PF Power Fittings Technical Reference

JFG Copper Aluminum Transition Branch Clamp

Models: JFG-25 – JFG-240 (9 sizes) · Main wire: 50–240 mm² · Branch wire: 25–240 mm²

JFG Copper Aluminum Transition Branch Clamp

The Table Is The One On The JFL Sheet

Nine rows, four columns, and every number the same as the all-aluminium JFL clamp: main wire 50~240 mm² on all nine rows, branch 25, 35, 50, 70, 95, 120, 150, 185, 240.

Nothing in the data distinguishes the two products. The only thing that makes this clamp a transition clamp is the JFG prefix and the word in the name column. So the choice between JFL and JFG cannot be made from the table — it is made from what is connected to it.

What A Transition Clamp Has To Do

Copper and aluminium in contact, with moisture present, form a galvanic couple. Aluminium sits far down the table, so it becomes the anode and is consumed at the joint; the contact resistance rises and the joint runs hot. The standard answers are a bimetallic interface — a copper or copper-alloy element joined to the aluminium by friction welding, explosion welding or a brazed liner — or a plated barrier that keeps the two metals apart.

A transition clamp therefore has a defined orientation: the copper side goes to the copper, the aluminium side to the aluminium.

This sheet does not print which side is which. The two wire columns are identical in range, the model number does not encode it, and no material column exists. Reversed on site, the clamp is a copper-aluminium joint with the wrong metal on each side — which is exactly the failure the part was bought to prevent.

Ask us to confirm the orientation before the clamps go to site, and mark the outgoing side on the packing. It is a two-minute question and it is not answerable from this page.

Nine Sizes, Still One Body

As on the aluminium sheet, the main range never changes — 50~240 mm² on all nine rows — so this is a bolted main plate rather than a fixed groove, with nine branch grooves.

That matters for a transition joint in one specific way: the bolted plate carries the whole current through its contact faces, and those faces are where the two metals meet. The sheet prints no plate thickness, no bolt size and no torque. For a bimetallic joint that is the wrong three things to leave out, because the interface is the part that ages.

What The Page Does Not Say

  • No copper alloy — pure copper, bronze and copper-clad aluminium behave very differently, and all three are used in this product class.
  • No plating — tin or silver on the copper side changes the joint resistance and the service life.
  • No dimensions, no weight — the nine sizes cannot be compared on metal or freighted against a budget.
  • No rated current and no pull-out force — the two numbers a branch clamp is bought for.
  • No temperature rise or short-circuit rating — normally required for a bimetallic joint in a substation.

If the joint is going into a design submission, all five have to come from us in writing.

Where It Is Used

The usual cases are a copper transformer terminal feeding an aluminium overhead line, and a copper busbar tapping an aluminium conductor. Both are places where the alternative — an aluminium clamp with a copper conductor in it — fails slowly and out of sight.

For the transformer-terminal case where the stud thread matters more than the conductor, the SBG bimetallic clamp prints the thread on every row. Where both sides are copper, SBT is the all-copper family.

Technical Parameters

NameModelMain Wire (mm2)Branch Wire (mm2)
Copper-Aluminum Branch ClampJFG-2550~24025
Copper-Aluminum Branch ClampJFG-3550~24035
Copper-Aluminum Branch ClampJFG-5050~24050
Copper-Aluminum Branch ClampJFG-7050~24070
Copper-Aluminum Branch ClampJFG-9550~24095
Copper-Aluminum Branch ClampJFG-12050~240120
Copper-Aluminum Branch ClampJFG-15050~240150
Copper-Aluminum Branch ClampJFG-18550~240185
Copper-Aluminum Branch ClampJFG-24050~240240

The all-aluminium version of the same nine sizes: JFL aluminum branch clamp. Bimetallic terminal clamps with the stud thread printed: SBG. All-copper terminal clamps: SBT.

Note: Nine bimetallic branch clamps whose table is numerically identical to the aluminium JFL sheet — same 50~240 mm2 main on every row, same nine branch sizes — so the prefix is the only thing distinguishing the two products. A transition clamp has a copper side and an aluminium side; this sheet does not say which is which, and reversing it produces the galvanic joint the part exists to prevent. No copper alloy, no plating, no dimensions, no weight, no rated current and no pull-out force are printed. The main side is a bolted plate because the 50–240 mm2 range cannot be a fixed groove, and the plate’s torque is not given either.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: