TJL / TJT / TJG Insulated Service T Clamp

Models: 1.1 to 4.4 (10 combinations) in three materials · Application: 10 kV insulated overhead cable branch
Three Materials, One Table
The catalogue prints one parameter table with the model written as TJL、TJT、TJG-1.1. That is not shorthand for one product — it is three products that share the same casting dimensions:
- TJL — aluminium body, for aluminium conductor on both legs
- TJT — copper body, for copper conductor
- TJG — bimetal, copper on one side and aluminium on the other, for a copper-to-aluminium transition
Because the dimensions are shared, the material letter is the only thing you select. There is no size difference between a TJL-2.1 and a TJG-2.1, and no weight difference to compare. What changes is the metal in contact with the conductor — and that is the whole point of having three.

Put a copper conductor into an aluminium body and you have made a galvanic cell at every joint on the line. TJG exists so you do not have to: aluminium side to the aluminium run, copper side to the copper tap, with the transition inside the fitting instead of at a bare connection.
The Number Is a Triangle Again
X.Y is main line X, branch Y, on a four-step ladder:
| Digit | Conductor section |
|---|---|
| 1 | 35 – 50 mm² |
| 2 | 70 – 95 mm² |
| 3 | 120 – 150 mm² |
| 4 | 185 – 240 mm² |
Ten rows exist and ten combinations are possible with the branch never larger than the run: 1+2+3+4 = 10. No 1.2, no 2.3, no 3.1 in reverse. A 120–150 mm² run tapped at 35–50 mm² is 3.1; the same run tapped at 185–240 mm² does not exist, because the branch is cast into the body.

One Cover Fits All Ten
The last column reads TJL、TJT、TJG50-240 on every single row. Ten models, one insulating cover.
That is worth more than it looks. A crew carrying the cover for a 1.1 also carries the cover for a 4.4, so a van does not have to stock ten boxes, and a wrong-size pull from the store does not stop the job. The cover is a 50–240 mm² class item; the clamp inside it is the part that changes.
10 kV Insulated Cable, Not Bare Conductor
This is a service-branch clamp for insulated overhead cable — the ABC and covered-conductor systems common on 10 kV distribution. It is not a bare-conductor tee. The insulating cover is not optional hardware; it is what makes the branch joint touch-safe, and it is specced with the clamp because the clamp body has the profile the cover clips onto.
For bare 10 kV and 35 kV work, the TL U-bolt T clamp is the corresponding fitting. For the insulated dead-ends that terminate the same cable, see the NXJ bundled insulated suspension clamp.
Technical Parameters
| Model | Applicable Conductor (mm2) | Matching Insulating Cover | |
|---|---|---|---|
| Main Conductor | Branch Conductor | ||
| TJL, TJT, TJG-1.1 | 35~50 | 35~50 | TJL, TJT, TJG50-240 |
| TJL, TJT, TJG-2.1 | 70~95 | 35~50 | TJL, TJT, TJG50-240 |
| TJL, TJT, TJG-2.2 | 70~95 | 70~95 | TJL, TJT, TJG50-240 |
| TJL, TJT, TJG-3.1 | 120~150 | 35~50 | TJL, TJT, TJG50-240 |
| TJL, TJT, TJG-3.2 | 120~150 | 70~95 | TJL, TJT, TJG50-240 |
| TJL, TJT, TJG-3.3 | 120~150 | 120~150 | TJL, TJT, TJG50-240 |
| TJL, TJT, TJG-4.1 | 185~240 | 35~50 | TJL, TJT, TJG50-240 |
| TJL, TJT, TJG-4.2 | 185~240 | 70~95 | TJL, TJT, TJG50-240 |
| TJL, TJT, TJG-4.3 | 185~240 | 120~150 | TJL, TJT, TJG50-240 |
| TJL, TJT, TJG-4.4 | 185~240 | 185~240 | TJL, TJT, TJG50-240 |
Note: Specify which of the three material letters you need and the conductor on each leg. The cover is ordered separately from the clamp — state the quantity of each.