JBC Insulation Piercing Clamp

A bolted clamp that makes a branch or a jumper joint on insulated overhead line without stripping the insulation. The bolt drives a set of teeth through the insulation and into the conductor; a sealing body closes around the entry so water cannot follow the puncture in.
That is the whole point of the product: on a live 10 kV line you cannot strip a conductor, and on any line stripping is the slow part of the job. This clamp removes that step.

The 10 kV version, above — a taller body than the 1 kV unit in the first picture, which is what the extra insulation and creepage cost you in size.
The two drawings


The face section is the useful one. H is the overall height and B the overall width across the two conductor grooves, read straight off those views. Look closely at the grooves: one channel has a row of teeth drawn at its base, the other does not. The teeth are the piercing contact — that is where the conductor gets punctured, and the bolt above it is what drives them in.
L is the third dimension in the table. The two drawings here only letter the cross-section, so if L is critical to your clearance check, ask us for the outline that dimensions it. We would rather send you the right drawing than have you read a number off a page and guess which way it runs.
All 24 sizes
| Applicable Voltage | Model | Main Wire (mm2) | Branch Wire (mm2) | Main Dimensions (mm) | Bolt Qty | Current Carrying Capacity (A) | ||
|---|---|---|---|---|---|---|---|---|
| L | B | H | ||||||
| 1kV | JBC-1.5~35/1.5~10 | 1.5~35 | 1.5~10 | 25 | 35 | 53 | 1 | 75 |
| 1kV | JBC-10~50/1.5~10 | 10~50 | 1.5~10 | 30 | 32 | 49 | 1 | 75 |
| 1kV | JBC-25~95/1.5~10 | 25~95 | 1.5~10 | 33 | 39 | 58 | 1 | 75 |
| 1kV | JBC-16~95/4~50 | 16~95 | 4~50 | 45 | 43 | 74 | 1 | 200 |
| 1kV | JBC-35~150/6~50 | 35~150 | 6~50 | 45 | 50 | 74 | 1 | 200 |
| 1kV | JBC-16~70/16~70 | 16~70 | 16~70 | 53 | 52 | 84 | 1 | 250 |
| 1kV | JBC-16~120/16~120 | 16~120 | 16~120 | 53 | 52 | 84 | 1 | 300 |
| 1kV | JBC-35~150/35~150 | 35~150 | 35~150 | 52 | 56 | 84 | 1 | 350 |
| 1kV | JBC-70~185/16~95 | 70~185 | 16~95 | 68 | 73 | 103 | 2 | 330 |
| 1kV | JBC-150~240/16~50 | 150~240 | 16~50 | 83 | 76 | 103 | 2 | 200 |
| 1kV | JBC-120~240/25~120 | 120~240 | 25~120 | 79 | 60 | 94 | 2 | 400 |
| 1kV | JBC-95~240/50~150 | 95~240 | 50~150 | 76 | 78 | 103 | 2 | 450 |
| 1kV | JBC-95~240/95~240 | 95~240 | 95~240 | 79 | 64 | 94 | 2 | 550 |
| 10kV | JBC10-25~95/16~70 | 25~95 | 16~70 | 83 | 68 | 98 | 2 | 270 |
| 10kV | JBC10-25~50/25~50 | 25~50 | 25~50 | 94 | 72 | 115 | 2 | 200 |
| 10kV | JBC10-70~120/25~50 | 70~120 | 25~50 | 94 | 77 | 115 | 2 | 200 |
| 10kV | JBC10-70~120/70~120 | 70~120 | 70~120 | 95 | 79 | 115 | 2 | 400 |
| 10kV | JBC10-150~240/70~120 | 150~240 | 70~120 | 95 | 86 | 115 | 2 | 400 |
| 10kV | JBC10-95~240/95~240 | 95~240 | 95~240 | 95 | 90 | 115 | 2 | 550 |
| 10kV | JBC10-150~240/25~50 | 150~240 | 25~50 | 95 | 86 | 115 | 2 | 200 |
| 10kV | JBC10-95~240/16~50 | 95~240 | 16~50 | 83 | 76 | 113 | 2 | 200 |
| 10kV | JBC10-95~240/50~150 | 95~240 | 50~150 | 83 | 86 | 113 | 2 | 450 |
| 10kV | JBC10-150~300/35~150 | 150~300 | 35~150 | 83 | 92 | 118 | 2 | 450 |
| 10kV | JBC10-150~300/150~300 | 150~300 | 150~300 | 85 | 100 | 136 | 2 | 600 |
The rating follows the thinner conductor, not the body
This is the one thing to understand before you pick from that table.
Look at these three:
| Model | Main | Branch | Bolts | Rating |
|---|---|---|---|---|
| JBC-16 |
16~95 | 4~50 | 1 | 200 A |
| JBC-35 |
35~150 | 6~50 | 1 | 200 A |
| JBC-150 |
150~240 | 16~50 | 2 | 200 A |
The main conductor goes from 95 mm² to 240 mm² and the bolt count doubles, and the rating does not move: 200 A all three times, because the branch range is the same. The branch is the bottleneck — heat is made where the current crosses the puncture, and that crossing is sized by the thinner conductor.
The same rule at the top of the range: every model with a 1.5~10 mm² branch is rated 75 A, all three of them, whether the main is 35, 50 or 95 mm².
So do not size a piercing clamp from the main conductor. Size it from the branch, then confirm the main fits.
Same body, double the rating
Two pairs in the table have identical L, B and H and different ratings:
| Body L×B×H | Models | Rating |
|---|---|---|
| 53 × 52 × 84 | JBC-16 |
250 A |
| 53 × 52 × 84 | JBC-16 |
300 A |
| 95 × 86 × 115 | JBC10-150 |
200 A |
| 95 × 86 × 115 | JBC10-150 |
400 A |
The second pair is the one that matters. Two 10 kV clamps, the same casting, the same 95 × 86 × 115 envelope, and one is rated at twice the current of the other. If you buy on dimensions alone you can end up with half the rating you needed and never see it on the drawing.
The difference is the branch groove: 2550 mm² against 70120 mm². Wider groove, more contact area, more current. Ask for the rating and the branch range, not just the size.
1 kV and 10 kV are not interchangeable
| 1 kV | 10 kV | |
|---|---|---|
| Range | 13 models | 11 models |
| Largest conductor | 240 mm² | 300 mm² |
| Bolts | 1 or 2 | 2 on every model |
| Height H | 49 to 103 | 113 to 136 |
| Smallest branch | 1.5 mm² | 16 mm² |
A 10 kV clamp is a taller body — 113 mm minimum against 103 mm maximum at 1 kV — because the insulation has to be thicker and the creepage longer. That is also why there is no single-bolt 10 kV model: one bolt cannot close a body that size evenly.
300 mm² exists only at 10 kV. A 1 kV branch from a 300 mm² main has to be built another way.
1.5 mm² branch exists only at 1 kV — the three 75 A models. There is no 10 kV clamp for a small control or metering tap.
When to use this instead of a wedge or a bolted clamp
| JBC piercing | JXD wedge | JBT bolted | |
|---|---|---|---|
| Insulation | pierced, not stripped | stripped, cover fitted | stripped |
| Voltage | 1 kV and 10 kV | 1 kV | any |
| Conductor | insulated aluminium | aluminium and ACSR | copper or bimetallic |
| Fixing | 1 or 2 bolts | wedge, no bolts | 2 bolts per side |
Use JBC when the line is insulated and you want to tap it without stripping — a live-line branch, a service tee, a jumper. Use JXD when the run is 1 kV, the conductor is bare or you are willing to strip, and you want a joint with no thread to vibrate loose. Use JBT when the conductor is copper.
For a permanent grounding point on an insulated line, the clamp with a grounding eye rather than a branch groove is the JBCD grounding piercing clamp.