PF Power Fittings Technical Reference

JBL Parallel Groove Clamp for Railway

JBL aluminium parallel groove clamp, three-bolt version

An aluminium parallel groove clamp for electrified railway work — traction feeder, return conductor, and the bonding runs around a substation. Same shape as the overhead-line parallel groove clamps, different duty: railway installations specify this body because it takes a heavier bolt and a deeper groove than the distribution equivalent at the same conductor size.

The photograph is the three-bolt version in a two-groove body. The grooves are on both sides of the casting, so the same clamp takes one conductor each side.

JBL clamp drawing with B, L, H, R and M marked

Dimensions

ModelConductor (mm²)Main dimensions (mm)Bolts
LBHRM
JBL-6~7016~704435455.082
JBL-10~9510~954440506.582
JBL-25~12025~1205545507.082
JBL-25~12025~1208545507.083
JBL-25~15025~1505550558.582
JBL-25~15025~1508550558.583
JBL-50~30050~30055627011.0102
JBL-50~30050~30085627011.0103

Eight rows, five clamps

Read the model column and you will see three codes twice:

Model Bolt variants L
JBL-6~70 2 only 44
JBL-10~95 2 only 44
JBL-25~120 2 and 3 55 or 85
JBL-25~150 2 and 3 55 or 85
JBL-50~300 2 and 3 55 or 85

JBL-25~120 on its own does not identify a part. B, H, R and M are identical across the two rows; the only differences are L and the bolt count. Say how many bolts you want — the two are separate catalogue items and we will not guess which one your schedule means.

The bolt rule is simple: three bolts are 30 mm longer than two, and nothing else changes. 55 to 85 on all three codes. That is what a third bolt costs you in length, and it is the number you need when you are checking whether the clamp still clears the structure.

What each letter is

The drawing on this page letters all five, which the other parallel groove pages do not:

  • L — length along the bolts. This is the dimension the bolt count changes.
  • B — width across the body, perpendicular to the conductors.
  • H — depth of the body, from the bolt head down to the far face.
  • R — groove radius. Twice R is the conductor outside diameter, so R 5.0 takes a 10 mm conductor and R 11.0 takes a 22 mm one.
  • M — bolt thread. M8 on the four smaller clamps, M10 only on JBL-50~300.

R runs 5.0, 6.5, 7.0, 8.5, 11.0 straight up the table as the conductor size rises, so it is the column to check when you are matching the clamp to a conductor the catalogue does not list.

The first model is misnamed

JBL-6~70 is listed against 16~70 mm², not 6~70. The code carries a 6 that the conductor range does not. That is how the factory prints it and how it appears on their drawing, so this page keeps the code as it is — but if your schedule says “JBL for 6 mm²”, the smallest clamp here starts at 16 mm² and there is no 6 mm² option in the JBL range.

JBL-10~95 is the only one that goes down to 10 mm².

Where it sits in the range

Aluminium, two grooves, bolts — that is the same description as the JB distribution clamp and the JBLY shaped clamp. The differences that matter:

  • JBL is the railway body: M8 bolts where JB uses smaller hardware, and a deeper H for the same conductor.
  • JBL reaches 300 mm², where JB stops at 240.
  • JBL uses the plain two-groove casting, while JBLY is the shaped body with the two- and three-section variants.

If the conductor is steel strand rather than aluminium, the right clamp is the JBB steel strand clamp — aluminium grooves will not grip galvanised steel reliably over the life of a railway installation.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: