PF Power Fittings Technical Reference

JXD Wedge Type Parallel Groove Clamp

JXD wedge clamp, bare and with insulating cover

A two-piece aluminium clamp: a C-shaped body and a wedge that is driven into it. There are no bolts. The wedge is pushed home with a tool, the body springs open around both conductors, and the stored elastic energy in the aluminium keeps the joint tight for the life of the line.

The photograph shows both states — the bare wedge and body on the left, the same clamp with its insulating cover fitted on the right. The cover has four cable entries because the clamp is symmetric: either conductor may enter either side.

JXD installation tool

That second picture is the installation tool, not the clamp. It is the factory’s own tool and it is the reason the shell number matters, as explained below.

Where it is used

Overhead distribution at 1 kV and below — splicing or tapping insulated aluminium conductor and ACSR on a line that carries no tension. The clamp is not a tension fitting: it will hold the joint, not the line.

The insulating cover is what makes it usable on an insulated overhead line. Strip the insulation where the clamp sits, fit the clamp, close the cover. The joint then has insulation again, but it is not a sealed joint, so it belongs on a dry overhead run and not on a cable buried in the ground.

Ten shells, and the tool follows the shell

The factory states it plainly: the body is made in ten sizes, shell 1 to shell 10, and the tool is chosen by shell number, not by conductor.

Shell Tool
JXD-1 to JXD-6 small tool
JXD-7 to JXD-10 large tool

So a single job can need two tools. A line that goes from 35 mm² to 240 mm² crosses from shell 1 to shell 10 and will need both the small and the large tool on site. That is worth checking before mobilising a crew — one tool will not cover the whole schedule.

The shell number is in the middle of the code: JXD-8-403 is shell 8.

Pick your conductor table first

The same clamp covers four different conductor families, and each family has its own table because the conductor outside diameter differs for the same nominal area. Read down the column for one side and across the row for the other; the cell is the code.

Both sides are listed for the same conductor set because the clamp is symmetric — a -403 is the same part whichever conductor goes in which groove. That is why every table is filled only above the diagonal.

1. Insulated aluminium conductor, JKLYJ

Wire SpecificationJKLYJ-35JKLYJ-50JKLYJ-70JKLYJ-95JKLYJ-120JKLYJ-150JKLYJ-185JKLYJ-240
Wire Diameter (mm)78.41011.61314.616.218.4
JKLYJ-35JXD-1-104JXD-1-105JXD-2-107JXD-2-109JXD-4-201JXD-4-203JXD-7-302JXD-7-401
JKLYJ-50JXD-1-106JXD-2-109JXD-2-111JXD-4-203JXD-4-204JXD-7-303JXD-7-402
JKLYJ-70JXD-3-111JXD-3-113JXD-5-204JXD-5-205JXD-8-307JXD-8-403
JKLYJ-95JXD-3-115JXD-5-205JXD-5-206JXD-8-308JXD-8-404
JKLYJ-120JXD-6-206JXD-6-207JXD-9-309JXD-9-405
JKLYJ-150JXD-6-208JXD-9-310JXD-9-406
JKLYJ-185JXD-10-313JXD-10-407
JKLYJ-240JXD-10-409

2. Bare aluminium conductor, LJ and TJ

Wire SpecificationLJ(TJ)-35LJ(TJ)-50LJ(TJ)-70LJ(TJ)-95LJ(TJ)-120LJ(TJ)-150LJ(TJ)-185LJ(TJ)-240
Wire Diameter (mm)7.5910.812.4814.2515.7517.520
LJ(TJ)-35JXD-1-105JXD-1-106JXD-2-109JXD-2-111JXD-4-203JXD-4-204JXD-7-304JXD-7-402
LJ(TJ)-50JXD-1-108JXD-2-111JXD-2-113JXD-4-204JXD-4-205JXD-7-307JXD-7-403
LJ(TJ)-70JXD-3-113JXD-3-115JXD-5-205JXD-5-206JXD-8-308JXD-8-405
LJ(TJ)-95JXD-3-116JXD-5-206JXD-5-207JXD-8-309JXD-8-406
LJ(TJ)-120JXD-6-207JXD-6-209JXD-9-311JXD-9-407
LJ(TJ)-150JXD-6-210JXD-9-314JXD-9-408
LJ(TJ)-185JXD-10-316JXD-10-410
LJ(TJ)-240JXD-10-411

3. Insulated ACSR, JKLGYJ

Wire SpecificationJKLGYJ-35JKLGYJ-50JKLGYJ-70JKLGYJ-95JKLGYJ-120JKLGYJ-150JKLGYJ-185JKLGYJ-240
Wire Diameter (mm)7.759.1210.8312.9314.3215.8417.9620.52
JKLGYJ-35/6JXD-1-105JXD-1-106JXD-2-110JXD-2-112JXD-4-203JXD-4-204JXD-7-304JXD-7-403
JKLGYJ-50/8JXD-1-109JXD-2-111JXD-2-114JXD-4-204JXD-4-205JXD-7-307JXD-7-404
JKLGYJ-70/10JXD-3-113JXD-3-116JXD-5-205JXD-5-206JXD-8-308JXD-8-405
JKLGYJ-95/15, 95/20JXD-3-118JXD-5-207JXD-5-208JXD-8-311JXD-8-407
JKLGYJ-120/20, 120/25JXD-6-208JXD-6-209JXD-9-313JXD-9-408
JKLGYJ-150/20, 150/25JXD-6-210JXD-9-314JXD-9-409
JKLGYJ-185/25, 185/30JXD-10-316JXD-10-410
JKLGYJ-240/30, 240/40JXD-10-411

4. Bare ACSR, LGJ

Wire SpecificationLGJ-35/6LGJ-50/8LGJ-70/10LGJ-95LGJ-120LGJ-150LGJ-185LGJ-240
Wire Diameter (mm)8.169.611.413.6115.07, 15.7416.67, 17.118.9, 18.8821.6, 21.66
LGJ-35/6JXD-1-106JXD-1-107JXD-2-111JXD-2-114JXD-4-204JXD-4-205JXD-7-307JXD-7-404
LGJ-50/8JXD-1-110JXD-2-112JXD-2-115JXD-4-205JXD-4-206JXD-7-308JXD-7-405
LGJ-70/10JXD-3-114JXD-3-117JXD-5-206JXD-5-207JXD-8-310JXD-8-406
LGJ-95/15, 95/20JXD-3-119JXD-5-208JXD-5-209JXD-8-313JXD-8-408
LGJ-120/20, 120/25JXD-6-209JXD-6-210JXD-9-315JXD-9-409
LGJ-150/20, 150/25JXD-6-211JXD-9-316JXD-9-410
LGJ-185/25, 185/30JXD-10-318JXD-10-411
LGJ-240/30, 240/40JXD-10-412

The code has five parts, and three of them are not enough

JXD-8-403 reads as: series JXD, shell 8, then a three-digit groove code 403. Only the full string identifies a clamp.

28 of the 51 three-digit codes appear under more than one shell. They are different parts:

Three digits Shells it appears under Example
403 7 and 8 JXD-7-403 is LJ 50 × LJ 240; JXD-8-403 is JKLYJ 70 × JKLYJ 240
206 4, 5 and 6 JXD-4-206 is LGJ 50 × LGJ 150; JXD-6-206 is JKLYJ 120 × JKLYJ 120
313 8, 9 and 10 JXD-8-313 is LGJ 95 × LGJ 185; JXD-10-313 is JKLYJ 185 × JKLYJ 185
405 7, 8 and 9 JXD-7-405 is LJ 50 × LJ 240; JXD-9-405 is JKLYJ 120 × JKLYJ 240

An order that says “403” and stops there cannot be filled. Write the shell.

And the same code means different conductors in different tables

This is the part that catches people out. Take JXD-1-105, which appears in three of the four tables:

Table What JXD-1-105 joins
JKLYJ 35 mm² to 50 mm² insulated
LJ 35 mm² to 35 mm² bare
JKLGYJ 35 mm² to 35 mm² insulated ACSR

Same part in all three — the clamp does not care what the conductor is called, it cares what diameter it is. The 35 mm² insulated conductor is 7.0 mm, the bare one 7.5 mm, the ACSR 7.75 mm, and all three fit the same groove. All 34 codes that appear in more than one table carry a different conductor pair in each, because the same nominal area is a different diameter in each family.

So a quotation that says “JXD-1-105, quantity 200” is incomplete. State the conductor family and the two conductor sizes, and we will confirm the code against the right table. If you give us the code from the wrong table the clamp will still be the same part, but if you give us a conductor list we will check it properly.

Sizing rules that hold across all four tables

  • Outside diameter, not nominal area, decides the code. 35 mm² is 7.0 mm in JKLYJ, 7.5 mm in LJ, 7.75 mm in JKLGYJ and 8.16 mm in LGJ — four different codes for what a schedule calls the same conductor.
  • Each table has 36 useful cells, eight conductor sizes taken two at a time including a conductor with itself: 24 splicing combinations plus 8 self-joints.
  • The self-joint column is not one code per area. Joining 240 mm² to itself is JXD-10-409 in JKLYJ but JXD-10-412 in LGJ, because the ACSR is 3.2 mm larger.
  • The largest conductor is 240 mm² in all four families. There is no 300 in this series.

How it compares with the other two clamps on this site

JXD wedge JBC piercing JBT bolted
Fixing wedge, driven in bolt, one or two bolts, two per side
Insulation stripped, then cover fitted pierced, not stripped stripped
Voltage 1 kV 1 kV and 10 kV any
Conductor aluminium and ACSR to 240 mm² insulated aluminium to 300 mm² copper, or bimetallic

Choose JXD when the line is insulated overhead, the conductor is aluminium, and you want a joint that cannot work loose under vibration — a wedge has no thread to shake out. Choose JBC when you cannot strip the insulation, typically on a live-line branch. Choose JBT when the conductor is copper or the joint is copper to aluminium.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: