TL means — copper, aluminium — and it is the only reason to buy this instead of the plain aluminium JBLY.
The photograph shows the arrangement plainly: silver aluminium casting, two bolts, and an orange-copper lining visible in both grooves and along the end face.
The body is the same shaped casting as JBLY: divided along its length into two or three sections, each with its own bolt.

Three ways to put copper on aluminium
The copper is not the same on every clamp. The factory makes this body three ways:
| Method | What it is | Sizes |
|---|---|---|
| Explosion bonded | copper plate explosively welded to the aluminium, then machined | 9 |
| Friction welded | copper plate friction welded to the aluminium | 9 |
| Copper insert | a copper piece set into the casting | 4 |
Explosion bonded and friction welded measure identically. All nine rows match to the millimetre — same L, same B, same H, same R, same M, same bolt count. The two methods exist because different factories in the group have different presses, not because the clamp differs. If a tender names one method and your project can accept the other, they are dimensionally interchangeable.
The copper insert is a different clamp, and it is dealt with separately below.
1. Explosion bonded
| Model | Conductor (mm2) | Main dimensions (mm) | Bolts | ||||
|---|---|---|---|---|---|---|---|
| L | B | H | R | M | |||
| JBTL-10~70-2 | 10~70 | 40 | 36 | 40 | 5 | 8 | 2 |
| JBTL-10~70-3 | 10~70 | 60 | 36 | 40 | 5 | 8 | 3 |
| JBTL-35~120-2 | 35~120 | 45 | 48 | 55 | 7 | 10 | 2 |
| JBTL-35~120-2-Extended | 35~120 | 70 | 48 | 55 | 7 | 10 | 2 |
| JBTL-35~120-3 | 35~120 | 70 | 48 | 55 | 7 | 10 | 3 |
| JBTL-50~240-2 | 50~240 | 45 | 60 | 70 | 10 | 10 | 2 |
| JBTL-50~240-2-Extended | 50~240 | 70 | 60 | 70 | 10 | 10 | 2 |
| JBTL-50~240-3 | 50~240 | 70 | 60 | 70 | 10 | 10 | 3 |
| JBTL-185~400 | 185~400 | 90 | 75 | 75 | 13.5 | 12 | 3 |
2. Friction welded
| Model | Conductor (mm2) | Main dimensions (mm) | Bolts | ||||
|---|---|---|---|---|---|---|---|
| L | B | H | R | M | |||
| JBTL-10~70-2 | 10~70 | 40 | 36 | 40 | 5 | 8 | 2 |
| JBTL-10~70-3 | 10~70 | 60 | 36 | 40 | 5 | 8 | 3 |
| JBTL-35~120-2 | 35~120 | 45 | 48 | 55 | 7 | 10 | 2 |
| JBTL-35~120-2-Extended | 35~120 | 70 | 48 | 55 | 7 | 10 | 2 |
| JBTL-35~120-3 | 35~120 | 70 | 48 | 55 | 7 | 10 | 3 |
| JBTL-50~240-2 | 50~240 | 45 | 60 | 70 | 10 | 10 | 2 |
| JBTL-50~240-2-Extended | 50~240 | 70 | 60 | 70 | 10 | 10 | 2 |
| JBTL-50~240-3 | 50~240 | 70 | 60 | 70 | 10 | 10 | 3 |
| JBTL-185~400 | 185~400 | 90 | 75 | 75 | 13.5 | 12 | 3 |
The table is printed in full rather than cross-referenced, because a schedule that says “friction welded” needs to see the numbers in front of it. Check any row against the table above and it is the same.
A third section costs 20 mm on JBTL-10~70 (40 to 60) and 25 mm on the two larger sizes (45 to 70). The extended two-bolt version is the same length as the three-bolt version, so extending buys contact length without adding a bolt — the same rule as the aluminium JBLY.
3. Copper insert
| Model | Conductor (mm2) | Main dimensions (mm) | Bolts | ||||
|---|---|---|---|---|---|---|---|
| L | B | H | R | M | |||
| JBTL-35~120-2 | 35~120 | 45 | 44 | 55 | 7 | 10 | 2 |
| JBTL-35~120-3 | 35~120 | 70 | 44 | 55 | 7 | 10 | 3 |
| JBTL-50~240-2 | 50~240 | 45 | 56 | 65 | 10 | 10 | 2 |
| JBTL-50~240-3 | 50~240 | 70 | 56 | 65 | 10 | 10 | 3 |
Four rows only. No 1070, and nothing above 240 mm² — the 185400 size exists only in the welded versions.
The insert body is narrower on every row:
| Model | Explosion / friction B | Copper insert B | H welded | H insert |
|---|---|---|---|---|
| 35~120, 2-section | 48 | 44 | 55 | 55 |
| 35~120, 3-section | 48 | 44 | 55 | 55 |
| 50~240, 2-section | 60 | 56 | 70 | 65 |
| 50~240, 3-section | 60 | 56 | 70 | 65 |
4 mm off the width everywhere, and 5 mm off the height on the 50~240. So the insert version is not a drop-in substitute — it is a smaller body with the same groove, and it will fit in places the welded version will not. That is usually why people ask for it.
Which one to quote
- Copper conductor to aluminium conductor, dry overhead — any of the three. Quote explosion bonded unless the tender says otherwise; it is the widest used.
- Tight structure, thin clearance — the copper insert, 4 mm narrower.
- Above 240 mm² — welded only, up to 400 mm².
- 10 mm² conductor — welded only.
State the method on the enquiry. “JBTL-35~120” alone does not tell us which of the two bodies you want.
This page and the twelve-row JBTL
There is another clamp sold under the JBTL code: a twelve-row range that matches the all-copper JBT size for size and uses flash welding. That one is the JBTL flash-welded clamp.
The difference in one line: the twelve-row clamp is the plain two-groove body with a welded copper plate; this page is the shaped two- or three-section body. Same letters, different casting, different sizes, no interchange.
One naming warning
The 2020 sample book calls the nine welded rows JBTLY, not JBTL, and prints them as a separate product from the twelve-row JBTL. The exporter’s English catalogue calls the same nine rows JBTL. So the same nine sizes travel under two names depending on which book your buyer is holding.
If an enquiry says JBTLY, it means the nine rows on this page. If it says JBTL and gives nine sizes, it also means this page. If it says JBTL and gives twelve, it is the other clamp.