XGU-F Abrasion Resistant Suspension Clamp


Models: XGU-1F – XGU-6F, 5AF – 6AF, 5BF – 7BF (11 sizes) · Conductor: 5–48.7 mm · Nominal Failure Load: 40–60 kN · Reference Weight: 1.7–6.4 kg
The F suffix marks the abrasion resistant version. The difference from a plain XGU is the interface between clamp and conductor: instead of bare cast iron at the groove, the conductor sits on a liner, and the keeper bears on it through a wider face.
That matters on ACSR that moves. A suspension clamp is not supposed to grip, so under differential ice load or a gust the conductor does slide a few millimetres in the groove. Over a few thousand cycles the outer aluminium strands fret against the cast surface, the zinc-adjacent layer wears, and the strand that carries the tension at the mouth of the groove thins. The liner is what stands between the conductor and that wear.
Technical Parameters
F series — plain hanger, 1F to 6F
| Model | Applicable Conductor Diameter (Including Wrapping) (mm) | Main Dimensions (mm) | Nominal Failure Load (kN) | Reference Weight (kg) | ||
|---|---|---|---|---|---|---|
| L | R | H | ||||
| XGU-1F | 5.0~7.0 | 180 | 4.0 | 82 | 40 | 1.7 |
| XGU-2F | 7.1~13.0 | 200 | 7.0 | 102 | 40 | 2.0 |
| XGU-3F | 13.1~21.0 | 220 | 11.0 | 121 | 40 | 2.7 |
| XGU-4F | 21.1~26.0 | 250 | 13.5 | 130 | 40 | 3.4 |
| XGU-5F | 23.0~33.0 | 300 | 17.0 | 140 | 60 | 4.5 |
| XGU-6F | 34.0~45.0 | 300 | 23.0 | 155 | 60 | 5.1 |


AF series — ball socket top
| Model | Applicable Conductor Diameter (Including Wrapping) (mm) | Main Dimensions (mm) | Nominal Failure Load (kN) | Reference Weight (kg) | ||
|---|---|---|---|---|---|---|
| L | R | H | ||||
| XGU-5AF | 23.0~33.0 | 300 | 17 | 210 | 60 | 5.7 |
| XGU-6AF | 34.0~45.0 | 300 | 23 | 220 | 60 | 6.1 |


BF series — U-shackle top
| Model | Applicable Conductor Diameter (Including Wrapping) (mm) | Main Dimensions (mm) | Nominal Failure Load (kN) | Reference Weight (kg) | ||
|---|---|---|---|---|---|---|
| L | R | H | ||||
| XGU-5BF | 23.0~33.0 | 300 | 17 | 190 | 60 | 5.4 |
| XGU-6BF | 34.0~45.0 | 300 | 23 | 205 | 60 | 5.8 |
| XGU-7BF | 45.0~48.7 | 300 | 26 | 310 | 60 | 6.4 |
Which of the Three You Are Ordering
The F page is really three sub-families, and they are not interchangeable by name alone:
- F (1F to 6F) — the abrasion resistant body with a plain hanger. Six sizes, and the only branch that covers the small conductors: 1F starts at 5 mm.
- AF (5AF, 6AF) — the XGU-A ball socket top with the abrasion resistant treatment. Two sizes, 23 to 45 mm.
- BF (5BF, 6BF, 7BF) — the XGU-B U-shackle top with the abrasion resistant treatment. Three sizes, 23 to 48.7 mm, and the 7BF is the largest clamp in the whole XGU range.
So “XGU-5F”, “XGU-5AF” and “XGU-5BF” are three different fittings that all take a 23~33 mm conductor at 60 kN. The one you want depends on what the insulator string ends in, not on the conductor.
The Liner Costs Load on the Large Sizes
Compare the ratings across the two halves of the range:
| Size | Plain / A / B | F version | Change |
|---|---|---|---|
| 5 (23~33 mm) | 70 kN | 60 kN | −10 kN |
| 6 (34~45 mm) | 70 kN | 60 kN | −10 kN |
| 1 to 4 (5~26 mm) | 40 kN | 40 kN | none |
On the small sizes the abrasion resistant version is rated exactly as the plain clamp. On the two large sizes it is rated 60 kN where the A and B are 70 kN. If your string is a 70 kN design and you want the liner, you are looking at a de-rated clamp and the string rating has to follow it. Say so at the quote stage rather than discovering it in the type-test report.
Read the H Column With Care
Three things in this sheet follow a rule of their own, and they are worth knowing before you dimension a string from it.
H on the base F series is 20 mm above the plain clamp — except at 1F. XGU-2F is 102 against 82 for XGU-2, XGU-3F is 121 against 102, XGU-4F is 130 against 110. XGU-1F is 82, exactly the same as XGU-1. The smallest size does not raise the seat: on a 5 to 7 mm conductor there is nothing to be gained from it, and 82 mm is that clamp’s height. On a drawing it still has to be right.
The AF and BF heights are 53 to 62 mm above their A and B equivalents, at identical weight. 5AF is 210 against 157 for 5A, 5BF is 190 against 137 for 5B. A liner that adds no measurable mass adding 53 mm of height does not add up — these two columns are most likely measuring the overall height of the assembly rather than the pin-to-seat drop that H means everywhere else in this family.
XGU-7BF stands at H 156 mm, in the band of the 6BF above it. The 310 on that row is a slip: the 7BF is the 7B body with the abrasion resistant treatment, and a height above its own body length would mean the clamp stood off itself.
We quote these tables as printed because that is what the catalogue says. For any job where the string height matters, ask us for the dimensioned drawing with the quotation and we will send the assembly we actually build rather than the number in the column.
Sizing Rule
R works the same way as the rest of the family — half the largest conductor diameter plus half a millimetre — and the liner does not change it:
| Model | Range (mm) | Upper ÷ 2 + 0.5 | R listed |
|---|---|---|---|
| XGU-1F | 5.0~7.0 | 4.0 | 4.0 |
| XGU-2F | 7.1~13.0 | 7.0 | 7.0 |
| XGU-3F | 13.1~21.0 | 11.0 | 11.0 |
| XGU-4F | 21.1~26.0 | 13.5 | 13.5 |
| XGU-5F / 5AF / 5BF | 23.0~33.0 | 17.0 | 17 |
| XGU-6F / 6AF / 6BF | 34.0~45.0 | 23.0 | 23 |
| XGU-7BF | 45.0~48.7 | 24.9 | 26 |
The liner sits inside that radius, so the conductor outside diameter you size from is the wrapped diameter and does not change. Size from the wrapped bundle, pick the R, then pick the top fitting.
Material & Finish
- Body and keeper: malleable cast iron
- Liner: the conductor-facing abrasion resistant insert
- Cotter pin: stainless steel
- Remaining hardware: steel, hot-dip galvanized
- Finish: hot-dip galvanized to ISO 1461 on all iron and steel parts, minimum 65 μm
- Tolerance: ±0.5 mm on the groove and mounting interfaces, coating thickness checked to ISO 2178
- Certification: mill test certificates on request
Related Clamps
XGU center-pivoted — the plain version, 40 kN, 5 to 26 mm.
XGU-J aluminium alloy — alloy body and keeper for the same range, 24 to 46 percent lighter.
XCS twin conductor clamp — for bundles above the 48.7 mm ceiling of this family.