JTL Copper Aluminium Connection Clamp

Models: JTL-100A to JTL-1000A (8 sizes) · Conductor: 16 – 185 mm² · Body: copper-aluminium bimetal
The Number Is Amps
JTL-100A is a 100 amp clamp, not a 100 mm² one. The trailing A is the unit, and the eight models run 100, 200, 300, 400, 500, 600, 800 and 1000 A.
They map onto conductor ranges in a clean ladder:
| Model | Rating | Conductor |
|---|---|---|
| JTL-100A | 100 A | 16 – 25 mm² |
| JTL-200A | 200 A | 25 – 35 mm² |
| JTL-300A | 300 A | 35 – 50 mm² |
| JTL-400A | 400 A | 50 – 70 mm² |
| JTL-500A | 500 A | 70 – 95 mm² |
| JTL-600A | 600 A | 95 – 120 mm² |
| JTL-800A | 800 A | 120 – 150 mm² |
| JTL-1000A | 1000 A | 150 – 185 mm² |
The ranges overlap at the boundaries — 25 mm² appears in both the 100 A and 200 A rows, 35 mm² in 200 A and 300 A, and so on up the table. That is deliberate: a conductor at the top of one range and the bottom of the next will physically fit both, and the choice is made on current, not on fit.
Size by the load, then confirm the conductor fits the range. Sizing by conductor alone will put you one step light on a heavily loaded feeder.
This JTL Is Not the 4-to-2 JTL
There are two unrelated families in this catalogue sharing the JTL prefix:
| This page | JTL 4 to 2 clamp | |
|---|---|---|
| Model format | JTL-100A | JTL-2/4-300/40-900K |
| Job | Bimetal connection clamp | Quad-to-twin bundle transition |
| Weight | not listed | 23.0 – 24.0 kg |
If a purchase order says “JTL” with no other detail, it could be either. Put the model format or the application on the enquiry.
Dimensions Step in Two Bands
| Column | Range | Behaviour |
|---|---|---|
| Ø | 10.5 – 14.5 mm | Bolt hole, steps at 500 A |
| L | 76 – 136 mm | Overall length, climbs every size |
| L1 | 40 – 75 mm | Clamp length, flat 68 mm at 500/600 A |
| W | 23 – 40 mm | Body width |
| A / A1 / A2 | 3.2 – 6.0 mm | Plate and gap dimensions |
Ø and L1 both step at the same place — the 10.5/12.5 mm hole runs from 100 A to 400 A, and 14.5 mm from 500 A up. That is the bolt size changing from M10 to M14, and it happens at 500 A because that is where the clamp needs a bigger bolt to carry the current.
L climbs monotonically, 76 to 136 mm, so the fitting does grow with rating. Nothing anomalous in this table — which is worth saying, because several other pages in this group are not so clean.
No Weight Column
The catalogue gives no reference weight for this family. That is unusual here — nearly every other fitting on these pages carries one — and it means we cannot quote freight from the catalogue.
Ask us for the weight when you order. For a bimetal clamp of this size expect roughly 0.1 to 0.6 kg depending on rating, but we will confirm rather than have you budget on an estimate.
Where It Is Used
- Copper cable into an aluminium busbar or lug — the primary case
- Equipment terminals where the stud is copper and the conductor is aluminium
- Meter and control panel wiring at the lower ratings
The bimetal body does the transition internally, so unlike a plain aluminium clamp with a composite washer, there is no separate interface to get wrong at installation.

Technical Parameters
| Model | Applicable Conductor (mm2) | Main Dimensions (mm) | ||||||
|---|---|---|---|---|---|---|---|---|
| Ø | L | L1 | W | A | A1 | A2 | ||
| JTL-100A | 16~25 | 10.5 | 76 | 40 | 23 | 3.2 | 2.7 | 3.5 |
| JTL-200A | 25~35 | 12.5 | 85 | 52 | 25 | 4.0 | 3.0 | 4.0 |
| JTL-300A | 35~50 | 12.5 | 95 | 58 | 29 | 4.2 | 3.5 | 4.5 |
| JTL-400A | 50~70 | 12.5 | 104 | 61 | 31 | 4.2 | 3.5 | 4.5 |
| JTL-500A | 70~95 | 14.5 | 109 | 68 | 33 | 4.5 | 4.0 | 5.0 |
| JTL-600A | 95~120 | 14.5 | 114 | 68 | 35 | 4.5 | 4.0 | 5.0 |
| JTL-800A | 120~150 | 14.5 | 125 | 75 | 35 | 5.0 | 4.0 | 5.5 |
| JTL-1000A | 150~185 | 14.5 | 136 | 75 | 40 | 5.0 | 4.5 | 6.0 |
Related Clamps
Copper-aluminium washers for bolted joints: TLYP composite sheet. Transition plates for busbar: MG copper aluminium transition plate. Bimetal T clamps: TJG insulated T clamp. Insulated cable branch: JFG transition branch clamp.
Note: The model number is the current rating. Ranges overlap at the boundaries — size by load, then check the conductor fits. No catalogue weight; ask us.