PF Power Fittings Technical Reference

TJL / TJT / TJG Insulated Service T Clamp

TJL aluminium T clamp

Models: 1.1 to 4.4 (10 combinations) in three materials · Application: 10 kV insulated overhead cable branch

Three Materials, One Table

The catalogue prints one parameter table with the model written as TJL、TJT、TJG-1.1. That is not shorthand for one product — it is three products that share the same casting dimensions:

  • TJL — aluminium body, for aluminium conductor on both legs
  • TJT — copper body, for copper conductor
  • TJG — bimetal, copper on one side and aluminium on the other, for a copper-to-aluminium transition

Because the dimensions are shared, the material letter is the only thing you select. There is no size difference between a TJL-2.1 and a TJG-2.1, and no weight difference to compare. What changes is the metal in contact with the conductor — and that is the whole point of having three.

TJT copper T clamp

Put a copper conductor into an aluminium body and you have made a galvanic cell at every joint on the line. TJG exists so you do not have to: aluminium side to the aluminium run, copper side to the copper tap, with the transition inside the fitting instead of at a bare connection.

The Number Is a Triangle Again

X.Y is main line X, branch Y, on a four-step ladder:

Digit Conductor section
1 35 – 50 mm²
2 70 – 95 mm²
3 120 – 150 mm²
4 185 – 240 mm²

Ten rows exist and ten combinations are possible with the branch never larger than the run: 1+2+3+4 = 10. No 1.2, no 2.3, no 3.1 in reverse. A 120–150 mm² run tapped at 35–50 mm² is 3.1; the same run tapped at 185–240 mm² does not exist, because the branch is cast into the body.

TJG bimetal T clamp

One Cover Fits All Ten

The last column reads TJL、TJT、TJG50-240 on every single row. Ten models, one insulating cover.

That is worth more than it looks. A crew carrying the cover for a 1.1 also carries the cover for a 4.4, so a van does not have to stock ten boxes, and a wrong-size pull from the store does not stop the job. The cover is a 50–240 mm² class item; the clamp inside it is the part that changes.

10 kV Insulated Cable, Not Bare Conductor

This is a service-branch clamp for insulated overhead cable — the ABC and covered-conductor systems common on 10 kV distribution. It is not a bare-conductor tee. The insulating cover is not optional hardware; it is what makes the branch joint touch-safe, and it is specced with the clamp because the clamp body has the profile the cover clips onto.

For bare 10 kV and 35 kV work, the TL U-bolt T clamp is the corresponding fitting. For the insulated dead-ends that terminate the same cable, see the NXJ bundled insulated suspension clamp.

Technical Parameters

ModelApplicable Conductor (mm2)Matching Insulating Cover
Main ConductorBranch Conductor
TJL, TJT, TJG-1.135~5035~50TJL, TJT, TJG50-240
TJL, TJT, TJG-2.170~9535~50TJL, TJT, TJG50-240
TJL, TJT, TJG-2.270~9570~95TJL, TJT, TJG50-240
TJL, TJT, TJG-3.1120~15035~50TJL, TJT, TJG50-240
TJL, TJT, TJG-3.2120~15070~95TJL, TJT, TJG50-240
TJL, TJT, TJG-3.3120~150120~150TJL, TJT, TJG50-240
TJL, TJT, TJG-4.1185~24035~50TJL, TJT, TJG50-240
TJL, TJT, TJG-4.2185~24070~95TJL, TJT, TJG50-240
TJL, TJT, TJG-4.3185~240120~150TJL, TJT, TJG50-240
TJL, TJT, TJG-4.4185~240185~240TJL, TJT, TJG50-240

Note: Specify which of the three material letters you need and the conductor on each leg. The cover is ordered separately from the clamp — state the quantity of each.

Sizing data behind this page

The sizes above are nominal. What a conductor of that nominal size actually measures — outer diameter, calculated breaking load, weight per kilometre — is what a clamp groove or a sleeve bore is matched against, and it is in these tables: