JY-LY Splice Tube

Models: JY-35LY – JY-300LY and JY-70/10 – JY-240/30 · Conductor: JKLYJ-35 – JKLGYJ-240/30

JY-LY Splice Tube

An Insulated Splice Is A Splice Plus A Cover

Two tables sit on this page, and both are for insulated overhead line — JKLYJ and JKLGYJ, the covered-conductor types. That matters because a splice on covered conductor leaves a bare metal joint in the middle of an insulated run, so the cover is part of the assembly, not an accessory.

The first table carries the interesting column: Matching Insulation Cover.

Sleeve Cover
JY-35LY, JY-50LY JY-35/50
JY-70LY, JY-95LY JY-70/95
JY-120LY, JY-150LY JY-120/150
JY-185LY, JY-240LY JY-185/240
JY-300LY JY-300

Nine sleeves, five covers. Each cover spans two adjacent sizes, except the largest which stands alone.

So ordering one sleeve leaves you with a bare joint. Ask for the sleeve and its cover as a pair — the cover is not implied by the model number and does not appear in the sleeve’s own dimensions.

Note also that JY-35LY and JY-50LY share the same 20 mm tube diameter and differ only in length, 130 against 140 mm. One cover covers both, which is the reason they are paired.

The Second Table Is Two-Piece

The lower table is for JKLGYJ — covered ACSR, with a steel core — and it prints two sets of dimensions:

  • L / D / d — the outer aluminium sleeve, 360 to 570 mm long.
  • L1 / D1 / d1 — a short inner sleeve, 110 to 170 mm long.

The inner sleeve goes over the steel core first, then the outer over the whole conductor. d1 is the steel-core bore, and it tracks the core closely:

Conductor Steel area Core diameter d1
JKLGYJ-70/10 10 mm² 3.8 4.5
JKLGYJ-120/20 20 mm² 5.4 6.2
JKLGYJ-240/30 30 mm² 6.5 7.9

A consistent 0.7 to 1.4 mm of clearance, exactly as you would want for a compression fit over the core. This is the column to check if a joint is failing on the steel — an inner sleeve whose d1 is more than about 1.5 mm over the core will not grip it.

Compare that with the JYB bare-conductor sheet, where the same kind of second dimension set does not track the steel area at all. Here it does; there it does not. Trust this one.

The Codes Repeat The Bare-Conductor Numbers

This is the trap on the page. The second table’s models are JY-70/10, JY-95/15, JY-120/20, JY-150/25, JY-185/25, JY-240/30 — the exact format used on the bare-conductor splice sheets, where a JY-150/25 is an uncovered sleeve for LGJ-150/25.

On this page JY-150/25 is an insulated two-piece splice for JKLGYJ-150/25 — two sleeves, a 500 mm outer, plus a cover. The identical string on the bare-conductor sheets denotes a single uncovered sleeve for LGJ-150/25.

So the same model string means two different parts depending on which sheet it came from. Quote the page, not just the code, and if a purchase order says JY-150/25 with no other context, confirm whether the run is covered or bare before it is made.

The upper table’s codes avoid this by carrying the LY suffix. That is the marker for an insulated splice — if the model has no LY, it is not from this table.

Grip

The first table rates 4.9 kN on a 35 mm² covered conductor up to 38.7 kN on 300 mm²; the second runs 21.0 to 68.0 kN. Both are well below the bare-conductor sleeves of the same size, which is expected: an insulated overhead line runs at lower tension than a bare transmission conductor, and these fittings are sized for distribution duty.

Do not substitute an LY sleeve onto a bare conductor on the strength of a higher grip claim from another sheet — the two are rated for different service.

Technical Parameters

JY-LY Splice Tube JY-LY Splice Tube JY-LY Splice Tube

ModelApplicable WireMain Dimensions (mm)Grip Force (kN)Matching Insulation Cover
dDL
JY-35LYJKLYJ-357.6201304.9JY-35/50
JY-50LYJKLYJ-509.0201406.7JY-35/50
JY-70LYJKLYJ-7011.0221709.8JY-70/95
JY-95LYJKLYJ-9512.52418013.0JY-70/95
JY-120LYJKLYJ-12014.02621016.5JY-120/150
JY-150LYJKLYJ-15015.52824020.0JY-120/150
JY-185LYJKLYJ-18517.03226025.4JY-185/240
JY-240LYJKLYJ-24019.53429033.0JY-185/240
JY-300LYJKLYJ-30022.03631038.7JY-300
ModelApplicable WireMain Dimensions (mm)Grip Force (kN)
LDdL1D1d1
JY-70/10JKLGYJ70/103602613.0110124.521.0
JY-95/15JKLGYJ95/154302615.0130145.731.5
JY-120/20JKLGYJ120/204303016.0130146.236.9
JY-150/25JKLGYJ150/255003018.5150147.048.7
JY-185/25JKLGYJ185/255203220.5150147.053.5
JY-240/30JKLGYJ240/305703623.0170167.968.0

Bare aluminium conductor sleeves: JY-L, JT-L. Bare ACSR: JT, JYB. Covers for insulated joints: YG conductor fixing clamp.

Note: Nine sleeves share five insulation covers, so a sleeve alone leaves a bare joint — order the pair. JY-35LY and JY-50LY are the same 20 mm tube in two lengths. The lower table is two-piece and its d1 tracks the steel core to within 1.4 mm. Its codes repeat the bare-conductor format, so a JY-150/25 here is not the JY-150/25 on the bare sheet; the LY suffix marks the insulated range.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: