YG GP YG GPS Conductor Fixing Clamp

Models: YG-GPS15/1 – YG-GPS15/5, YG-GP15/1 – /5, YG-GP20/1 – /5 · Wire: 25–300 mm² · Voltage: 1 kV and 10 kV

The Same Five Clamps, Three Times

There are three tables and they are not three products. The wire data in all three is identical — the same clamps, the same outer diameters, the same wire sizes, the same bolts.

What changes is one column: the matching insulator.

Table Prefix Insulator
1 YG-GPS15/1 – /5 PS15
2 YG-GP15/1 – /5 P15
3 YG-GP20/1 – /5 P20

So there are five clamp bodies and three insulator fits — fifteen part numbers. The S in GPS is the PS-type insulator; the plain GP15 and GP20 are the two pin insulators.

Order the code that matches the insulator on your pole. The clamp half is the same on all three sheets, which means a GPS15/3 and a GP20/3 are the same clamp and differ only in the shape of the seat that goes over the insulator.

Choose by Outer Diameter, Not by mm²

This is the part that catches people out. The table carries two wire columns per voltage class — outer diameter and cross-section — and the same clamp covers very different mm² at 1 kV and at 10 kV:

Wire 1 kV OD 1 kV clamp 10 kV OD 10 kV clamp
25 mm² 8.4 mm /1 14.8 mm /2
50 mm² 11.2 /1 17.1 /2
70 mm² 12.8 /2 18.8 /3
95 mm² 14.8 /2 20.4 /3
120 mm² 16.2 /2 21.8 /4
150 mm² 18.2 /3 23.4 /4
185 mm² 20.2 /3 25.0 /5
240 mm² 22.6 /4 27.2 /5
300 mm² — — 29.4 /5

A 120 mm² conductor takes clamp /2 at 1 kV and clamp /4 at 10 kV. The 10 kV insulation roughly doubles the diameter of the same conductor, and these clamps grip the outside of the insulation.

So the mm² column is a cross-reference for the buyer, and the diameter column is the specification. If a client gives you only a cross-section, you cannot size the clamp without also knowing the voltage class and the cable type.

The Diameter Bands Are Contiguous Per Clamp

Read the OD ranges per clamp and they do not overlap:

  • /1 8.4–11.2 mm
  • /2 12.8–17.1 mm
  • /3 18.2–20.4 mm
  • /4 21.8–23.4 mm
  • /5 25.0–29.4 mm

The gaps between those bands — 11.2 to 12.8, 20.4 to 21.8, 23.4 to 25.0 — are not missing sizes. They are the diameters where no standard covered conductor exists at either voltage.

That makes the selection mechanical: measure the OD, find the band, take that clamp. No table lookup needed.

Nylon, and What That Buys

The note says high-strength reinforced nylon, and that is the whole point of the product: a metal clamp on a covered conductor is a metal loop around a conductor, and the insulation has to be restored around it. A nylon clamp is already the insulation.

It also carries a self-weight release function — the clamp is designed to let the conductor slip rather than drag a pole down if a span comes away. That is a safety feature, not a clamping failure, and it is the reason the bolts are M8 rather than something heavier.

M8×35 to M8×55, one size per clamp, and the bolt length grows with the clamp — a longer clamp needs a longer bolt to reach through.

Technical Parameters

YG-GPS15, for PS15 insulators

YG GP YG GPS Conductor Fixing Clamp YG GP YG GPS Conductor Fixing Clamp

SpecificationMatching InsulatorOverhead Insulated Aluminum Wire 1kVOverhead Insulated Aluminum Wire 10kVHexagon Bolt Specification
Outer Diameter (mm)Wire Specification (mm2)Outer Diameter (mm)Wire Specification (mm2)
YG-GPS15/1PS158.425M8X35
9.835
11.250
YG-GPS15/2PS1512.87014.825M8X40
14.89515.835
16.212017.150
YG-GPS15/3PS1518.215018.870M8X45
20.218520.495
YG-GPS15/4PS1522.624021.8120M8X50
23.4150
YG-GPS15/5PS1525.0185M8X55
27.2240
29.4300

YG-GP15, for P15 insulators

YG GP YG GPS Conductor Fixing Clamp YG GP YG GPS Conductor Fixing Clamp

SpecificationMatching InsulatorOverhead Insulated Aluminum Wire 1kVOverhead Insulated Aluminum Wire 10kVHexagon Bolt Specification
Outer Diameter (mm)Wire Specification (mm2)Outer Diameter (mm)Wire Specification (mm2)
YG-GP15/1P158.425M8X35
9.835
11.250
YG-GP15/2P1512.87014.825M8X40
14.89515.835
16.212017.150
YG-GP15/3P1518.215018.870M8X45
20.218520.495
YG-GP15/4P1522.624021.8120M8X50
23.4150
YG-GP15/5P1525.0185M8X55
27.2240
29.4300

YG-GP20, for P20 insulators

YG GP YG GPS Conductor Fixing Clamp YG GP YG GPS Conductor Fixing Clamp

SpecificationMatching InsulatorOverhead Insulated Aluminum Wire 1kVOverhead Insulated Aluminum Wire 10kVHexagon Bolt Specification
Outer Diameter (mm)Wire Specification (mm2)Outer Diameter (mm)Wire Specification (mm2)
YG-GP20/1P208.425M8X35
9.835
11.250
YG-GP20/2P2012.87014.825M8X40
14.89515.835
16.212017.150
YG-GP20/3P2018.215018.870M8X45
20.218520.495
YG-GP20/4P2022.624021.8120M8X50
23.4150
YG-GP20/5P2025.0185M8X55
27.2240
29.4300

Insulated covers and grounding for the same lines: JDL grounding clamp. Cable clamps for bare HV cable: JGH, JGP, JGW. Installation diagrams for covered conductor: Insulated conductor fitting installation diagrams.

Note: the three tables are the same five clamps with three insulator fits — fifteen part numbers, five bodies. Size by cable outer diameter: a 120 mm² conductor is clamp /2 at 1 kV and clamp /4 at 10 kV. The nylon body is the insulation, and the clamp releases under its own weight rather than pulling a pole over.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: